Draga SlovenijaDraga Slovenija

Drinking water in Southeast Slovenia

In 2024–2026 the state monitoring took 681 samples in Southeast Slovenia, across 84 supply areas; 55 (8.1%) were not compliant. The median estimated hardness is 14.8 °dH.

Samples 2024–202668184 supply areas
Non-compliant558.1%
Municipalities with repeated non-compliance2of 21
Hardness (estimate)14.8 °dHhard

Municipalities in Southeast Slovenia

MunicipalityRatingSamplesNon-compliantHardness (°dH)Nitrate (mg/L)
Črnomeljoccasional non-compliance46112.1 moderately hard3.17
Dolenjske Topliceoccasional non-compliance16315 hard7.59
Kočevjemostly compliant57410.5 moderately hard3.78
Kostelcompliant16014.8 hard1.52
Loški Potokmostly compliant16112 moderately hard4
Metlikacompliant34014.2 hard5.77
Mirnamostly compliant31315.9 hard3.82
Mirna Pečcompliant10013.9 moderately hard0.82
Mokronog - Trebelnomostly compliant45817.3 hard5.71
Novo mestooccasional non-compliance116914.2 hard4.89
Osilnicaoccasional non-compliance10314 hard1.65
Ribnicaoccasional non-compliance87811.7 moderately hard3.34
Semičmostly compliant23317.2 hard2.38
Sodražicamostly compliant25312.8 moderately hard3.1
Stražaoccasional non-compliance51214.7 hard3.85
Šentjernejoccasional non-compliance91715.2 hard4.21
Šentrupertrepeated non-compliance45215.1 hard7.77
Škocjanrepeated non-compliance25318.1 hard5.18
Šmarješke Topliceoccasional non-compliance51214.7 hard3.85
Trebnjecompliant42021.7 very hard6.9
Žužemberkcompliant39013 moderately hard6.1

Measured values

ParameterHighest valueAgainst the limit
E. coli>100 per 100 mLlimit 0 per 100 mL · 681 samples · 5× over the limit
Enterococci35 per 100 mLlimit 0 per 100 mL · 681 samples · 7× over the limit
Coliform bacteria>100 per 100 mLlimit 0 per 100 mL · 681 samples · 21× over the limit
Clostridium perfringens13 per 100 mLlimit 0 per 100 mL · 498 samples · 7× over the limit
Nitrate16.7 mg/Llimit 50 mg/L · 130 samples
Nitrite0.015 mg/Llimit 0.5 mg/L · 130 samples
Nitrate/50 + nitrite/30.33limit 1 · 130 samples
Single pesticide (highest)0.13 µg/L (Desetil-atrazin)limit 0.1 µg/L · 13 samples · 1× over the limit
Pesticides, total0.053 µg/Llimit 0.5 µg/L · 4 samples
PFAS, totalbelow 0.03 µg/Llimit 0.5 µg/L · 9 samples
PFOAbelow 0.0005 µg/Lpart of the 20-PFAS sum, limit 0.1 µg/L · 9 samples
PFOS0.0006 µg/Lpart of the 20-PFAS sum, limit 0.1 µg/L · 9 samples
Lead0.65 µg/Llimit 10 µg/L · 36 samples
Arsenic0.59 µg/Llimit 10 µg/L · 79 samples
Uranium1.2 µg/Llimit 30 µg/L · 43 samples
Copper0.017 mg/Llimit 2 mg/L · 79 samples
Nickel0.31 µg/Llimit 20 µg/L · 41 samples
Cadmium0.23 µg/Llimit 5 µg/L · 79 samples
Chromium0.89 µg/Llimit 50 µg/L · 79 samples
Antimony0.1 µg/Llimit 10 µg/L · 79 samples
Selenium1.1 µg/Llimit 20 µg/L · 79 samples
Boron0.026 mg/Llimit 1.5 mg/L · 79 samples
Fluoride0.77 mg/Llimit 1.5 mg/L · 134 samples
Trihalomethanes, total60 µg/Llimit 100 µg/L · 77 samples
Haloacetic acids7.1 µg/Llimit 60 µg/L · 9 samples
Chlorate0.26 mg/Llimit 0.25 mg/L · 37 samples · 1× over the limit
Chloritebelow 0.05 mg/Llimit 0.25 mg/L · 37 samples
Benzenebelow 0.3 µg/Llimit 1 µg/L · 2 samples
PAHs, totalbelow 0.005 µg/Llimit 0.1 µg/L · 2 samples
Benzo(a)pyrenebelow 0.004 µg/Llimit 0.01 µg/L · 2 samples
Bisphenol Abelow 0.25 µg/Llimit 2.5 µg/L · 4 samples
Free chlorine0.61 mg/Lno limit value · 400 samples
Manganese0.68 µg/Llimit 50 µg/L · 79 samples
Iron80 µg/Llimit 200 µg/L · 79 samples
Aluminium78 µg/Llimit 200 µg/L · 84 samples
Ammonium0.081 mg/Llimit 0.5 mg/L · 130 samples
Chloride29 mg/Llimit 250 mg/L · 130 samples
Sulphate16 mg/Llimit 250 mg/L · 130 samples
Sodium78 mg/Llimit 200 mg/L · 79 samples
pH6.9–8.4limit 6.5–9.5 · 681 samples
Electrical conductivity671 µS/cmlimit 2,500 µS/cm · 681 samples

Samples by year

01502992016: 299 samples, 18 non-compliant’162017: 299 samples, 18 non-compliant’172018: 298 samples, 10 non-compliant’182019: 298 samples, 22 non-compliant’192020: 257 samples, 25 non-compliant’202021: 262 samples, 20 non-compliant’212022: 263 samples, 33 non-compliant’222023: 263 samples, 19 non-compliant’232024: 261 samples, 23 non-compliant’242025: 278 samples, 26 non-compliant’252026: 142 samples, 6 non-compliant’26
compliant non-compliant · Samples in Southeast Slovenia

How to read the results

The ratings are a Draga Slovenija summary, not an official NIJZ rating.

Other regions

Source: NIJZ and NLZOH, mpv.si; latest sample 31 Aug 2026. Processing: Draga Slovenija.

Frequently asked questions

What is the drinking water like in Southeast Slovenia?

In 2024–2026 the state monitoring took 681 samples in Southeast Slovenia, across 84 supply areas; 55 (8.1%) were not compliant.

Where is the water hardest in Southeast Slovenia?

By estimate Trebnje (21.7 °dH), Škocjan (18.1 °dH), Mokronog - Trebelno (17.3 °dH).

AI chat

Ask the data, in plain language

The AI chat finds the answer in the official register and shows it with a table you can download and a link into the map. Free; it only needs an account.

For example: Which municipalities issued the most building permits last year?

Open the AI chat

AI chat