Draga SlovenijaDraga Slovenija

Drinking water in Medvode

Occasional non-compliance

In 2024–2026 the state monitoring took 72 samples of drinking water on the 11 supply areas serving the municipality, of which 12 were not compliant (E. coli or enterococci bacteria in 1 sample). By the operators’ figures and our estimate the water is hard (≈15.9 °dH).

These are state monitoring results from 2024–2026, not a notice about the water today. Current notices (boil-water, do-not-use) are published by the water-system operator on its website.

Samples 2024–20267211 supply areas
Non-compliant1217%
Hardness (operator and estimate)15.9 °dHhard
Nitrate, median7.5 mg/Llimit 50 mg/L
Hardness for settlements the operator lists separately (32)
SettlementHardnessBand
Belo15–16 °dHhard
Brezovica pri Medvodah11.5–12.5 °dHmoderately hard
Dol15–17 °dHhard
Dragočajna9–12 °dHmoderately hard
Golo Brdo18 °dHhard
Goričane15–17 °dHhard
Hraše9–12 °dHmoderately hard
Ladja15–17 °dHhard
Medvode15–17 °dHhard
Moše8–12 °dHmoderately hard
Ojstrica15–16 °dHhard
Osolnik18–19 °dHhard
Osolnik17–18 °dHhard
Rakovnik15–17 °dHhard
severni del vasi15–16 °dHhard
Smlednik (Brezovec)15–17 °dHhard
Sora15–17 °dHhard
Spodnja Senica15–17 °dHhard
Spodnje Pirniče15–17 °dHhard
Studenčice12–15 °dHmoderately hard
Topol pri Medvodah11–13 °dHmoderately hard
Topol pri Medvodah11.5–12.5 °dHmoderately hard
Trnovec15–16 °dHhard
Valburga9–12 °dHmoderately hard
Vaše15–17 °dHhard
Verje15–17 °dHhard
Vikrče15–17 °dHhard
Zbilje15–17 °dHhard
Zgornja Senica15–17 °dHhard
Zgornje Pirniče15–17 °dHhard
Žlebe14–16 °dHhard
Žlebe – zgornji del vasi12–15 °dHmoderately hard

Source: JP VOKA SNAGA d.o.o.

Water systems in Medvode

In 2024–2026 the state monitoring sampled 11 supply areas; the largest, MEDVODE, supplies 13,554 users. The address search shows the nearest sampling points, not necessarily your water system; the system that supplies you is named on your water bill.

Supply areas at a glance
AreaUsersRating
MEDVODE13,554occasional non-compliance
ŽLEBE300repeated non-compliance
ŽLEBE - SENIČICA230repeated non-compliance
TOPOL204compliant
STUDENČICE154compliant
GOLO BRDO - POLANA142compliant
ŽLEBE - PLANINA - JETERBENK #2140Faecal bacteria in 1 sample
Trnovec - Govejek100compliant
GOLO BRDO54compliant
BELO53occasional non-compliance
Osolnik16compliant
MEDVODE: occasional non-complianceMEDVODE: occasional non-complianceMEDVODE: occasional non-complianceŽLEBE: repeated non-complianceŽLEBE: repeated non-complianceŽLEBE - SENIČICA: repeated non-complianceTOPOL: compliantTOPOL: compliantSTUDENČICE: compliantGOLO BRDO - POLANA: compliantŽLEBE - PLANINA - JETERBENK #2: occasional non-complianceTrnovec - Govejek: compliantGOLO BRDO: compliantMedvodeSvetjeOsolnikŽlebeStudenčiceGolo BrdoZgornje PirničeSpodnje PirničeZbiljeValburgaŠkofja LokaKranjDobrova-Polhov GradecŠenčur5 km
  • compliant
  • occasional non-compliance
  • repeated non-compliance

Sampling points of the state monitoring in recent years, coloured by the result for the area. Click a dot for the area's figures. Place names © OpenStreetMap

MEDVODE

Occasional non-compliance

Operator: JP VOKA SNAGA · 13,554 users · water system Medvode

Samples 2024–2026
28, 6 non-compliant
Water source
Groundwater, not influenced by surface water
Treatment
Occasional disinfection, sodium hypochlorite disinfection
Hardness (operator)
15–17 °dH, hard source
Latest sample
27 Aug 2026
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 28 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 28 samples
Nitrate12 mg/Llimit 50 mg/L · 5 samples
PFAS, totalbelow 0.03 µg/Llimit 0.5 µg/L · 1 sample
PFOA0.0006 µg/Lpart of the 20-PFAS sum, limit 0.1 µg/L · 1 sample
PFOS0.0006 µg/Lpart of the 20-PFAS sum, limit 0.1 µg/L · 1 sample
Arsenicbelow 1 µg/Llimit 10 µg/L · 5 samples
Manganesebelow 1 µg/Llimit 50 µg/L · 5 samples
Ironbelow 10 µg/Llimit 200 µg/L · 5 samples
Non-compliant samples (6)
  • · Coliform bacteria >80 per 100 mL limit 0 per 100 mL
  • · marked non-compliant; the published data gives no reason
  • · marked non-compliant; the published data gives no reason
  • · Coliform bacteria 1 per 100 mL limit 0 per 100 mL
  • · Coliform bacteria 1 per 100 mL limit 0 per 100 mL
  • · Coliform bacteria 2 per 100 mL limit 0 per 100 mL

ŽLEBE

Repeated or health-relevant non-compliance

Operator: JP VOKA SNAGA · 300 users · water system Žlebe

Samples 2024–2026
6, 1 non-compliant
Water source
Groundwater, not influenced by surface water
Treatment
Regular disinfection, sodium hypochlorite disinfection
Hardness (operator)
12–15 °dH, moderately hard source
Latest sample
27 Aug 2026
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 6 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 6 samples
Nitrate3.4 mg/Llimit 50 mg/L · 1 sample
Lead16 µg/Llimit 10 µg/L · 3 samples · 1× over the limit
Non-compliant samples (1)
  • · Lead 16 µg/L limit 10 µg/L

ŽLEBE - SENIČICA

Repeated or health-relevant non-compliance

Operator: Občina Medvode · 230 users · water system Žlebe - Seničica

Samples 2024–2026
5, 3 non-compliant
Water source
Influenced by surface water
Treatment
Sodium hypochlorite disinfection
Hardness (estimate)
≈18.1 °dH, hard
Latest sample
27 May 2026
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 5 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 5 samples
Nitrate7.5 mg/Llimit 50 mg/L · 1 sample
Lead15 µg/Llimit 10 µg/L · 2 samples · 1× over the limit
Non-compliant samples (3)
  • · marked non-compliant; the published data gives no reason
  • · Lead 15 µg/L limit 10 µg/L
  • · Coliform bacteria 11 per 100 mL limit 0 per 100 mL

TOPOL

All samples compliant

Operator: JP VOKA SNAGA · 204 users · water system Topol

Samples 2024–2026
5, all compliant
Water source
Influenced by surface water
Treatment
Regular disinfection, sodium hypochlorite disinfection
Hardness (operator)
11.5–12.5 °dH, moderately hard source
Latest sample
10 Apr 2026
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 5 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 5 samples

STUDENČICE

All samples compliant

Operator: JP VOKA SNAGA · 154 users · water system Studenčice

Samples 2024–2026
4, all compliant
Water source
Groundwater, not influenced by surface water
Treatment
Sodium hypochlorite disinfection
Hardness (operator)
12–15 °dH, moderately hard source
Latest sample
24 Sep 2025
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 4 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 4 samples

GOLO BRDO - POLANA

All samples compliant

Operator: Občina Medvode · 142 users · water system Golo Brdo-Polana

Samples 2024–2026
4, all compliant
Water source
Influenced by surface water
Treatment
No treatment
Hardness (estimate)
≈17.5 °dH, hard
Latest sample
12 Nov 2025
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 4 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 4 samples
Lead0.93 µg/Llimit 10 µg/L · 2 samples

ŽLEBE - PLANINA - JETERBENK #2

Faecal bacteria in 1 sample

Operator: Društvo za varstvo voda ŽLEBE · 140 users · water system Žlebe - Planina - Jeterbenk

Samples 2024–2026
5, 1 non-compliant
Water source
Groundwater, not influenced by surface water
Treatment
Sodium hypochlorite disinfection
Hardness (estimate)
≈14.1 °dH, hard
Latest sample
24 Mar 2026
Measured values
E. coli1 per 100 mLlimit 0 per 100 mL · 5 samples · 1× over the limit
Enterococci3 per 100 mLlimit 0 per 100 mL · 5 samples · 1× over the limit
Non-compliant samples (1)
  • · E. coli 1 per 100 mL limit 0 per 100 mL, Enterococci 3 per 100 mL limit 0 per 100 mL, Coliform bacteria 55 per 100 mL limit 0 per 100 mL

Trnovec - Govejek

All samples compliant

Operator: Občina Medvode · 100 users · water system Trnovec - Govejek

Samples 2024–2026
5, all compliant
Water source
Influenced by surface water
Treatment
Sodium hypochlorite disinfection
Hardness (estimate)
≈14.6 °dH, hard
Latest sample
10 Apr 2026
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 5 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 5 samples
Nitrate2.5 mg/Llimit 50 mg/L · 1 sample
Leadbelow 1 µg/Llimit 10 µg/L · 3 samples

GOLO BRDO

All samples compliant

Operator: JP VOKA SNAGA · 54 users · water system Golo Brdo

Samples 2024–2026
5, all compliant
Water source
Influenced by surface water
Treatment
Regular disinfection, sodium hypochlorite disinfection
Hardness (operator)
18 °dH, hard source
Latest sample
21 Apr 2026
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 5 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 5 samples
Nitrate8.4 mg/Llimit 50 mg/L · 1 sample
Lead1.8 µg/Llimit 10 µg/L · 3 samples

BELO

Occasional non-compliance

Operator: JP VOKA SNAGA · 53 users · water system Belo

Samples 2024–2026
4, 1 non-compliant
Water source
Influenced by surface water
Treatment
Regular disinfection, UV disinfection
Hardness (operator)
15–16 °dH, hard source
Latest sample
24 Mar 2026
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 4 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 4 samples
Non-compliant samples (1)
  • · Coliform bacteria 42 per 100 mL limit 0 per 100 mL

Osolnik

All samples compliant

Operator: JP VOKA SNAGA · 16 users · water system Osolnik

Samples 2024–2026
1, all compliant
Water source
Groundwater, not influenced by surface water
Treatment
Regular disinfection, sodium hypochlorite disinfection, UV disinfection
Hardness (operator)
17–18 °dH, hard source
Latest sample
10 Apr 2026
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 1 sample
Enterococci0 per 100 mLlimit 0 per 100 mL · 1 sample

Measured values 2024–2026

The highest measured value of each parameter in the samples from the water systems that supply the municipality, and the share of the limit it reaches.

ParameterHighest valueAgainst the limit
E. coli1 per 100 mLlimit 0 per 100 mL · 72 samples · 1× over the limit
Enterococci3 per 100 mLlimit 0 per 100 mL · 72 samples · 1× over the limit
Coliform bacteria>80 per 100 mLlimit 0 per 100 mL · 72 samples · 7× over the limit
Clostridium perfringens0 per 100 mLlimit 0 per 100 mL · 21 samples
Nitrate12 mg/Llimit 50 mg/L · 9 samples
Nitritebelow 0.01 mg/Llimit 0.5 mg/L · 9 samples
Nitrate/50 + nitrite/30.24limit 1 · 9 samples
PFAS, totalbelow 0.03 µg/Llimit 0.5 µg/L · 1 sample
PFOA0.0006 µg/Lpart of the 20-PFAS sum, limit 0.1 µg/L · 1 sample
PFOS0.0006 µg/Lpart of the 20-PFAS sum, limit 0.1 µg/L · 1 sample
Lead16 µg/Llimit 10 µg/L · 13 samples · 2× over the limit
Arsenicbelow 1 µg/Llimit 10 µg/L · 5 samples
Uranium0.48 µg/Llimit 30 µg/L · 3 samples
Copper0.0022 mg/Llimit 2 mg/L · 5 samples
Nickelbelow 1 µg/Llimit 20 µg/L · 3 samples
Cadmium0.024 µg/Llimit 5 µg/L · 5 samples
Chromium1.5 µg/Llimit 50 µg/L · 5 samples
Antimonybelow 1 µg/Llimit 10 µg/L · 5 samples
Seleniumbelow 1 µg/Llimit 20 µg/L · 5 samples
Boron0.013 mg/Llimit 1.5 mg/L · 5 samples
Fluoridebelow 1 mg/Llimit 1.5 mg/L · 9 samples
Trihalomethanes, total5.3 µg/Llimit 100 µg/L · 2 samples
Haloacetic acids18 µg/Llimit 60 µg/L · 1 sample
Chloratebelow 0.01 mg/Llimit 0.25 mg/L · 1 sample
Chloritebelow 0.01 mg/Llimit 0.25 mg/L · 1 sample
Tetrachloroethene + trichloroethenebelow 0.2 µg/Llimit 10 µg/L · 2 samples
Free chlorine0.25 mg/Lno limit value · 21 samples
Manganesebelow 1 µg/Llimit 50 µg/L · 5 samples
Ironbelow 10 µg/Llimit 200 µg/L · 5 samples
Aluminium21 µg/Llimit 200 µg/L · 5 samples
Ammoniumbelow 0.02 mg/Llimit 0.5 mg/L · 9 samples
Chloride6.6 mg/Llimit 250 mg/L · 9 samples
Sulphate9.2 mg/Llimit 250 mg/L · 9 samples
Sodium3.7 mg/Llimit 200 mg/L · 5 samples
pH7.1–8.3limit 6.5–9.5 · 72 samples
Electrical conductivity563 µS/cmlimit 2,500 µS/cm · 72 samples

Non-compliant samples

What the laboratory found in the samples that were not compliant:

Samples by year

014282016: 26 samples, 7 non-compliant’162017: 26 samples, 7 non-compliant’172018: 28 samples, 6 non-compliant’182019: 28 samples, 4 non-compliant’192020: 26 samples, 3 non-compliant’202021: 27 samples, 4 non-compliant’212022: 26 samples, 8 non-compliant’222023: 26 samples, 2 non-compliant’232024: 27 samples, 5 non-compliant’242025: 28 samples, 6 non-compliant’252026: 17 samples, 1 non-compliant’26
compliant non-compliant · Drinking-water samples in Medvode since 2016

What you can do

How to read the results

The ratings are a Draga Slovenija summary, not an official NIJZ rating.

More about water and property in Medvode

Estimate a property’s valueProperty prices in Medvode

Drinking water in neighbouring municipalities in the Central Slovenia region: Ljubljana, Brezovica, Škofljica, Ivančna Gorica, Vrhnika, Borovnica, Dol pri Ljubljani, Vodice, Velike Lašče, Ig, Domžale, Mengeš, Trzin, Moravče, Lukovica, Kamnik, Komenda, Dobrova - Polhov Gradec, Horjul, Dobrepolje, Grosuplje, Šmartno pri Litiji, Logatec.

Explanations of the parameters:

Follow the results for your address

When the state monitoring publishes a non-compliant result for the area by your address, we e-mail you (results come out about once a month). One address is free. This is not an urgent boil-water alert; the operator announces those.

Find your address and turn on following →

Monthly e-mail roundup: drinking water and the property market

Once a month: new drinking-water results and how the property market moved, in one e-mail. This is our existing monthly newsletter; we do not send a report for a single municipality. Unsubscribe with one click in every e-mail.

Email address only. Privacy statement.

Source: NIJZ and NLZOH, mpv.si; latest sample 31 Aug 2026. Processing: Draga Slovenija.

Frequently asked questions

Is the water in Medvode safe to drink?

These are past results, not a verdict on the water today; the operator announces current restrictions (boil-water notices). In 2024–2026 the state monitoring took 72 samples of drinking water on the 11 supply areas serving the municipality, of which 12 were not compliant (E. coli or enterococci bacteria in 1 sample). Details by water system are above.

How hard is the water in Medvode?

By the operators’ figures and, where there are none, our estimate 15.9 °dH (averaged over the water systems, weighted by users), which is hard water. To set appliances, use your own system’s figure.

Who operates the water supply in Medvode?

JP VOKA SNAGA d.o.o., Občina Medvode, Društvo za varstvo voda ŽLEBE. The largest supply area is MEDVODE.

Where are the official drinking-water test results?

The state monitoring publishes its results at mpv.si, and the operator publishes an annual report on internal control on its website. This page summarises the state monitoring since 2016.

AI chat

Ask the data, in plain language

The AI chat finds the answer in the official register and shows it with a table you can download and a link into the map. Free; it only needs an account.

For example: Which municipalities issued the most building permits last year?

Open the AI chat

AI chat