Draga SlovenijaDraga Slovenija

Drinking water in the Central Slovenia region

In 2024–2026 the state monitoring took 1,575 samples in the Central Slovenia region, across 144 supply areas; 128 (8.1%) were not compliant. The median estimated hardness is 15 °dH.

Samples 2024–20261,575144 supply areas
Non-compliant1288.1%
Municipalities with repeated non-compliance0of 24
Hardness (estimate)15 °dHhard

Municipalities in the Central Slovenia region

MunicipalityRatingSamplesNon-compliantHardness (°dH)Nitrate (mg/L)
Borovnicaoccasional non-compliance48817 hard4.65
Brezovicaoccasional non-compliance74614.2 hard5.8
Dobrepoljeoccasional non-compliance10116.3 hard4.45
Dobrova - Polhov Gradecoccasional non-compliance821311.6 moderately hard4.25
Dol pri Ljubljanioccasional non-compliance60415.8 hard9.7
Domžaleoccasional non-compliance110216.7 hard6.7
Grosupljemostly compliant74217.6 hard4.65
Horjuloccasional non-compliance30315.1 hard3.55
Igmostly compliant36318.1 hard4.9
Ivančna Goricaoccasional non-compliance53116.7 hard3.6
Kamnikoccasional non-compliance144257.1 soft3.8
Komendaoccasional non-compliance3516.2 soft3.45
Ljubljanaoccasional non-compliance5852714.6 hard12
Logatecmostly compliant62315.1 hard4.4
Lukovicaoccasional non-compliance28516.4 hard6.05
Medvodeoccasional non-compliance721215.9 hard7.5
Mengešoccasional non-compliance80217.2 hard24
Moravčecompliant10017.5 hard4.55
Škofljicaoccasional non-compliance97414.7 hard12
Šmartno pri Litijioccasional non-compliance66914.8 hard3.5
Trzinoccasional non-compliance70117.5 hard27
Velike Laščemostly compliant33117.7 hard4
Vodicecompliant1909.4 moderately hard4.6
Vrhnikaoccasional non-compliance69716.9 hard4

Measured values

ParameterHighest valueAgainst the limit
E. coli>80 per 100 mLlimit 0 per 100 mL · 1,575 samples · 20× over the limit
Enterococci72 per 100 mLlimit 0 per 100 mL · 1,575 samples · 28× over the limit
Coliform bacteria>80 per 100 mLlimit 0 per 100 mL · 1,575 samples · 90× over the limit
Clostridium perfringens9 per 100 mLlimit 0 per 100 mL · 421 samples · 14× over the limit
Nitrate31 mg/Llimit 50 mg/L · 273 samples
Nitrite0.11 mg/Llimit 0.5 mg/L · 267 samples
Nitrate/50 + nitrite/30.62limit 1 · 269 samples
Single pesticide (highest)0.052 µg/L (Desetil-atrazin)limit 0.1 µg/L · 12 samples
Pesticides, total0.086 µg/Llimit 0.5 µg/L · 6 samples
PFAS, totalbelow 0.03 µg/Llimit 0.5 µg/L · 17 samples
PFOA0.0021 µg/Lpart of the 20-PFAS sum, limit 0.1 µg/L · 19 samples
PFOS0.0083 µg/Lpart of the 20-PFAS sum, limit 0.1 µg/L · 19 samples
Lead16 µg/Llimit 10 µg/L · 100 samples · 2× over the limit
Arsenicbelow 1 µg/Llimit 10 µg/L · 154 samples
Uranium0.92 µg/Llimit 30 µg/L · 83 samples
Copper0.068 mg/Llimit 2 mg/L · 154 samples
Nickel2.7 µg/Llimit 20 µg/L · 83 samples
Cadmium0.078 µg/Llimit 5 µg/L · 154 samples
Chromium16 µg/Llimit 50 µg/L · 154 samples
Antimonybelow 1 µg/Llimit 10 µg/L · 154 samples
Selenium2.3 µg/Llimit 20 µg/L · 154 samples
Boron0.048 mg/Llimit 1.5 mg/L · 154 samples
Fluoride0.19 mg/Llimit 1.5 mg/L · 271 samples
Trihalomethanes, total19 µg/Llimit 100 µg/L · 86 samples
Haloacetic acids18 µg/Llimit 60 µg/L · 17 samples
Bromatebelow 2 µg/Llimit 10 µg/L · 1 sample
Chlorate0.48 mg/Llimit 0.25 mg/L · 51 samples · 2× over the limit
Chloritebelow 0.01 mg/Llimit 0.25 mg/L · 51 samples
Tetrachloroethene + trichloroethene1.5 µg/Llimit 10 µg/L · 45 samples
Bisphenol Abelow 0.025 µg/Llimit 2.5 µg/L · 3 samples
Free chlorine0.38 mg/Lno limit value · 531 samples
Manganese2.9 µg/Llimit 50 µg/L · 154 samples
Iron53 µg/Llimit 200 µg/L · 154 samples
Aluminium58 µg/Llimit 200 µg/L · 158 samples
Ammonium0.026 mg/Llimit 0.5 mg/L · 273 samples
Chloride45 mg/Llimit 250 mg/L · 273 samples
Sulphate180 mg/Llimit 250 mg/L · 273 samples
Sodium24 mg/Llimit 200 mg/L · 154 samples
pH6.3–8.3limit 6.5–9.5 · 1,575 samples · 2× outside the range
Electrical conductivity748 µS/cmlimit 2,500 µS/cm · 1,575 samples

Samples by year

03456892016: 689 samples, 62 non-compliant’162017: 683 samples, 64 non-compliant’172018: 689 samples, 64 non-compliant’182019: 688 samples, 63 non-compliant’192020: 630 samples, 60 non-compliant’202021: 616 samples, 41 non-compliant’212022: 621 samples, 63 non-compliant’222023: 622 samples, 53 non-compliant’232024: 608 samples, 51 non-compliant’242025: 624 samples, 59 non-compliant’252026: 343 samples, 18 non-compliant’26
compliant non-compliant · Samples in the Central Slovenia region

How to read the results

The ratings are a Draga Slovenija summary, not an official NIJZ rating.

Other regions

Source: NIJZ and NLZOH, mpv.si; latest sample 31 Aug 2026. Processing: Draga Slovenija.

Frequently asked questions

What is the drinking water like in the Central Slovenia region?

In 2024–2026 the state monitoring took 1,575 samples in the Central Slovenia region, across 144 supply areas; 128 (8.1%) were not compliant.

Where is the water hardest in the Central Slovenia region?

By estimate Ig (18.1 °dH), Velike Lašče (17.7 °dH), Grosuplje (17.6 °dH).

AI chat

Ask the data, in plain language

The AI chat finds the answer in the official register and shows it with a table you can download and a link into the map. Free; it only needs an account.

For example: Which municipalities issued the most building permits last year?

Open the AI chat

AI chat