Drinking water in the Primorsko-notranjska region
In 2024–2026 the state monitoring took 272 samples in the Primorsko-notranjska region, across 30 supply areas; 19 (7%) were not compliant. The median estimated hardness is 12 °dH.
Municipalities in the Primorsko-notranjska region
| Municipality | Rating | Samples | Non-compliant | Hardness (°dH) | Nitrate (mg/L) |
|---|---|---|---|---|---|
| Bloke | compliant | 11 | 0 | 16 hard | 4.4 |
| Cerknica | occasional non-compliance | 58 | 3 | 14.3 hard | 3.65 |
| Ilirska Bistrica | mostly compliant | 106 | 5 | 11.9 moderately hard | 4.55 |
| Loška dolina | compliant | 10 | 0 | 15.9 hard | 4.35 |
| Pivka | occasional non-compliance | 57 | 3 | 10.5 moderately hard | 3.44 |
| Postojna | occasional non-compliance | 82 | 10 | 10.5 moderately hard | 3.17 |
Measured values
| Parameter | Highest value | Against the limit |
|---|---|---|
| E. coli | 62 per 100 mL | limit 0 per 100 mL · 272 samples · 7× over the limit |
| Enterococci | 41 per 100 mL | limit 0 per 100 mL · 272 samples · 4× over the limit |
| Coliform bacteria | >100 per 100 mL | limit 0 per 100 mL · 272 samples · 13× over the limit |
| Clostridium perfringens | 5 per 100 mL | limit 0 per 100 mL · 220 samples · 2× over the limit |
| Nitrate | 6.13 mg/L | limit 50 mg/L · 46 samples |
| Nitrite | 0.0083 mg/L | limit 0.5 mg/L · 46 samples |
| Nitrate/50 + nitrite/3 | 0.12 | limit 1 · 46 samples |
| PFAS, total | below 0.03 µg/L | limit 0.5 µg/L · 2 samples |
| PFOA | below 0.0005 µg/L | part of the 20-PFAS sum, limit 0.1 µg/L · 2 samples |
| PFOS | below 0.0005 µg/L | part of the 20-PFAS sum, limit 0.1 µg/L · 2 samples |
| Lead | 2.1 µg/L | limit 10 µg/L · 25 samples |
| Arsenic | 0.15 µg/L | limit 10 µg/L · 28 samples |
| Uranium | 1.1 µg/L | limit 30 µg/L · 15 samples |
| Copper | 0.012 mg/L | limit 2 mg/L · 28 samples |
| Nickel | 19 µg/L | limit 20 µg/L · 15 samples |
| Cadmium | 0.033 µg/L | limit 5 µg/L · 28 samples |
| Chromium | 0.41 µg/L | limit 50 µg/L · 28 samples |
| Antimony | 0.19 µg/L | limit 10 µg/L · 28 samples |
| Selenium | 1.4 µg/L | limit 20 µg/L · 28 samples |
| Boron | 0.0049 mg/L | limit 1.5 mg/L · 28 samples |
| Fluoride | below 0.15 mg/L | limit 1.5 mg/L · 45 samples |
| Trihalomethanes, total | 46 µg/L | limit 100 µg/L · 24 samples |
| Haloacetic acids | below 5 µg/L | limit 60 µg/L · 2 samples |
| Chlorate | 0.13 mg/L | limit 0.25 mg/L · 11 samples |
| Chlorite | below 0.05 mg/L | limit 0.25 mg/L · 11 samples |
| Bisphenol A | 0.08 µg/L | limit 2.5 µg/L · 1 sample |
| Free chlorine | 1.33 mg/L | no limit value · 156 samples |
| Manganese | 0.51 µg/L | limit 50 µg/L · 28 samples |
| Iron | 26 µg/L | limit 200 µg/L · 28 samples |
| Aluminium | 42 µg/L | limit 200 µg/L · 66 samples |
| Ammonium | 0.016 mg/L | limit 0.5 mg/L · 46 samples |
| Chloride | 9 mg/L | limit 250 mg/L · 46 samples |
| Sulphate | 12 mg/L | limit 250 mg/L · 46 samples |
| Sodium | 3.7 mg/L | limit 200 mg/L · 28 samples |
| pH | 7.1–8.9 | limit 6.5–9.5 · 272 samples |
| Electrical conductivity | 512 µS/cm | limit 2,500 µS/cm · 272 samples |
Samples by year
How to read the results
- All samples compliant all samples in this period met the Drinking Water Decree.
- Mostly compliant (municipality) non-compliant samples came only from smaller systems that together supply less than a quarter of the users there.
- Occasional non-compliance individual samples were not compliant on indicator parameters (iron, manganese, turbidity, coliform bacteria), which point to a problem in treatment or the network but are not a health limit.
- Faecal bacteria in 1 sample E. coli or enterococci were found in one sample. That is a serious finding, but a single one; check its date and the later samples.
- Repeated or health-relevant non-compliance faecal bacteria (E. coli, enterococci) in two or more samples, or a health-based chemical limit (nitrate, pesticides, lead, arsenic …) exceeded at least once.
The ratings are a Draga Slovenija summary, not an official NIJZ rating.
Other regions
Source: NIJZ and NLZOH, mpv.si; latest sample 31 Aug 2026. Processing: Draga Slovenija.
Frequently asked questions
What is the drinking water like in the Primorsko-notranjska region?
In 2024–2026 the state monitoring took 272 samples in the Primorsko-notranjska region, across 30 supply areas; 19 (7%) were not compliant.
Where is the water hardest in the Primorsko-notranjska region?
By estimate Bloke (16 °dH), Loška dolina (15.9 °dH), Cerknica (14.3 °dH).