Drinking water in the Zasavska region
In 2024–2026 the state monitoring took 404 samples in the Zasavska region, across 56 supply areas; 68 (17%) were not compliant. The median estimated hardness is 14.2 °dH.
Municipalities in the Zasavska region
| Municipality | Rating | Samples | Non-compliant | Hardness (°dH) | Nitrate (mg/L) |
|---|---|---|---|---|---|
| Hrastnik | occasional non-compliance | 60 | 7 | 13.2 moderately hard | 4.4 |
| Litija | mostly compliant | 127 | 12 | 15.9 hard | 4.65 |
| Trbovlje | occasional non-compliance | 62 | 3 | 11.9 moderately hard | 5.55 |
| Zagorje ob Savi | occasional non-compliance | 155 | 46 | 14.4 hard | 5.8 |
Measured values
| Parameter | Highest value | Against the limit |
|---|---|---|
| E. coli | >80 per 100 mL | limit 0 per 100 mL · 404 samples · 12× over the limit |
| Enterococci | 60 per 100 mL | limit 0 per 100 mL · 404 samples · 19× over the limit |
| Coliform bacteria | >80 per 100 mL | limit 0 per 100 mL · 404 samples · 53× over the limit |
| Clostridium perfringens | 71 per 100 mL | limit 0 per 100 mL · 170 samples · 7× over the limit |
| Nitrate | 19 mg/L | limit 50 mg/L · 95 samples |
| Nitrite | below 0.01 mg/L | limit 0.5 mg/L · 95 samples |
| Nitrate/50 + nitrite/3 | 0.38 | limit 1 · 95 samples |
| PFAS, total | below 0.03 µg/L | limit 0.5 µg/L · 5 samples |
| PFOA | below 0.0005 µg/L | part of the 20-PFAS sum, limit 0.1 µg/L · 5 samples |
| PFOS | below 0.0005 µg/L | part of the 20-PFAS sum, limit 0.1 µg/L · 5 samples |
| Lead | 3.4 µg/L | limit 10 µg/L · 21 samples |
| Arsenic | below 1 µg/L | limit 10 µg/L · 52 samples |
| Uranium | 1 µg/L | limit 30 µg/L · 27 samples |
| Copper | 0.073 mg/L | limit 2 mg/L · 52 samples |
| Nickel | below 1 µg/L | limit 20 µg/L · 27 samples |
| Cadmium | 0.03 µg/L | limit 5 µg/L · 52 samples |
| Chromium | below 1 µg/L | limit 50 µg/L · 52 samples |
| Antimony | 1.2 µg/L | limit 10 µg/L · 52 samples |
| Selenium | 2 µg/L | limit 20 µg/L · 52 samples |
| Boron | 0.03 mg/L | limit 1.5 mg/L · 52 samples |
| Fluoride | 0.17 mg/L | limit 1.5 mg/L · 95 samples |
| Trihalomethanes, total | 6.4 µg/L | limit 100 µg/L · 52 samples |
| Haloacetic acids | below 5 µg/L | limit 60 µg/L · 5 samples |
| Chlorate | 0.06 mg/L | limit 0.25 mg/L · 29 samples |
| Chlorite | below 0.01 mg/L | limit 0.25 mg/L · 29 samples |
| Tetrachloroethene + trichloroethene | below 0.2 µg/L | limit 10 µg/L · 3 samples |
| Bisphenol A | below 0.025 µg/L | limit 2.5 µg/L · 1 sample |
| Free chlorine | 0.55 mg/L | no limit value · 212 samples |
| Manganese | 2.1 µg/L | limit 50 µg/L · 52 samples |
| Iron | 450 µg/L | limit 200 µg/L · 52 samples · 1× over the limit |
| Aluminium | 66 µg/L | limit 200 µg/L · 52 samples |
| Ammonium | below 0.02 mg/L | limit 0.5 mg/L · 95 samples |
| Chloride | 59 mg/L | limit 250 mg/L · 95 samples |
| Sulphate | 30 mg/L | limit 250 mg/L · 95 samples |
| Sodium | 6.4 mg/L | limit 200 mg/L · 52 samples |
| pH | 6.4–8.6 | limit 6.5–9.5 · 404 samples · 1× outside the range |
| Electrical conductivity | 689 µS/cm | limit 2,500 µS/cm · 404 samples |
Samples by year
How to read the results
- All samples compliant all samples in this period met the Drinking Water Decree.
- Mostly compliant (municipality) non-compliant samples came only from smaller systems that together supply less than a quarter of the users there.
- Occasional non-compliance individual samples were not compliant on indicator parameters (iron, manganese, turbidity, coliform bacteria), which point to a problem in treatment or the network but are not a health limit.
- Faecal bacteria in 1 sample E. coli or enterococci were found in one sample. That is a serious finding, but a single one; check its date and the later samples.
- Repeated or health-relevant non-compliance faecal bacteria (E. coli, enterococci) in two or more samples, or a health-based chemical limit (nitrate, pesticides, lead, arsenic …) exceeded at least once.
The ratings are a Draga Slovenija summary, not an official NIJZ rating.
Other regions
Source: NIJZ and NLZOH, mpv.si; latest sample 31 Aug 2026. Processing: Draga Slovenija.
Frequently asked questions
What is the drinking water like in the Zasavska region?
In 2024–2026 the state monitoring took 404 samples in the Zasavska region, across 56 supply areas; 68 (17%) were not compliant.
Where is the water hardest in the Zasavska region?
By estimate Litija (15.9 °dH), Zagorje ob Savi (14.4 °dH), Hrastnik (13.2 °dH).