Draga SlovenijaDraga Slovenija

Drinking water in Zagorje ob Savi

Occasional non-compliance

In 2024–2026 the state monitoring took 155 samples of drinking water on the 25 supply areas serving the municipality, of which 46 were not compliant (E. coli or enterococci bacteria in 16 samples). The water is estimated to be hard (≈14.4 °dH).

These are state monitoring results from 2024–2026, not a notice about the water today. Current notices (boil-water, do-not-use) are published by the water-system operator on its website.

Samples 2024–202615525 supply areas
Non-compliant4630%
Hardness (estimate)14.4 °dHhard
Nitrate, median5.8 mg/Llimit 50 mg/L

Water systems in Zagorje ob Savi

In 2024–2026 the state monitoring sampled 25 supply areas; the largest, ŠEMNIK - STRAHOVLJE, supplies 6,713 users. The address search shows the nearest sampling points, not necessarily your water system; the system that supplies you is named on your water bill.

Supply areas at a glance
AreaUsersRating
ŠEMNIK - STRAHOVLJE6,713compliant
IZLAKE1,112occasional non-compliance
ELEKTROELEMENT1,000occasional non-compliance
ROVE902compliant
KOTREDEŽ - LOŠČ (del Zagorja)690compliant
PODKUM - ZAGORJE426occasional non-compliance
ŠENTLAMBERT281occasional non-compliance
ČOLNIŠČE272occasional non-compliance
TIRNA - ROVIŠČE257repeated non-compliance
MLINŠE - KOLOVRAT167compliant
Zgornje Jesenovo132Faecal bacteria in 1 sample
ČEMŠENIK126compliant
Peške- Kandrše113compliant
ŠENTGOTARD110Faecal bacteria in 1 sample
SLIVNA109compliant
Potoška vas105Faecal bacteria in 1 sample
ROVE - TESEN100repeated non-compliance
TIRNA II86occasional non-compliance
VIDRGA82Faecal bacteria in 1 sample
Dobrljevo80Faecal bacteria in 1 sample
Spodnje Jesenovo, Spodnje Znojile80occasional non-compliance
LEPIŠ79Faecal bacteria in 1 sample
BREZJE - Zagorje77repeated non-compliance
PRVINE42compliant
PLANINSKI DOM DR. FRANCETA GOLOBA NA ČEMŠENIŠKI PLANINI1Faecal bacteria in 1 sample
ŠEMNIK - STRAHOVLJE: compliantŠEMNIK - STRAHOVLJE: compliantIZLAKE: occasional non-complianceELEKTROELEMENT: occasional non-complianceROVE: compliantKOTREDEŽ - LOŠČ (del Zagorja): compliantPODKUM - ZAGORJE: occasional non-complianceŠENTLAMBERT: occasional non-complianceČOLNIŠČE: occasional non-complianceTIRNA - ROVIŠČE: repeated non-complianceMLINŠE - KOLOVRAT: compliantZgornje Jesenovo: occasional non-complianceČEMŠENIK: compliantPeške- Kandrše: compliantŠENTGOTARD: occasional non-compliancePotoška vas: occasional non-complianceROVE - TESEN: repeated non-complianceTIRNA II: occasional non-complianceVIDRGA: occasional non-complianceDobrljevo: occasional non-complianceSpodnje Jesenovo, Spodnje Znojile: occasional non-complianceLEPIŠ: occasional non-complianceBREZJE - Zagorje: repeated non-compliancePRVINE: compliantZagorje ob SaviIzlakeVidrgaŠentlambertČemšenikŠentgotardPotoška vasDobrljevoLitijaTaborMoravčeŠmartno pri LitijiKamnikRadečeVranskoPreboldSevnicaŽalec5 km
  • compliant
  • occasional non-compliance
  • repeated non-compliance

Sampling points of the state monitoring in recent years, coloured by the result for the area. Click a dot for the area's figures. Place names © OpenStreetMap

ŠEMNIK - STRAHOVLJE

All samples compliant

Operator: Komunala Zagorje · 6,713 users · water system Šemnik - Strahovlje

Samples 2024–2026
18, all compliant
Water source
Influenced by surface water
Treatment
Chlorine gas disinfection
Hardness (estimate)
≈13.7 °dH, moderately hard
Latest sample
17 Aug 2026
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 18 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 18 samples
Nitrate6.2 mg/Llimit 50 mg/L · 5 samples
Arsenicbelow 1 µg/Llimit 10 µg/L · 4 samples
Manganesebelow 1 µg/Llimit 50 µg/L · 4 samples
Iron18 µg/Llimit 200 µg/L · 4 samples

IZLAKE

Occasional non-compliance

Operator: Komunala Zagorje · 1,112 users · water system Izlake

Samples 2024–2026
10, 1 non-compliant
Water source
Influenced by surface water
Treatment
Sodium hypochlorite disinfection
Hardness (estimate)
≈17.5 °dH, hard
Latest sample
16 Jun 2026
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 10 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 10 samples
Nitrate9.7 mg/Llimit 50 mg/L · 3 samples
Arsenicbelow 1 µg/Llimit 10 µg/L · 2 samples
Manganese2.1 µg/Llimit 50 µg/L · 2 samples
Iron450 µg/Llimit 200 µg/L · 2 samples · 1× over the limit
Non-compliant samples (1)
  • · Iron 450 µg/L limit 200 µg/L

ELEKTROELEMENT

Occasional non-compliance

Operator: Elektroelement · 1,000 users · water system Elektroelement

Samples 2024–2026
11, 1 non-compliant
Water source
Groundwater, not influenced by surface water
Treatment
Sodium hypochlorite disinfection, UV disinfection
Hardness (estimate)
≈11.7 °dH, moderately hard
Latest sample
17 Aug 2026
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 11 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 11 samples
Nitrate5.3 mg/Llimit 50 mg/L · 3 samples
PFAS, totalbelow 0.03 µg/Llimit 0.5 µg/L · 1 sample
Lead0.65 µg/Llimit 10 µg/L · 3 samples
Arsenicbelow 1 µg/Llimit 10 µg/L · 2 samples
Manganesebelow 1 µg/Llimit 50 µg/L · 2 samples
Iron10 µg/Llimit 200 µg/L · 2 samples
Non-compliant samples (1)
  • · marked non-compliant; the published data gives no reason

ROVE

All samples compliant

Operator: Komunala Zagorje · 902 users · water system Rove

Samples 2024–2026
11, all compliant
Water source
Groundwater, not influenced by surface water
Treatment
Chlorine gas disinfection
Hardness (estimate)
≈16.9 °dH, hard
Latest sample
3 Aug 2026
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 11 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 11 samples
Nitrate6.6 mg/Llimit 50 mg/L · 3 samples
Arsenicbelow 1 µg/Llimit 10 µg/L · 2 samples
Manganesebelow 1 µg/Llimit 50 µg/L · 2 samples
Iron30 µg/Llimit 200 µg/L · 2 samples

KOTREDEŽ - LOŠČ (del Zagorja)

All samples compliant

Operator: Komunala Zagorje · 690 users · water system Kotredež - Lošč

Samples 2024–2026
11, all compliant
Water source
Influenced by surface water
Treatment
Chlorine gas disinfection
Hardness (estimate)
≈14.9 °dH, hard
Latest sample
20 Aug 2026
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 11 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 11 samples
Nitrate5.3 mg/Llimit 50 mg/L · 3 samples
Arsenicbelow 1 µg/Llimit 10 µg/L · 2 samples
Manganesebelow 1 µg/Llimit 50 µg/L · 2 samples
Ironbelow 10 µg/Llimit 200 µg/L · 2 samples

PODKUM - ZAGORJE

Occasional non-compliance

Operator: Zagorje ob Savi · 426 users · water system Podkum - Zagorje

Samples 2024–2026
2, 1 non-compliant
Water source
Groundwater, not influenced by surface water
Treatment
No treatment
Hardness (estimate)
≈14.9 °dH, hard
Latest sample
19 Aug 2024
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 2 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 2 samples
Non-compliant samples (1)
  • · Coliform bacteria 9 per 100 mL limit 0 per 100 mL

ŠENTLAMBERT

Occasional non-compliance

Operator: DRUŠTVO ZA VAROVANJE VODA IN OKOLJA ŠENTLAMBERT · 281 users · water system Šentlambert

Samples 2024–2026
5, 3 non-compliant
Water source
Groundwater, not influenced by surface water
Hardness (estimate)
≈15.7 °dH, hard
Latest sample
30 Mar 2026
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 5 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 5 samples
Non-compliant samples (3)
  • · Coliform bacteria >80 per 100 mL limit 0 per 100 mL
  • · Coliform bacteria >80 per 100 mL limit 0 per 100 mL
  • · Coliform bacteria 1 per 100 mL limit 0 per 100 mL

ČOLNIŠČE

Occasional non-compliance

Operator: DRUŠTVO ZA VARSTVO VODA-OKOLJA ČOLNIŠČE · 272 users · water system Čolnišče

Samples 2024–2026
6, 1 non-compliant
Water source
Groundwater, not influenced by surface water
Hardness (estimate)
≈20.2 °dH, hard
Latest sample
25 Aug 2026
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 6 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 6 samples
Nitrate11 mg/Llimit 50 mg/L · 2 samples
Non-compliant samples (1)
  • · Coliform bacteria 1 per 100 mL limit 0 per 100 mL

TIRNA - ROVIŠČE

Repeated or health-relevant non-compliance

Operator: Tirna · 257 users · water system Tirna - Rovišče

Samples 2024–2026
6, 5 non-compliant
Water source
Groundwater, not influenced by surface water
Hardness (estimate)
≈12.9 °dH, moderately hard
Latest sample
25 Aug 2026
Measured values
E. coli10 per 100 mLlimit 0 per 100 mL · 6 samples · 2× over the limit
Enterococci14 per 100 mLlimit 0 per 100 mL · 6 samples · 4× over the limit
Nitrate5.8 mg/Llimit 50 mg/L · 1 sample
Non-compliant samples (5)
  • · E. coli 10 per 100 mL limit 0 per 100 mL, Enterococci 7 per 100 mL limit 0 per 100 mL, Coliform bacteria >80 per 100 mL limit 0 per 100 mL
  • · Enterococci 14 per 100 mL limit 0 per 100 mL, Coliform bacteria >80 per 100 mL limit 0 per 100 mL
  • · Enterococci 6 per 100 mL limit 0 per 100 mL, Coliform bacteria >80 per 100 mL limit 0 per 100 mL
  • · Enterococci 2 per 100 mL limit 0 per 100 mL, Coliform bacteria >80 per 100 mL limit 0 per 100 mL
  • · E. coli 2 per 100 mL limit 0 per 100 mL, Coliform bacteria 48 per 100 mL limit 0 per 100 mL

MLINŠE - KOLOVRAT

All samples compliant

Operator: Zagorje ob Savi · 167 users · water system Mlinše - Kolovrat

Samples 2024–2026
5, all compliant
Water source
Groundwater, not influenced by surface water
Treatment
Sodium hypochlorite disinfection
Hardness (estimate)
≈17 °dH, hard
Latest sample
16 Apr 2026
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 5 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 5 samples
Nitrate3.9 mg/Llimit 50 mg/L · 2 samples

Zgornje Jesenovo

Faecal bacteria in 1 sample

Operator: Zagorje ob Savi · 132 users · water system VV Zgornje Jesenovo

Samples 2024–2026
5, 5 non-compliant
Water source
Influenced by surface water
Hardness (estimate)
≈10.4 °dH, moderately hard
Latest sample
12 Mar 2026
Measured values
E. coli>80 per 100 mLlimit 0 per 100 mL · 5 samples · 1× over the limit
Enterococci3 per 100 mLlimit 0 per 100 mL · 5 samples · 1× over the limit
Non-compliant samples (5)
  • · Coliform bacteria >80 per 100 mL limit 0 per 100 mL
  • · E. coli >80 per 100 mL limit 0 per 100 mL, Enterococci 3 per 100 mL limit 0 per 100 mL, Coliform bacteria >80 per 100 mL limit 0 per 100 mL, Clostridium perfringens 1 per 100 mL limit 0 per 100 mL
  • · Coliform bacteria >80 per 100 mL limit 0 per 100 mL
  • · Coliform bacteria 22 per 100 mL limit 0 per 100 mL
  • · Coliform bacteria >80 per 100 mL limit 0 per 100 mL

ČEMŠENIK

All samples compliant

Operator: Zagorje ob Savi · 126 users · water system Čemšenik

Samples 2024–2026
5, all compliant
Water source
Groundwater, not influenced by surface water
Treatment
Sodium hypochlorite disinfection
Hardness (estimate)
≈12.7 °dH, moderately hard
Latest sample
23 Mar 2026
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 5 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 5 samples

Peške- Kandrše

All samples compliant

Operator: Komunala Zagorje · 113 users · water system Peške - Kandrše

Samples 2024–2026
5, all compliant
Water source
Influenced by surface water
Treatment
Sodium hypochlorite disinfection
Hardness (estimate)
≈15.6 °dH, hard
Latest sample
30 Mar 2026
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 5 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 5 samples

ŠENTGOTARD

Faecal bacteria in 1 sample

Operator: Zagorje ob Savi · 110 users · water system Šentgotard

Samples 2024–2026
5, 4 non-compliant
Water source
Groundwater, not influenced by surface water
Treatment
No treatment
Hardness (estimate)
≈9.6 °dH, moderately hard
Latest sample
12 Mar 2026
Measured values
E. coli3 per 100 mLlimit 0 per 100 mL · 5 samples · 1× over the limit
Enterococci7 per 100 mLlimit 0 per 100 mL · 5 samples · 1× over the limit
Non-compliant samples (4)
  • · Coliform bacteria 7 per 100 mL limit 0 per 100 mL
  • · E. coli 3 per 100 mL limit 0 per 100 mL, Enterococci 7 per 100 mL limit 0 per 100 mL, Coliform bacteria 53 per 100 mL limit 0 per 100 mL
  • · Coliform bacteria 3 per 100 mL limit 0 per 100 mL
  • · Coliform bacteria 8 per 100 mL limit 0 per 100 mL

SLIVNA

All samples compliant

Operator: KSP Litija · 109 users · water system Slivna - Mala Sela

Samples 2024–2026
3, all compliant
Water source
Influenced by surface water
Treatment
Sodium hypochlorite disinfection
Hardness (operator)
15 °dH, hard source
Latest sample
13 Apr 2026
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 3 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 3 samples

Potoška vas

Faecal bacteria in 1 sample

Operator: Komunala Zagorje · 105 users · water system Potoška vas

Samples 2024–2026
5, 1 non-compliant
Water source
Groundwater, not influenced by surface water
Treatment
Chlorine gas disinfection
Hardness (estimate)
≈12.9 °dH, moderately hard
Latest sample
12 Mar 2026
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 5 samples
Enterococci1 per 100 mLlimit 0 per 100 mL · 5 samples · 1× over the limit
Non-compliant samples (1)
  • · Enterococci 1 per 100 mL limit 0 per 100 mL

ROVE - TESEN

Repeated or health-relevant non-compliance

Operator: Zagorje ob Savi · 100 users · water system Rove - Tesen

Samples 2024–2026
5, 5 non-compliant
Water source
Groundwater, not influenced by surface water
Hardness (estimate)
≈14.5 °dH, hard
Latest sample
23 Mar 2026
Measured values
E. coli1 per 100 mLlimit 0 per 100 mL · 5 samples · 1× over the limit
Enterococci6 per 100 mLlimit 0 per 100 mL · 5 samples · 2× over the limit
Nitrate4 mg/Llimit 50 mg/L · 1 sample
Non-compliant samples (5)
  • · Coliform bacteria 12 per 100 mL limit 0 per 100 mL
  • · Enterococci 2 per 100 mL limit 0 per 100 mL, Coliform bacteria 73 per 100 mL limit 0 per 100 mL
  • · Coliform bacteria 1 per 100 mL limit 0 per 100 mL
  • · E. coli 1 per 100 mL limit 0 per 100 mL, Enterococci 6 per 100 mL limit 0 per 100 mL, Coliform bacteria >80 per 100 mL limit 0 per 100 mL
  • · Coliform bacteria 10 per 100 mL limit 0 per 100 mL

TIRNA II

Occasional non-compliance

Operator: Zagorje ob Savi · 86 users · water system Tirna II

Samples 2024–2026
5, 1 non-compliant
Water source
Groundwater, not influenced by surface water
Hardness (estimate)
≈18.3 °dH, hard
Latest sample
30 Mar 2026
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 5 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 5 samples
Nitrate11 mg/Llimit 50 mg/L · 1 sample
Non-compliant samples (1)
  • · Coliform bacteria 1 per 100 mL limit 0 per 100 mL

VIDRGA

Faecal bacteria in 1 sample

Operator: Zagorje ob Savi · 82 users · water system Vidrga

Samples 2024–2026
5, 4 non-compliant
Water source
Influenced by surface water
Hardness (estimate)
≈17 °dH, hard
Latest sample
30 Mar 2026
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 5 samples
Enterococci2 per 100 mLlimit 0 per 100 mL · 5 samples · 1× over the limit
Nitrate6.2 mg/Llimit 50 mg/L · 1 sample
Non-compliant samples (4)
  • · Coliform bacteria 6 per 100 mL limit 0 per 100 mL
  • · Coliform bacteria 2 per 100 mL limit 0 per 100 mL
  • · Enterococci 2 per 100 mL limit 0 per 100 mL, Coliform bacteria 5 per 100 mL limit 0 per 100 mL
  • · Coliform bacteria 6 per 100 mL limit 0 per 100 mL

Dobrljevo

Faecal bacteria in 1 sample

Operator: Vodovodno društvo Dobrljevo · 80 users · water system Dobrljevo

Samples 2024–2026
5, 3 non-compliant
Water source
Influenced by surface water
Hardness (estimate)
≈15.2 °dH, hard
Latest sample
23 Mar 2026
Measured values
E. coli1 per 100 mLlimit 0 per 100 mL · 5 samples · 1× over the limit
Enterococci20 per 100 mLlimit 0 per 100 mL · 5 samples · 1× over the limit
Nitrate6.6 mg/Llimit 50 mg/L · 1 sample
Non-compliant samples (3)
  • · marked non-compliant; the published data gives no reason
  • · Clostridium perfringens 1 per 100 mL limit 0 per 100 mL
  • · E. coli 1 per 100 mL limit 0 per 100 mL, Enterococci 20 per 100 mL limit 0 per 100 mL, Coliform bacteria >80 per 100 mL limit 0 per 100 mL, Clostridium perfringens 3 per 100 mL limit 0 per 100 mL

Spodnje Jesenovo, Spodnje Znojile

Occasional non-compliance

Operator: Društvo za varstvo voda in okolja Žaga · 80 users · water system Spodnje Jesenovo

Samples 2024–2026
5, 4 non-compliant
Water source
Influenced by surface water
Hardness (estimate)
≈14.2 °dH, hard
Latest sample
23 Mar 2026
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 5 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 5 samples
Nitrate6.6 mg/Llimit 50 mg/L · 2 samples
Non-compliant samples (4)
  • · Coliform bacteria 1 per 100 mL limit 0 per 100 mL
  • · Coliform bacteria 2 per 100 mL limit 0 per 100 mL
  • · marked non-compliant; the published data gives no reason
  • · Coliform bacteria 1 per 100 mL limit 0 per 100 mL

LEPIŠ

Faecal bacteria in 1 sample

Operator: Zagorje ob Savi · 79 users · water system Lepiš

Samples 2024–2026
4, 3 non-compliant
Water source
Groundwater, not influenced by surface water
Hardness (estimate)
≈15.3 °dH, hard
Latest sample
10 Oct 2025
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 4 samples
Enterococci1 per 100 mLlimit 0 per 100 mL · 4 samples · 1× over the limit
Non-compliant samples (3)
  • · Enterococci 1 per 100 mL limit 0 per 100 mL, Coliform bacteria 7 per 100 mL limit 0 per 100 mL
  • · Coliform bacteria >80 per 100 mL limit 0 per 100 mL
  • · Coliform bacteria >80 per 100 mL limit 0 per 100 mL

BREZJE - Zagorje

Repeated or health-relevant non-compliance

Operator: Zagorje ob Savi · 77 users · water system BREZJE - Zagorje

Samples 2024–2026
5, 3 non-compliant
Water source
Influenced by surface water
Hardness (estimate)
≈11.5 °dH, moderately hard
Latest sample
23 Mar 2026
Measured values
E. coli>16 per 100 mLlimit 0 per 100 mL · 5 samples · 2× over the limit
Enterococci60 per 100 mLlimit 0 per 100 mL · 5 samples · 2× over the limit
Nitrate4.6 mg/Llimit 50 mg/L · 1 sample
Non-compliant samples (3)
  • · Coliform bacteria 38 per 100 mL limit 0 per 100 mL
  • · E. coli >16 per 100 mL limit 0 per 100 mL, Enterococci 60 per 100 mL limit 0 per 100 mL, Coliform bacteria >80 per 100 mL limit 0 per 100 mL, Clostridium perfringens 1 per 100 mL limit 0 per 100 mL
  • · E. coli 1 per 100 mL limit 0 per 100 mL, Enterococci 18 per 100 mL limit 0 per 100 mL, Coliform bacteria >80 per 100 mL limit 0 per 100 mL

PRVINE

All samples compliant

Operator: Komunala Zagorje · 42 users · water system Prvine

Samples 2024–2026
5, all compliant
Water source
Groundwater, not influenced by surface water
Treatment
Sodium hypochlorite disinfection
Hardness (estimate)
≈15 °dH, hard
Latest sample
23 Mar 2026
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 5 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 5 samples

PLANINSKI DOM DR. FRANCETA GOLOBA NA ČEMŠENIŠKI PLANINI

Faecal bacteria in 1 sample

Operator: GOSTINSKE STORITVE URŠKA · 1 user · water system Planinski Dom Dr. Franceta Goloba na Čemšeniški Planini

Samples 2024–2026
3, 1 non-compliant
Water source
Undetermined
Hardness (estimate)
≈2.7 °dH, soft
Latest sample
18 May 2026
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 3 samples
Enterococci2 per 100 mLlimit 0 per 100 mL · 3 samples · 1× over the limit
Non-compliant samples (1)
  • · Enterococci 2 per 100 mL limit 0 per 100 mL, Coliform bacteria 59 per 100 mL limit 0 per 100 mL

Measured values 2024–2026

The highest measured value of each parameter in the samples from the water systems that supply the municipality, and the share of the limit it reaches.

ParameterHighest valueAgainst the limit
E. coli>80 per 100 mLlimit 0 per 100 mL · 155 samples · 8× over the limit
Enterococci60 per 100 mLlimit 0 per 100 mL · 155 samples · 15× over the limit
Coliform bacteria>80 per 100 mLlimit 0 per 100 mL · 155 samples · 40× over the limit
Clostridium perfringens3 per 100 mLlimit 0 per 100 mL · 71 samples · 4× over the limit
Nitrate11 mg/Llimit 50 mg/L · 29 samples
Nitritebelow 0.007 mg/Llimit 0.5 mg/L · 29 samples
Nitrate/50 + nitrite/30.22limit 1 · 29 samples
PFAS, totalbelow 0.03 µg/Llimit 0.5 µg/L · 1 sample
PFOAbelow 0.0005 µg/Lpart of the 20-PFAS sum, limit 0.1 µg/L · 1 sample
PFOSbelow 0.0005 µg/Lpart of the 20-PFAS sum, limit 0.1 µg/L · 1 sample
Lead0.65 µg/Llimit 10 µg/L · 3 samples
Arsenicbelow 1 µg/Llimit 10 µg/L · 12 samples
Uranium1 µg/Llimit 30 µg/L · 6 samples
Copper0.073 mg/Llimit 2 mg/L · 12 samples
Nickelbelow 1 µg/Llimit 20 µg/L · 6 samples
Cadmium0.03 µg/Llimit 5 µg/L · 12 samples
Chromiumbelow 1 µg/Llimit 50 µg/L · 12 samples
Antimony1.2 µg/Llimit 10 µg/L · 12 samples
Selenium1.7 µg/Llimit 20 µg/L · 12 samples
Boron0.03 mg/Llimit 1.5 mg/L · 12 samples
Fluoride0.17 mg/Llimit 1.5 mg/L · 29 samples
Trihalomethanes, total6.2 µg/Llimit 100 µg/L · 14 samples
Haloacetic acidsbelow 5 µg/Llimit 60 µg/L · 1 sample
Chlorate0.04 mg/Llimit 0.25 mg/L · 6 samples
Chloritebelow 0.01 mg/Llimit 0.25 mg/L · 6 samples
Free chlorine0.34 mg/Lno limit value · 59 samples
Manganese2.1 µg/Llimit 50 µg/L · 12 samples
Iron450 µg/Llimit 200 µg/L · 12 samples · 1× over the limit
Aluminium66 µg/Llimit 200 µg/L · 12 samples
Ammoniumbelow 0.013 mg/Llimit 0.5 mg/L · 29 samples
Chloride34 mg/Llimit 250 mg/L · 29 samples
Sulphate20 mg/Llimit 250 mg/L · 29 samples
Sodium6.4 mg/Llimit 200 mg/L · 12 samples
pH7.1–8.2limit 6.5–9.5 · 155 samples
Electrical conductivity643 µS/cmlimit 2,500 µS/cm · 155 samples

Non-compliant samples

What the laboratory found in the samples that were not compliant:

Showing the latest 30 of 46 non-compliant samples.

Samples by year

033652016: 65 samples, 18 non-compliant’162017: 65 samples, 9 non-compliant’172018: 65 samples, 9 non-compliant’182019: 65 samples, 13 non-compliant’192020: 59 samples, 10 non-compliant’202021: 59 samples, 8 non-compliant’212022: 59 samples, 11 non-compliant’222023: 59 samples, 14 non-compliant’232024: 59 samples, 18 non-compliant’242025: 61 samples, 20 non-compliant’252026: 35 samples, 8 non-compliant’26
compliant non-compliant · Drinking-water samples in Zagorje ob Savi since 2016

What you can do

How to read the results

The ratings are a Draga Slovenija summary, not an official NIJZ rating.

More about water and property in Zagorje ob Savi

Estimate a property’s valueProperty prices in Zagorje ob Savi

Drinking water in neighbouring municipalities in the Zasavska region: Trbovlje, Hrastnik, Litija.

Explanations of the parameters:

Follow the results for your address

When the state monitoring publishes a non-compliant result for the area by your address, we e-mail you (results come out about once a month). One address is free. This is not an urgent boil-water alert; the operator announces those.

Find your address and turn on following →

Monthly e-mail roundup: drinking water and the property market

Once a month: new drinking-water results and how the property market moved, in one e-mail. This is our existing monthly newsletter; we do not send a report for a single municipality. Unsubscribe with one click in every e-mail.

Email address only. Privacy statement.

Source: NIJZ and NLZOH, mpv.si; latest sample 31 Aug 2026. Processing: Draga Slovenija.

Frequently asked questions

Is the water in Zagorje ob Savi safe to drink?

These are past results, not a verdict on the water today; the operator announces current restrictions (boil-water notices). In 2024–2026 the state monitoring took 155 samples of drinking water on the 25 supply areas serving the municipality, of which 46 were not compliant (E. coli or enterococci bacteria in 16 samples). Details by water system are above.

How hard is the water in Zagorje ob Savi?

Estimated from electrical conductivity at 14.4 °dH, which is hard water. The operator publishes the exact value for its network.

Who operates the water supply in Zagorje ob Savi?

Komunala Zagorje, Elektroelement, Zagorje ob Savi, DRUŠTVO ZA VAROVANJE VODA IN OKOLJA ŠENTLAMBERT, DRUŠTVO ZA VARSTVO VODA-OKOLJA ČOLNIŠČE. The largest supply area is ŠEMNIK - STRAHOVLJE.

Where are the official drinking-water test results?

The state monitoring publishes its results at mpv.si, and the operator publishes an annual report on internal control on its website. This page summarises the state monitoring since 2016.

AI chat

Ask the data, in plain language

The AI chat finds the answer in the official register and shows it with a table you can download and a link into the map. Free; it only needs an account.

For example: Which municipalities issued the most building permits last year?

Open the AI chat

AI chat