Drinking water: Komunala Zagorje
Komunala Zagorje supplies drinking water to 10,061 users in the municipality of Zagorje ob Savi. In 2024–2026 the state monitoring sampled 8 water systems of this operator and took 69 samples, of which 3 were not compliant. Water hardness differs between systems, 12.9–17.5 °dH; most customers get hard water (≈14.6 °dH).
These are state monitoring results from 2024–2026, not a notice about the water today. Current notices (boil-water, do-not-use) are published by the water-system operator on its website.
Notices from Komunala Zagorje
Boil-water notices, bans on use and supply interruptions are published by Komunala Zagorje on its website and in local media. This page shows state monitoring results, not current notices. What a boil-water notice means is explained on Boiling water.
Water systems run by Komunala Zagorje
| Water system | Municipalities | Users | Hardness (°dH) | Assessment |
|---|---|---|---|---|
| Šemnik - Strahovlje | Zagorje ob Savi | 6,713 | ≈13.7 | compliant |
| Izlake | Zagorje ob Savi | 1,112 | ≈17.5 | Occasional non-compliance |
| Rove | Zagorje ob Savi | 902 | ≈16.9 | compliant |
| Kotredež - Lošč | Zagorje ob Savi | 690 | ≈14.9 | compliant |
| Podkum | 384 | ≈15.6 | Occasional non-compliance | |
| Peške - Kandrše | Zagorje ob Savi | 113 | ≈15.6 | compliant |
| Potoška vas | Zagorje ob Savi | 105 | ≈12.9 | Faecal bacteria in 1 sample |
| Prvine | Zagorje ob Savi | 42 | ≈15 | compliant |
Measured values 2024–2026
| Parameter | Highest value | Against the limit |
|---|---|---|
| E. coli | 0 per 100 mL | limit 0 per 100 mL · 69 samples |
| Enterococci | 1 per 100 mL | limit 0 per 100 mL · 69 samples · 1× over the limit |
| Coliform bacteria | 1 per 100 mL | limit 0 per 100 mL · 69 samples · 1× over the limit |
| Clostridium perfringens | 0 per 100 mL | limit 0 per 100 mL · 44 samples |
| Nitrate | 9.7 mg/L | limit 50 mg/L · 16 samples |
| Nitrite | below 0.007 mg/L | limit 0.5 mg/L · 16 samples |
| Nitrate/50 + nitrite/3 | 0.19 | limit 1 · 16 samples |
| Arsenic | below 1 µg/L | limit 10 µg/L · 10 samples |
| Uranium | 1 µg/L | limit 30 µg/L · 5 samples |
| Copper | 0.073 mg/L | limit 2 mg/L · 10 samples |
| Nickel | below 1 µg/L | limit 20 µg/L · 5 samples |
| Cadmium | 0.03 µg/L | limit 5 µg/L · 10 samples |
| Chromium | below 1 µg/L | limit 50 µg/L · 10 samples |
| Antimony | 1.2 µg/L | limit 10 µg/L · 10 samples |
| Selenium | 1.2 µg/L | limit 20 µg/L · 10 samples |
| Boron | 0.03 mg/L | limit 1.5 mg/L · 10 samples |
| Fluoride | below 0.1 mg/L | limit 1.5 mg/L · 16 samples |
| Trihalomethanes, total | 6.2 µg/L | limit 100 µg/L · 11 samples |
| Chlorate | 0.04 mg/L | limit 0.25 mg/L · 3 samples |
| Chlorite | below 0.01 mg/L | limit 0.25 mg/L · 3 samples |
| Free chlorine | 0.27 mg/L | no limit value · 41 samples |
| Manganese | 2.1 µg/L | limit 50 µg/L · 10 samples |
| Iron | 450 µg/L | limit 200 µg/L · 10 samples · 1× over the limit |
| Aluminium | 66 µg/L | limit 200 µg/L · 10 samples |
| Ammonium | below 0.013 mg/L | limit 0.5 mg/L · 16 samples |
| Chloride | 6.6 mg/L | limit 250 mg/L · 16 samples |
| Sulphate | 20 mg/L | limit 250 mg/L · 16 samples |
| Sodium | 6.4 mg/L | limit 200 mg/L · 10 samples |
| pH | 7.1–8.1 | limit 6.5–9.5 · 69 samples |
| Electrical conductivity | 552 µS/cm | limit 2,500 µS/cm · 69 samples |
Non-compliant samples
- · IZLAKE · Iron 450 µg/L limit 200 µg/L
- · PODKUM · Coliform bacteria 1 per 100 mL limit 0 per 100 mL
- · Potoška vas · Enterococci 1 per 100 mL limit 0 per 100 mL
Samples by year
Municipalities
What you can do
- Check which system supplies you. The operator is named on your water bill; the address search only shows the nearest sampling points.
- Follow the operator’s notices. Boil-water notices and bans on use are announced by the operator, usually on its website and in local media.
- Mind the building’s own pipes. The samples show the water in the network. In older buildings (before about 1970) let the water run for a while in the morning; an analysis of your own tap can be ordered from NLZOH or another accredited laboratory.
- Filters and softeners. A softener reduces limescale but removes neither bacteria nor other contaminants. A carbon filter improves taste and needs regular replacement. Against bacteria, boil the water as the operator instructs.
- Own wells and springs are not part of the state monitoring; their owner is responsible for them and for testing the water.
- Before buying a property ask whether it is connected to the public supply or has its own source, who the operator is, and look at the operator’s recent notices.
How to read the results
- All samples compliant all samples in this period met the Drinking Water Decree.
- Mostly compliant (municipality) non-compliant samples came only from smaller systems that together supply less than a quarter of the users there.
- Occasional non-compliance individual samples were not compliant on indicator parameters (iron, manganese, turbidity, coliform bacteria), which point to a problem in treatment or the network but are not a health limit.
- Faecal bacteria in 1 sample E. coli or enterococci were found in one sample. That is a serious finding, but a single one; check its date and the later samples.
- Repeated or health-relevant non-compliance faecal bacteria (E. coli, enterococci) in two or more samples, or a health-based chemical limit (nitrate, pesticides, lead, arsenic …) exceeded at least once.
The ratings are a Draga Slovenija summary, not an official NIJZ rating.
Source: NIJZ and NLZOH, mpv.si; latest sample 31 Aug 2026. Processing: Draga Slovenija.
Frequently asked questions
Is the water from Komunala Zagorje safe to drink?
Komunala Zagorje supplies drinking water to 10,061 users in the municipality of Zagorje ob Savi. In 2024–2026 the state monitoring sampled 8 water systems of this operator and took 69 samples, of which 3 were not compliant. The operator announces current restrictions on use.
How hard is the water from Komunala Zagorje?
Water hardness differs between systems, 12.9–17.5 °dH; most customers get hard water (≈14.6 °dH).
Where does Komunala Zagorje publish boil-water notices?
On its website and in local media. A boil-water notice applies until the operator lifts it.