Drinking water in the Pomurska region
In 2024–2026 the state monitoring took 292 samples in the Pomurska region, across 36 supply areas; 15 (5.1%) were not compliant. The median estimated hardness is 14.2 °dH.
Municipalities in the Pomurska region
| Municipality | Rating | Samples | Non-compliant | Hardness (°dH) | Nitrate (mg/L) |
|---|---|---|---|---|---|
| Apače | compliant | 11 | 0 | 12.8 moderately hard | 30 |
| Beltinci | compliant | 26 | 0 | 13.1 moderately hard | 19 |
| Cankova | occasional non-compliance | 78 | 2 | 14.8 hard | 17 |
| Črenšovci | repeated non-compliance | 11 | 4 | 9.9 moderately hard | 22 |
| Gornja Radgona | compliant | 19 | 0 | 13.9 moderately hard | 31 |
| Gornji Petrovci | repeated non-compliance | 5 | 1 | 11.4 moderately hard | 8.9 |
| Hodoš | compliant | 5 | 0 | 8.1 soft | 2.3 |
| Križevci | compliant | 4 | 0 | 17.1 hard | 10.5 |
| Kuzma | occasional non-compliance | 78 | 2 | 14.8 hard | 17 |
| Lendava | compliant | 18 | 0 | 8.1 soft | 8.4 |
| Ljutomer | occasional non-compliance | 122 | 2 | 14 hard | 14 |
| Moravske Toplice | occasional non-compliance | 91 | 2 | 14.6 hard | 15.5 |
| Murska Sobota | occasional non-compliance | 78 | 2 | 14.8 hard | 17 |
| Odranci | repeated non-compliance | 11 | 4 | 9.9 moderately hard | 22 |
| Puconci | repeated non-compliance | 6 | 2 | 11.7 moderately hard | 20 |
| Radenci | mostly compliant | 29 | 4 | 13.8 moderately hard | 31 |
| Rogašovci | occasional non-compliance | 92 | 2 | 14.9 hard | 17 |
| Šalovci | repeated non-compliance | 16 | 1 | 6.4 soft | 3.25 |
| Tišina | occasional non-compliance | 84 | 2 | 14.9 hard | 18 |
| Turnišče | compliant | 11 | 0 | 11.7 moderately hard | 32 |
| Velika Polana | repeated non-compliance | 10 | 1 | 8.8 moderately hard | 38.5 |
Measured values
| Parameter | Highest value | Against the limit |
|---|---|---|
| E. coli | 1 per 100 mL | limit 0 per 100 mL · 292 samples · 1× over the limit |
| Enterococci | 0 per 100 mL | limit 0 per 100 mL · 292 samples |
| Coliform bacteria | 13 per 100 mL | limit 0 per 100 mL · 292 samples · 4× over the limit |
| Clostridium perfringens | 0 per 100 mL | limit 0 per 100 mL · 1 sample |
| Nitrate | 44 mg/L | limit 50 mg/L · 54 samples |
| Nitrite | below 0.007 mg/L | limit 0.5 mg/L · 54 samples |
| Nitrate/50 + nitrite/3 | 0.88 | limit 1 · 54 samples |
| Single pesticide (highest) | 1.6 µg/L (Metolaklor ESA) | limit 0.1 µg/L · 49 samples · 18× over the limit |
| Pesticides, total | 0.31 µg/L | limit 0.5 µg/L · 16 samples |
| PFAS, total | below 0.03 µg/L | limit 0.5 µg/L · 8 samples |
| PFOA | below 0.0005 µg/L | part of the 20-PFAS sum, limit 0.1 µg/L · 8 samples |
| PFOS | below 0.0005 µg/L | part of the 20-PFAS sum, limit 0.1 µg/L · 8 samples |
| Lead | 2.5 µg/L | limit 10 µg/L · 23 samples |
| Arsenic | below 1 µg/L | limit 10 µg/L · 42 samples |
| Uranium | 2.9 µg/L | limit 30 µg/L · 24 samples |
| Copper | 0.023 mg/L | limit 2 mg/L · 42 samples |
| Nickel | 1 µg/L | limit 20 µg/L · 23 samples |
| Cadmium | 0.03 µg/L | limit 5 µg/L · 42 samples |
| Chromium | below 1 µg/L | limit 50 µg/L · 42 samples |
| Antimony | below 1 µg/L | limit 10 µg/L · 42 samples |
| Selenium | 2.2 µg/L | limit 20 µg/L · 42 samples |
| Boron | 0.047 mg/L | limit 1.5 mg/L · 42 samples |
| Fluoride | 0.15 mg/L | limit 1.5 mg/L · 54 samples |
| Trihalomethanes, total | 15 µg/L | limit 100 µg/L · 34 samples |
| Haloacetic acids | below 5 µg/L | limit 60 µg/L · 8 samples |
| Chlorate | 0.24 mg/L | limit 0.25 mg/L · 22 samples |
| Chlorite | below 0.01 mg/L | limit 0.25 mg/L · 22 samples |
| Tetrachloroethene + trichloroethene | below 0.2 µg/L | limit 10 µg/L · 34 samples |
| Benzene | below 0.2 µg/L | limit 1 µg/L · 1 sample |
| PAHs, total | below 0.004 µg/L | limit 0.1 µg/L · 1 sample |
| Benzo(a)pyrene | below 0.004 µg/L | limit 0.01 µg/L · 1 sample |
| Free chlorine | 0.18 mg/L | no limit value · 173 samples |
| Manganese | 34 µg/L | limit 50 µg/L · 42 samples |
| Iron | 34 µg/L | limit 200 µg/L · 42 samples |
| Aluminium | 22 µg/L | limit 200 µg/L · 42 samples |
| Ammonium | below 0.013 mg/L | limit 0.5 mg/L · 54 samples |
| Chloride | 30 mg/L | limit 250 mg/L · 54 samples |
| Sulphate | 46 mg/L | limit 250 mg/L · 54 samples |
| Sodium | 21 mg/L | limit 200 mg/L · 42 samples |
| pH | 6.5–7.7 | limit 6.5–9.5 · 292 samples |
| Electrical conductivity | 870 µS/cm | limit 2,500 µS/cm · 292 samples |
Samples by year
How to read the results
- All samples compliant all samples in this period met the Drinking Water Decree.
- Mostly compliant (municipality) non-compliant samples came only from smaller systems that together supply less than a quarter of the users there.
- Occasional non-compliance individual samples were not compliant on indicator parameters (iron, manganese, turbidity, coliform bacteria), which point to a problem in treatment or the network but are not a health limit.
- Faecal bacteria in 1 sample E. coli or enterococci were found in one sample. That is a serious finding, but a single one; check its date and the later samples.
- Repeated or health-relevant non-compliance faecal bacteria (E. coli, enterococci) in two or more samples, or a health-based chemical limit (nitrate, pesticides, lead, arsenic …) exceeded at least once.
The ratings are a Draga Slovenija summary, not an official NIJZ rating.
Other regions
Source: NIJZ and NLZOH, mpv.si; latest sample 31 Aug 2026. Processing: Draga Slovenija.
Frequently asked questions
What is the drinking water like in the Pomurska region?
In 2024–2026 the state monitoring took 292 samples in the Pomurska region, across 36 supply areas; 15 (5.1%) were not compliant.
Where is the water hardest in the Pomurska region?
By estimate Križevci (17.1 °dH), Rogašovci (14.9 °dH), Tišina (14.9 °dH).