Draga SlovenijaDraga Slovenija

Drinking water in Šmarje pri Jelšah

Mostly compliant

In 2024–2026 the state monitoring took 74 samples of drinking water on the 6 supply areas serving the municipality, of which 1 was not compliant (E. coli or enterococci bacteria in 1 sample). The non-compliant samples came from smaller systems; most residents get water from systems without any. The water is estimated to be hard (≈17.5 °dH).

These are state monitoring results from 2024–2026, not a notice about the water today. Current notices (boil-water, do-not-use) are published by the water-system operator on its website.

Samples 2024–2026746 supply areas
Non-compliant11.4%
Hardness (estimate)17.5 °dHhard
Nitrate, median6.2 mg/Llimit 50 mg/L

Water systems in Šmarje pri Jelšah

In 2024–2026 the state monitoring sampled 6 supply areas; the largest, LOKA - ŠMARJE -ROGAŠKA, supplies 12,771 users. The address search shows the nearest sampling points, not necessarily your water system; the system that supplies you is named on your water bill.

Supply areas at a glance
AreaUsersRating
LOKA - ŠMARJE -ROGAŠKA12,771compliant
DOLGA GORA - ŠMARJE PRI JELŠAH575Faecal bacteria in 1 sample
PIJOVCI - PRELOGE289compliant
ZBELOVSKA GORA - PEČICA (NUNSKA GORA)262compliant
BOBOVO149compliant
SLADKA GORA122compliant
LOKA - ŠMARJE -ROGAŠKA: compliantLOKA - ŠMARJE -ROGAŠKA: compliantLOKA - ŠMARJE -ROGAŠKA: compliantDOLGA GORA - ŠMARJE PRI JELŠAH: occasional non-compliancePIJOVCI - PRELOGE: compliantZBELOVSKA GORA - PEČICA (NUNSKA GORA): compliantBOBOVO: compliantSLADKA GORA: compliantŠmarje pri JelšahGrobelnoKristan VrhMestinjeZibikaHajnskoLemberg pri ŠmarjuZavrše pri GrobelnemBodrišna vasKoretnoPodčetrtekRogaška SlatinaSlovenske KonjicePoljčane5 km
  • compliant
  • occasional non-compliance

Sampling points of the state monitoring in recent years, coloured by the result for the area. Click a dot for the area's figures. Place names © OpenStreetMap

LOKA - ŠMARJE -ROGAŠKA

All samples compliant

Operator: OKP Rogaška Slatina · 12,771 users · water system Loka -Šmarje- Rogaška

The area also extends into Rogaška Slatina.

Samples 2024–2026
46, all compliant
Water source
Groundwater, not influenced by surface water
Treatment
Regular disinfection, chlorine gas disinfection
Hardness (estimate)
≈17.5 °dH, hard
Latest sample
15 Jul 2026
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 46 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 46 samples
Nitrate6.2 mg/Llimit 50 mg/L · 7 samples
Single pesticide (highest)below 0.05 µg/Llimit 0.1 µg/L · 3 samples
PFAS, totalbelow 0.03 µg/Llimit 0.5 µg/L · 1 sample
Arsenicbelow 1 µg/Llimit 10 µg/L · 7 samples
Manganesebelow 1 µg/Llimit 50 µg/L · 7 samples
Ironbelow 10 µg/Llimit 200 µg/L · 7 samples

DOLGA GORA - ŠMARJE PRI JELŠAH

Faecal bacteria in 1 sample

Operator: OKP Rogaška Slatina · 575 users · water system Dolga Gora - Šmarje pri Jelšah

Samples 2024–2026
9, 1 non-compliant
Water source
Groundwater, not influenced by surface water
Treatment
Regular disinfection, sodium hypochlorite disinfection
Hardness (estimate)
≈17.3 °dH, hard
Latest sample
11 May 2026
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 9 samples
Enterococci4 per 100 mLlimit 0 per 100 mL · 9 samples · 1× over the limit
Nitrate9.3 mg/Llimit 50 mg/L · 1 sample
PFAS, totalbelow 0.03 µg/Llimit 0.5 µg/L · 1 sample
Arsenicbelow 1 µg/Llimit 10 µg/L · 1 sample
Manganesebelow 1 µg/Llimit 50 µg/L · 1 sample
Ironbelow 10 µg/Llimit 200 µg/L · 1 sample
Non-compliant samples (1)
  • · Enterococci 4 per 100 mL limit 0 per 100 mL, Coliform bacteria 54 per 100 mL limit 0 per 100 mL

PIJOVCI - PRELOGE

All samples compliant

Operator: OKP Rogaška Slatina · 289 users · water system Pijovci - Preloge

Samples 2024–2026
5, all compliant
Water source
Groundwater, not influenced by surface water
Treatment
Regular disinfection, sodium hypochlorite disinfection
Hardness (estimate)
≈17.6 °dH, hard
Latest sample
11 Mar 2026
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 5 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 5 samples

ZBELOVSKA GORA - PEČICA (NUNSKA GORA)

All samples compliant

Operator: OKP Rogaška Slatina · 262 users · water system Zbelovska Gora - Pečica (Nunska Gora)

Samples 2024–2026
5, all compliant
Water source
Groundwater, not influenced by surface water
Treatment
Regular disinfection, sodium hypochlorite disinfection
Hardness (estimate)
≈14.8 °dH, hard
Latest sample
11 Mar 2026
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 5 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 5 samples
Nitrate2.7 mg/Llimit 50 mg/L · 1 sample

BOBOVO

All samples compliant

Operator: OKP Rogaška Slatina · 149 users · water system Bobovo

Samples 2024–2026
5, all compliant
Water source
Groundwater, not influenced by surface water
Treatment
Regular disinfection, sodium hypochlorite disinfection
Hardness (estimate)
≈17.9 °dH, hard
Latest sample
11 Mar 2026
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 5 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 5 samples

SLADKA GORA

All samples compliant

Operator: OKP Rogaška Slatina · 122 users · water system Sladka Gora

Samples 2024–2026
4, all compliant
Water source
Groundwater, not influenced by surface water
Treatment
Occasional disinfection, sodium hypochlorite disinfection
Hardness (estimate)
≈18.3 °dH, hard
Latest sample
14 May 2026
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 4 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 4 samples

Measured values 2024–2026

The highest measured value of each parameter in the samples from the water systems that supply the municipality, and the share of the limit it reaches.

ParameterHighest valueAgainst the limit
E. coli0 per 100 mLlimit 0 per 100 mL · 74 samples
Enterococci4 per 100 mLlimit 0 per 100 mL · 74 samples · 1× over the limit
Coliform bacteria54 per 100 mLlimit 0 per 100 mL · 74 samples · 1× over the limit
Nitrate9.3 mg/Llimit 50 mg/L · 9 samples
Nitritebelow 0.007 mg/Llimit 0.5 mg/L · 9 samples
Nitrate/50 + nitrite/30.19limit 1 · 9 samples
Single pesticide (highest)below 0.05 µg/Llimit 0.1 µg/L · 3 samples
Pesticides, totalbelow 0.05 µg/Llimit 0.5 µg/L · 2 samples
PFAS, totalbelow 0.03 µg/Llimit 0.5 µg/L · 2 samples
PFOAbelow 0.0005 µg/Lpart of the 20-PFAS sum, limit 0.1 µg/L · 2 samples
PFOSbelow 0.0005 µg/Lpart of the 20-PFAS sum, limit 0.1 µg/L · 2 samples
Arsenicbelow 1 µg/Llimit 10 µg/L · 8 samples
Uranium0.32 µg/Llimit 30 µg/L · 5 samples
Copper0.006 mg/Llimit 2 mg/L · 8 samples
Nickelbelow 1 µg/Llimit 20 µg/L · 4 samples
Cadmium0.026 µg/Llimit 5 µg/L · 8 samples
Chromiumbelow 1 µg/Llimit 50 µg/L · 8 samples
Antimonybelow 1 µg/Llimit 10 µg/L · 8 samples
Selenium1.2 µg/Llimit 20 µg/L · 8 samples
Boronbelow 0.01 mg/Llimit 1.5 mg/L · 8 samples
Fluoridebelow 0.1 mg/Llimit 1.5 mg/L · 9 samples
Trihalomethanes, total2.1 µg/Llimit 100 µg/L · 7 samples
Haloacetic acidsbelow 5 µg/Llimit 60 µg/L · 2 samples
Chloratebelow 0.01 mg/Llimit 0.25 mg/L · 5 samples
Chlorite0.03 mg/Llimit 0.25 mg/L · 5 samples
Free chlorine0.9 mg/Lno limit value · 53 samples
Manganesebelow 1 µg/Llimit 50 µg/L · 8 samples
Ironbelow 10 µg/Llimit 200 µg/L · 8 samples
Aluminium10 µg/Llimit 200 µg/L · 8 samples
Ammoniumbelow 0.013 mg/Llimit 0.5 mg/L · 9 samples
Chloride5 mg/Llimit 250 mg/L · 9 samples
Sulphate24 mg/Llimit 250 mg/L · 9 samples
Sodium3.2 mg/Llimit 200 mg/L · 8 samples
pH6.9–7.9limit 6.5–9.5 · 74 samples
Electrical conductivity657 µS/cmlimit 2,500 µS/cm · 74 samples

Non-compliant samples

What the laboratory found in the samples that were not compliant:

Samples by year

018352016: 35 samples, 1 non-compliant’162017: 35 samples, 1 non-compliant’172018: 35 samples, 1 non-compliant’182019: 35 samples, all compliant’192020: 26 samples, all compliant’202021: 31 samples, all compliant’212022: 31 samples, 1 non-compliant’222023: 31 samples, 1 non-compliant’232024: 29 samples, all compliant’242025: 31 samples, 1 non-compliant’252026: 14 samples, all compliant’26
compliant non-compliant · Drinking-water samples in Šmarje pri Jelšah since 2016

What you can do

How to read the results

The ratings are a Draga Slovenija summary, not an official NIJZ rating.

More about water and property in Šmarje pri Jelšah

Estimate a property’s valueProperty prices in Šmarje pri Jelšah

Drinking water in neighbouring municipalities in the Savinjska region: Laško, Celje, Vojnik, Štore, Velenje, Šoštanj, Dobrna, Šentjur, Gornji Grad, Nazarje, Zreče, Žalec, Kozje, Dobje, Šmartno ob Paki, Slovenske Konjice, Ljubno, Luče, Prebold, Braslovče, Polzela, Rogaška Slatina, Mozirje, Rečica ob Savinji, Vitanje, Podčetrtek, Rogatec, Vransko, Solčava, Tabor.

Explanations of the parameters:

Follow the results for your address

When the state monitoring publishes a non-compliant result for the area by your address, we e-mail you (results come out about once a month). One address is free. This is not an urgent boil-water alert; the operator announces those.

Find your address and turn on following →

Monthly e-mail roundup: drinking water and the property market

Once a month: new drinking-water results and how the property market moved, in one e-mail. This is our existing monthly newsletter; we do not send a report for a single municipality. Unsubscribe with one click in every e-mail.

Email address only. Privacy statement.

Source: NIJZ and NLZOH, mpv.si; latest sample 31 Aug 2026. Processing: Draga Slovenija.

Frequently asked questions

Is the water in Šmarje pri Jelšah safe to drink?

These are past results, not a verdict on the water today; the operator announces current restrictions (boil-water notices). In 2024–2026 the state monitoring took 74 samples of drinking water on the 6 supply areas serving the municipality, of which 1 was not compliant (E. coli or enterococci bacteria in 1 sample). The non-compliant samples came from smaller systems; most residents get water from systems without any. Details by water system are above.

How hard is the water in Šmarje pri Jelšah?

Estimated from electrical conductivity at 17.5 °dH, which is hard water. The operator publishes the exact value for its network.

Who operates the water supply in Šmarje pri Jelšah?

OKP Rogaška Slatina. The largest supply area is LOKA - ŠMARJE -ROGAŠKA.

Where are the official drinking-water test results?

The state monitoring publishes its results at mpv.si, and the operator publishes an annual report on internal control on its website. This page summarises the state monitoring since 2016.

AI chat

Ask the data, in plain language

The AI chat finds the answer in the official register and shows it with a table you can download and a link into the map. Free; it only needs an account.

For example: Which municipalities issued the most building permits last year?

Open the AI chat

AI chat