Draga SlovenijaDraga Slovenija

Drinking water in Žirovnica

Repeated or health-relevant non-compliance

In 2024–2026 the state monitoring took 40 samples of drinking water on the 3 supply areas serving the municipality, of which 4 were not compliant (E. coli or enterococci bacteria in 3 samples). By the operators’ figures and our estimate the water is soft (≈6.1 °dH).

These are state monitoring results from 2024–2026, not a notice about the water today. Current notices (boil-water, do-not-use) are published by the water-system operator on its website.

Samples 2024–2026403 supply areas
Non-compliant410%
Hardness (operator and estimate)6.1 °dHsoft
Nitrate, median2.3 mg/Llimit 50 mg/L

Water systems in Žirovnica

In 2024–2026 the state monitoring sampled 3 supply areas; the largest, JESENICE ZAVRŠNICA, supplies 10,779 users. The address search shows the nearest sampling points, not necessarily your water system; the system that supplies you is named on your water bill.

JESENICE ZAVRŠNICA: repeated non-complianceAJDNA: compliantŽirovnicaBregZabreznicaRodineVrbaDoslovčeMosteSmokučRadovljicaTržičBled2 km
  • compliant
  • repeated non-compliance

Sampling points of the state monitoring in recent years, coloured by the result for the area. Click a dot for the area's figures. Place names © OpenStreetMap

JESENICE ZAVRŠNICA

Repeated or health-relevant non-compliance

Operator: JEKO · 10,779 users · water system Jesenice-Završnica

The area also extends into Jesenice.

Samples 2024–2026
26, 4 non-compliant
Water source
Influenced by surface water
Treatment
Sodium hypochlorite disinfection
Hardness (operator)
5.5–6.5 °dH, soft source
Latest sample
23 Jun 2026
E. coli3 per 100 mLlimit 0 per 100 mL · 26 samples · 3× over the limit
Enterococci0 per 100 mLlimit 0 per 100 mL · 26 samples
Nitrate2.3 mg/Llimit 50 mg/L · 6 samples
PFAS, totalbelow 0.03 µg/Llimit 0.5 µg/L · 1 sample
Arsenicbelow 1 µg/Llimit 10 µg/L · 6 samples
Manganesebelow 10 µg/Llimit 50 µg/L · 6 samples
Ironbelow 10 µg/Llimit 200 µg/L · 6 samples
Non-compliant samples (4)
  • · E. coli 1 per 100 mL limit 0 per 100 mL, Coliform bacteria 9 per 100 mL limit 0 per 100 mL
  • · E. coli 3 per 100 mL limit 0 per 100 mL, Coliform bacteria 6 per 100 mL limit 0 per 100 mL
  • · E. coli 3 per 100 mL limit 0 per 100 mL, Coliform bacteria 9 per 100 mL limit 0 per 100 mL
  • · Coliform bacteria 7 per 100 mL limit 0 per 100 mL

AJDNA

All samples compliant

Operator: JEKO · 1,168 users · water system Ajdna

Samples 2024–2026
11, all compliant
Water source
Groundwater, not influenced by surface water
Treatment
No treatment
Hardness (estimate)
≈6.7 °dH, soft
Latest sample
28 Jul 2026
E. coli0 per 100 mLlimit 0 per 100 mL · 11 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 11 samples
Nitrate3 mg/Llimit 50 mg/L · 3 samples
PFAS, totalbelow 0.03 µg/Llimit 0.5 µg/L · 1 sample
Arsenicbelow 1 µg/Llimit 10 µg/L · 2 samples
Manganesebelow 10 µg/Llimit 50 µg/L · 2 samples
Ironbelow 10 µg/Llimit 200 µg/L · 2 samples

URBAS - VALVASOR

All samples compliant

Operator: PD RADOVLJICA · 1 user · water system Valvasorjev Dom

Samples 2024–2026
3, all compliant
Water source
Groundwater, not influenced by surface water
Hardness (estimate)
≈6 °dH, soft
Latest sample
28 May 2026
E. coli0 per 100 mLlimit 0 per 100 mL · 3 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 3 samples
Nitrate2.7 mg/Llimit 50 mg/L · 1 sample

Measured values 2024–2026

The highest measured value of each parameter in the samples from the water systems that supply the municipality, and the share of the limit it reaches.

ParameterHighest valueAgainst the limit
E. coli3 per 100 mLlimit 0 per 100 mL · 40 samples · 3× over the limit
Enterococci0 per 100 mLlimit 0 per 100 mL · 40 samples
Coliform bacteria9 per 100 mLlimit 0 per 100 mL · 40 samples · 4× over the limit
Clostridium perfringens0 per 100 mLlimit 0 per 100 mL · 5 samples
Nitrate3 mg/Llimit 50 mg/L · 10 samples
Nitritebelow 0.01 mg/Llimit 0.5 mg/L · 10 samples
Nitrate/50 + nitrite/30.06limit 1 · 10 samples
PFAS, totalbelow 0.03 µg/Llimit 0.5 µg/L · 2 samples
PFOAbelow 0.0005 µg/Lpart of the 20-PFAS sum, limit 0.1 µg/L · 2 samples
PFOSbelow 0.0005 µg/Lpart of the 20-PFAS sum, limit 0.1 µg/L · 2 samples
Arsenicbelow 1 µg/Llimit 10 µg/L · 8 samples
Uraniumbelow 10 µg/Llimit 30 µg/L · 5 samples
Copperbelow 0.01 mg/Llimit 2 mg/L · 8 samples
Nickelbelow 10 µg/Llimit 20 µg/L · 4 samples
Cadmiumbelow 1 µg/Llimit 5 µg/L · 8 samples
Chromiumbelow 10 µg/Llimit 50 µg/L · 8 samples
Antimonybelow 1 µg/Llimit 10 µg/L · 8 samples
Seleniumbelow 1 µg/Llimit 20 µg/L · 8 samples
Boronbelow 0.01 mg/Llimit 1.5 mg/L · 8 samples
Fluoridebelow 1 mg/Llimit 1.5 mg/L · 10 samples
Trihalomethanes, totalbelow 2 µg/Llimit 100 µg/L · 1 sample
Haloacetic acidsbelow 5 µg/Llimit 60 µg/L · 2 samples
Tetrachloroethene + trichloroethenebelow 2 µg/Llimit 10 µg/L · 3 samples
Bisphenol Abelow 0.025 µg/Llimit 2.5 µg/L · 1 sample
Free chlorine0.11 mg/Lno limit value · 6 samples
Manganesebelow 10 µg/Llimit 50 µg/L · 8 samples
Ironbelow 10 µg/Llimit 200 µg/L · 8 samples
Aluminiumbelow 10 µg/Llimit 200 µg/L · 8 samples
Ammoniumbelow 0.02 mg/Llimit 0.5 mg/L · 10 samples
Chloridebelow 1 mg/Llimit 250 mg/L · 10 samples
Sulphate2.9 mg/Llimit 250 mg/L · 10 samples
Sodium0.41 mg/Llimit 200 mg/L · 8 samples
pH7.8–8.3limit 6.5–9.5 · 40 samples
Electrical conductivity224 µS/cmlimit 2,500 µS/cm · 40 samples

Non-compliant samples

What the laboratory found in the samples that were not compliant:

Samples by year

09172016: 17 samples, 1 non-compliant’162017: 17 samples, 2 non-compliant’172018: 17 samples, 2 non-compliant’182019: 17 samples, 5 non-compliant’192020: 14 samples, 2 non-compliant’202021: 14 samples, 1 non-compliant’212022: 14 samples, 1 non-compliant’222023: 14 samples, 3 non-compliant’232024: 14 samples, all compliant’242025: 17 samples, 4 non-compliant’252026: 9 samples, all compliant’26
compliant non-compliant · Drinking-water samples in Žirovnica since 2016

What you can do

How to read the results

The ratings are a Draga Slovenija summary, not an official NIJZ rating.

More about water and property in Žirovnica

Estimate a property’s valueProperty prices in Žirovnica

Drinking water in neighbouring municipalities in the Gorenjska region: Jesenice, Kranj, Cerklje na Gorenjskem, Tržič, Škofja Loka, Kranjska Gora, Radovljica, Bohinj, Bled, Naklo, Šenčur, Preddvor, Železniki, Žiri, Jezersko, Gorenja vas - Poljane, Gorje.

Explanations of the parameters:

Follow the results for your address

When the state monitoring publishes a non-compliant result for the area by your address, we e-mail you (results come out about once a month). One address is free. This is not an urgent boil-water alert; the operator announces those.

Find your address and turn on following →

Monthly e-mail roundup: drinking water and the property market

Once a month: new drinking-water results and how the property market moved, in one e-mail. This is our existing monthly newsletter; we do not send a report for a single municipality. Unsubscribe with one click in every e-mail.

Email address only. Privacy statement.

Source: NIJZ and NLZOH, mpv.si; latest sample 31 Aug 2026. Processing: Draga Slovenija.

Frequently asked questions

Is the water in Žirovnica safe to drink?

These are past results, not a verdict on the water today; the operator announces current restrictions (boil-water notices). In 2024–2026 the state monitoring took 40 samples of drinking water on the 3 supply areas serving the municipality, of which 4 were not compliant (E. coli or enterococci bacteria in 3 samples). Details by water system are above.

How hard is the water in Žirovnica?

By the operators’ figures and, where there are none, our estimate 6.1 °dH (averaged over the water systems, weighted by users), which is soft water. To set appliances, use your own system’s figure.

Who operates the water supply in Žirovnica?

JEKO, PD RADOVLJICA. The largest supply area is JESENICE ZAVRŠNICA.

Where are the official drinking-water test results?

The state monitoring publishes its results at mpv.si, and the operator publishes an annual report on internal control on its website. This page summarises the state monitoring since 2016.

AI chat

Ask the data, in plain language

The AI chat finds the answer in the official register and shows it with a table you can download and a link into the map. Free; it only needs an account.

For example: Which municipalities issued the most building permits last year?

Open the AI chat