Draga SlovenijaDraga Slovenija

Drinking water: Šemnik - Strahovlje water system

All samples compliant

The Šemnik - Strahovlje water system (operator Komunala Zagorje) supplies 6,713 users in the municipality of Zagorje ob Savi. In 2024–2026 the state monitoring took 18 samples and all were compliant.

These are state monitoring results from 2024–2026, not a notice about the water today. Current notices (boil-water, do-not-use) are published by the water-system operator on its website.

Samples 2024–2026181 supply area
Non-compliant00%
Hardness (estimate)13.7 °dHmoderately hard
Users6,713Komunala Zagorje

Supply areas

ŠEMNIK - STRAHOVLJE

All samples compliant

Operator: Komunala Zagorje · 6,713 users · water system Šemnik - Strahovlje

Samples 2024–2026
18, all compliant
Water source
Influenced by surface water
Treatment
Chlorine gas disinfection
Hardness (estimate)
≈13.7 °dH, moderately hard
Latest sample
17 Aug 2026
E. coli0 per 100 mLlimit 0 per 100 mL · 18 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 18 samples
Nitrate6.2 mg/Llimit 50 mg/L · 5 samples
Arsenicbelow 1 µg/Llimit 10 µg/L · 4 samples
Manganesebelow 1 µg/Llimit 50 µg/L · 4 samples
Iron18 µg/Llimit 200 µg/L · 4 samples

Measured values 2024–2026

ParameterHighest valueAgainst the limit
E. coli0 per 100 mLlimit 0 per 100 mL · 18 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 18 samples
Coliform bacteria0 per 100 mLlimit 0 per 100 mL · 18 samples
Clostridium perfringens0 per 100 mLlimit 0 per 100 mL · 18 samples
Nitrate6.2 mg/Llimit 50 mg/L · 5 samples
Nitritebelow 0.007 mg/Llimit 0.5 mg/L · 5 samples
Nitrate/50 + nitrite/30.12limit 1 · 5 samples
Arsenicbelow 1 µg/Llimit 10 µg/L · 4 samples
Uranium0.34 µg/Llimit 30 µg/L · 2 samples
Copper0.0048 mg/Llimit 2 mg/L · 4 samples
Nickelbelow 1 µg/Llimit 20 µg/L · 2 samples
Cadmiumbelow 0.1 µg/Llimit 5 µg/L · 4 samples
Chromiumbelow 1 µg/Llimit 50 µg/L · 4 samples
Antimonybelow 1 µg/Llimit 10 µg/L · 4 samples
Selenium1.1 µg/Llimit 20 µg/L · 4 samples
Boronbelow 0.01 mg/Llimit 1.5 mg/L · 4 samples
Fluoridebelow 0.1 mg/Llimit 1.5 mg/L · 5 samples
Trihalomethanes, total2.5 µg/Llimit 100 µg/L · 4 samples
Free chlorine0.27 mg/Lno limit value · 10 samples
Manganesebelow 1 µg/Llimit 50 µg/L · 4 samples
Iron18 µg/Llimit 200 µg/L · 4 samples
Aluminium66 µg/Llimit 200 µg/L · 4 samples
Ammoniumbelow 0.013 mg/Llimit 0.5 mg/L · 5 samples
Chloride2.7 mg/Llimit 250 mg/L · 5 samples
Sulphate15 mg/Llimit 250 mg/L · 5 samples
Sodium0.77 mg/Llimit 200 mg/L · 4 samples
pH7.1–7.8limit 6.5–9.5 · 18 samples
Electrical conductivity443 µS/cmlimit 2,500 µS/cm · 18 samples

Samples by year

0592016: 9 samples, 1 non-compliant’162017: 9 samples, all compliant’172018: 9 samples, all compliant’182019: 9 samples, all compliant’192020: 7 samples, all compliant’202021: 7 samples, all compliant’212022: 7 samples, 1 non-compliant’222023: 7 samples, all compliant’232024: 7 samples, all compliant’242025: 7 samples, all compliant’252026: 4 samples, all compliant’26
compliant non-compliant · Samples from the Šemnik - Strahovlje water system

Municipalities

Drinking water in Zagorje ob Savi

What you can do

How to read the results

The ratings are a Draga Slovenija summary, not an official NIJZ rating.

Follow the results for your address

When the state monitoring publishes a non-compliant result for the area by your address, we e-mail you (results come out about once a month). One address is free. This is not an urgent boil-water alert; the operator announces those.

Find your address and turn on following →

Source: NIJZ and NLZOH, mpv.si; latest sample 31 Aug 2026. Processing: Draga Slovenija.

Frequently asked questions

Is the water from the Šemnik - Strahovlje water system safe to drink?

The Šemnik - Strahovlje water system (operator Komunala Zagorje) supplies 6,713 users in the municipality of Zagorje ob Savi. In 2024–2026 the state monitoring took 18 samples and all were compliant. The operator announces current restrictions on use.

How hard is the water from the Šemnik - Strahovlje water system?

Estimated from electrical conductivity at 13.7 °dH, which is moderately hard water.

AI chat

Ask the data, in plain language

The AI chat finds the answer in the official register and shows it with a table you can download and a link into the map. Free; it only needs an account.

For example: Which municipalities issued the most building permits last year?

Open the AI chat

AI chat