Draga SlovenijaDraga Slovenija

Drinking water in Cerknica

Occasional non-compliance

In 2024–2026 the state monitoring took 58 samples of drinking water on the 8 supply areas serving the municipality, of which 3 were not compliant. By the operators’ figures and our estimate the water is hard (≈14.3 °dH).

These are state monitoring results from 2024–2026, not a notice about the water today. Current notices (boil-water, do-not-use) are published by the water-system operator on its website.

Samples 2024–2026588 supply areas
Non-compliant35.2%
Hardness (operator and estimate)14.3 °dHhard
Nitrate, median3.65 mg/Llimit 50 mg/L

Water systems in Cerknica

In 2024–2026 the state monitoring sampled 8 supply areas; the largest, CERKNICA - RAKEK, supplies 9,716 users. The address search shows the nearest sampling points, not necessarily your water system; the system that supplies you is named on your water bill.

Supply areas at a glance
AreaUsersRating
CERKNICA - RAKEK9,716occasional non-compliance
Begunje1,161compliant
Cajnarje243compliant
OSREDEK SV. VID208compliant
Bloška planota (Cerknica)197compliant
Podslivnica170occasional non-compliance
PIKOVNIK140occasional non-compliance
Rakov Škocjan2compliant
CERKNICA - RAKEK: occasional non-complianceCERKNICA - RAKEK: occasional non-complianceBegunje: compliantBegunje: compliantCajnarje: compliantOSREDEK SV. VID: compliantPodslivnica: occasional non-compliancePIKOVNIK: occasional non-complianceRakov Škocjan: compliantCerknicaCajnarjePodslivnicaPikovnikRakekBegunje pri CerkniciUnecGrahovoDolenje JezeroŽerovnicaLoška dolinaBlokePostojnaVelike LaščeBorovnicaBrezovicaLogatecPivkaIgIlirska Bistrica5 km
  • compliant
  • occasional non-compliance

Sampling points of the state monitoring in recent years, coloured by the result for the area. Click a dot for the area's figures. Place names © OpenStreetMap

CERKNICA - RAKEK

Occasional non-compliance

Operator: Komunala Cerknica · 9,716 users · water system Cerknica

Samples 2024–2026
19, 1 non-compliant
Water source
Influenced by surface water
Treatment
Ultrafiltration, chlorine dioxide disinfection
Hardness (operator)
14.2 °dH, hard source
Latest sample
31 Aug 2026
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 19 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 19 samples
Nitrate3.3 mg/Llimit 50 mg/L · 5 samples
PFAS, totalbelow 0.03 µg/Llimit 0.5 µg/L · 1 sample
Arsenicbelow 1 µg/Llimit 10 µg/L · 5 samples
Manganesebelow 1 µg/Llimit 50 µg/L · 5 samples
Ironbelow 10 µg/Llimit 200 µg/L · 5 samples
Non-compliant samples (1)
  • · marked non-compliant; the published data gives no reason

Begunje

All samples compliant

Operator: Komunala Cerknica · 1,161 users · water system Begunje

Samples 2024–2026
11, all compliant
Water source
Influenced by surface water
Treatment
Chlorine dioxide disinfection
Hardness (operator)
15 °dH, hard source
Latest sample
15 Jun 2026
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 11 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 11 samples
Nitrate5.3 mg/Llimit 50 mg/L · 3 samples
Arsenicbelow 1 µg/Llimit 10 µg/L · 2 samples
Manganesebelow 1 µg/Llimit 50 µg/L · 2 samples
Ironbelow 10 µg/Llimit 200 µg/L · 2 samples

Cajnarje

All samples compliant

Operator: Komunala Cerknica · 243 users · water system Cajnarje

Samples 2024–2026
6, all compliant
Water source
Groundwater, not influenced by surface water
Treatment
Sodium hypochlorite disinfection
Hardness (operator)
15.1 °dH, hard source
Latest sample
31 Aug 2026
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 6 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 6 samples
Nitrate4.3 mg/Llimit 50 mg/L · 1 sample

OSREDEK SV. VID

All samples compliant

Operator: Komunala Cerknica · 208 users · water system Osredek Sv. Vid

Samples 2024–2026
6, all compliant
Water source
Influenced by surface water
Treatment
Sodium hypochlorite disinfection
Hardness (operator)
11.4 °dH, moderately hard source
Latest sample
31 Aug 2026
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 6 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 6 samples
Nitrate4.9 mg/Llimit 50 mg/L · 1 sample

Bloška planota (Cerknica)

All samples compliant

Operator: Komunala Cerknica · 197 users · water system Bloška planota (Cerknica)

Samples 2024–2026
2, all compliant
Water source
Influenced by surface water
Treatment
Chlorine gas disinfection
Hardness (estimate)
≈15 °dH, hard
Latest sample
31 Aug 2026
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 2 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 2 samples
Nitrate4 mg/Llimit 50 mg/L · 1 sample

Podslivnica

Occasional non-compliance

Operator: Komunala Cerknica · 170 users · water system Podslivnica

Samples 2024–2026
4, 1 non-compliant
Water source
Influenced by surface water
Treatment
Filters, sodium hypochlorite disinfection, chlorine dioxide disinfection
Hardness (operator)
14.2 °dH, hard source
Latest sample
1 Apr 2026
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 4 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 4 samples
Non-compliant samples (1)
  • · marked non-compliant; the published data gives no reason

PIKOVNIK

Occasional non-compliance

Operator: Komunala Cerknica · 140 users · water system Pikovnik

Samples 2024–2026
5, 1 non-compliant
Water source
Groundwater, not influenced by surface water
Treatment
No treatment
Hardness (operator)
14.8 °dH, hard source
Latest sample
6 Mar 2026
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 5 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 5 samples
Non-compliant samples (1)
  • · Coliform bacteria 27 per 100 mL limit 0 per 100 mL

Rakov Škocjan

All samples compliant

Operator: Komunala Cerknica · 2 users · water system Rakov Škocjan

Samples 2024–2026
5, all compliant
Water source
Influenced by surface water
Treatment
Sodium hypochlorite disinfection
Hardness (operator)
11.4 °dH, moderately hard source
Latest sample
7 May 2026
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 5 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 5 samples
Nitrate2.1 mg/Llimit 50 mg/L · 1 sample

Measured values 2024–2026

The highest measured value of each parameter in the samples from the water systems that supply the municipality, and the share of the limit it reaches.

ParameterHighest valueAgainst the limit
E. coli0 per 100 mLlimit 0 per 100 mL · 58 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 58 samples
Coliform bacteria27 per 100 mLlimit 0 per 100 mL · 58 samples · 1× over the limit
Clostridium perfringens0 per 100 mLlimit 0 per 100 mL · 31 samples
Nitrate5.3 mg/Llimit 50 mg/L · 12 samples
Nitritebelow 0.007 mg/Llimit 0.5 mg/L · 12 samples
Nitrate/50 + nitrite/30.11limit 1 · 12 samples
PFAS, totalbelow 0.03 µg/Llimit 0.5 µg/L · 1 sample
PFOAbelow 0.0005 µg/Lpart of the 20-PFAS sum, limit 0.1 µg/L · 1 sample
PFOSbelow 0.0005 µg/Lpart of the 20-PFAS sum, limit 0.1 µg/L · 1 sample
Arsenicbelow 1 µg/Llimit 10 µg/L · 7 samples
Uranium1.1 µg/Llimit 30 µg/L · 4 samples
Copper0.011 mg/Llimit 2 mg/L · 7 samples
Nickelbelow 1 µg/Llimit 20 µg/L · 4 samples
Cadmium0.033 µg/Llimit 5 µg/L · 7 samples
Chromiumbelow 1 µg/Llimit 50 µg/L · 7 samples
Antimonybelow 1 µg/Llimit 10 µg/L · 7 samples
Selenium1.4 µg/Llimit 20 µg/L · 7 samples
Boronbelow 0.01 mg/Llimit 1.5 mg/L · 7 samples
Fluoridebelow 0.1 mg/Llimit 1.5 mg/L · 12 samples
Trihalomethanes, total7.3 µg/Llimit 100 µg/L · 5 samples
Haloacetic acidsbelow 5 µg/Llimit 60 µg/L · 1 sample
Chlorate0.01 mg/Llimit 0.25 mg/L · 2 samples
Chloritebelow 0.01 mg/Llimit 0.25 mg/L · 2 samples
Bisphenol A0.08 µg/Llimit 2.5 µg/L · 1 sample
Free chlorine0.33 mg/Lno limit value · 27 samples
Manganesebelow 1 µg/Llimit 50 µg/L · 7 samples
Ironbelow 10 µg/Llimit 200 µg/L · 7 samples
Aluminiumbelow 10 µg/Llimit 200 µg/L · 7 samples
Ammoniumbelow 0.013 mg/Llimit 0.5 mg/L · 12 samples
Chloride9 mg/Llimit 250 mg/L · 12 samples
Sulphate12 mg/Llimit 250 mg/L · 12 samples
Sodium3.7 mg/Llimit 200 mg/L · 7 samples
pH7.1–7.9limit 6.5–9.5 · 58 samples
Electrical conductivity485 µS/cmlimit 2,500 µS/cm · 58 samples

Non-compliant samples

What the laboratory found in the samples that were not compliant:

Samples by year

012242016: 22 samples, all compliant’162017: 24 samples, 2 non-compliant’172018: 24 samples, 1 non-compliant’182019: 24 samples, 1 non-compliant’192020: 21 samples, 2 non-compliant’202021: 21 samples, all compliant’212022: 21 samples, 1 non-compliant’222023: 21 samples, 3 non-compliant’232024: 21 samples, all compliant’242025: 21 samples, 2 non-compliant’252026: 16 samples, 1 non-compliant’26
compliant non-compliant · Drinking-water samples in Cerknica since 2016

What you can do

How to read the results

The ratings are a Draga Slovenija summary, not an official NIJZ rating.

More about water and property in Cerknica

Estimate a property’s valueProperty prices in Cerknica

Drinking water in neighbouring municipalities in the Primorsko-notranjska region: Ilirska Bistrica, Postojna, Pivka, Loška dolina, Bloke.

Explanations of the parameters:

Follow the results for your address

When the state monitoring publishes a non-compliant result for the area by your address, we e-mail you (results come out about once a month). One address is free. This is not an urgent boil-water alert; the operator announces those.

Find your address and turn on following →

Monthly e-mail roundup: drinking water and the property market

Once a month: new drinking-water results and how the property market moved, in one e-mail. This is our existing monthly newsletter; we do not send a report for a single municipality. Unsubscribe with one click in every e-mail.

Email address only. Privacy statement.

Source: NIJZ and NLZOH, mpv.si; latest sample 31 Aug 2026. Processing: Draga Slovenija.

Frequently asked questions

Is the water in Cerknica safe to drink?

These are past results, not a verdict on the water today; the operator announces current restrictions (boil-water notices). In 2024–2026 the state monitoring took 58 samples of drinking water on the 8 supply areas serving the municipality, of which 3 were not compliant. Details by water system are above.

How hard is the water in Cerknica?

By the operators’ figures and, where there are none, our estimate 14.3 °dH (averaged over the water systems, weighted by users), which is hard water. To set appliances, use your own system’s figure.

Who operates the water supply in Cerknica?

JP Komunala Cerknica d.o.o.. The largest supply area is CERKNICA - RAKEK.

Where are the official drinking-water test results?

The state monitoring publishes its results at mpv.si, and the operator publishes an annual report on internal control on its website. This page summarises the state monitoring since 2016.

AI chat

Ask the data, in plain language

The AI chat finds the answer in the official register and shows it with a table you can download and a link into the map. Free; it only needs an account.

For example: Which municipalities issued the most building permits last year?

Open the AI chat

AI chat