In 2024–2026 the state monitoring took 72 samples of drinking water on the 12 supply areas serving the municipality, of which 3 were not compliant. The non-compliant samples came from smaller systems; most residents get water from systems without any. The water is estimated to be hard (≈14.1 °dH).

These are state monitoring results from 2024–2026, not a notice about the water today. Current notices (boil-water, do-not-use) are published by the water-system operator on its website.

Samples 2024–20267212 supply areas
Non-compliant34.2%
Hardness (estimate)14.1 °dHhard
Nitrate, median3.7 mg/Llimit 50 mg/L

Water systems in Zreče

In 2024–2026 the state monitoring sampled 12 supply areas; the largest, ZREČE 1 (zgornji sistem), supplies 3,600 users. The address search shows the nearest sampling points, not necessarily your water system; the system that supplies you is named on your water bill.

Supply areas at a glance
AreaUsersRating
ZREČE 1 (zgornji sistem)3,600compliant
STRANICE1,300compliant
ZREČE 2 (spodnji sistem)1,160compliant
RESNIK172compliant
BRINJEVA GORA168compliant
ZLAKOVA150compliant
SKOMARJE126compliant
Padeški vrh122occasional non-compliance
GORENJE100compliant
Sistem za oskrbo s pitno vodo FIJAVŽ92compliant
HOTEL PLANJA ROGLA20compliant
TURISTIČNA KMETIJA KOVŠE - KOČNIK1occasional non-compliance
ZREČE 1 (zgornji sistem): compliantSTRANICE: compliantZREČE 2 (spodnji sistem): compliantRESNIK: compliantBRINJEVA GORA: compliantZLAKOVA: compliantSKOMARJE: compliantPadeški vrh: occasional non-complianceGORENJE: compliantSistem za oskrbo s pitno vodo FIJAVŽ: compliantHOTEL PLANJA ROGLA: compliantZrečeSkomarjePadeški VrhStraniceResnikZlakovaGorenjePlanina na PohorjuČrešnovaBoharinaSlovenska BistricaLovrenc na PohorjuVojnikMislinjaRušeRibnica na Pohorju5 km
  • compliant
  • occasional non-compliance

Sampling points of the state monitoring in recent years, coloured by the result for the area. Click a dot for the area's figures. Place names © OpenStreetMap

ZREČE 1 (zgornji sistem)

All samples compliant

Operator: Komunala Slovenska Bistrica · 3,600 users · water system Zreče

Samples 2024–2026
10, all compliant
Water source
Groundwater, not influenced by surface water
Treatment
Regular disinfection, sodium hypochlorite disinfection, calcium hypochlorite disinfection
Hardness (estimate)
≈16.9 °dH, hard
Latest sample
14 May 2026
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 10 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 10 samples
Nitrate4.4 mg/Llimit 50 mg/L · 2 samples
Single pesticide (highest)below 0.05 µg/Llimit 0.1 µg/L · 1 sample
Arsenicbelow 1 µg/Llimit 10 µg/L · 2 samples
Manganesebelow 1 µg/Llimit 50 µg/L · 2 samples
Ironbelow 10 µg/Llimit 200 µg/L · 2 samples

STRANICE

All samples compliant

Operator: Komunala Slovenska Bistrica · 1,300 users · water system Stranice

Samples 2024–2026
9, all compliant
Water source
Groundwater, not influenced by surface water
Treatment
Regular disinfection, sodium hypochlorite disinfection
Hardness (estimate)
≈14 °dH, hard
Latest sample
11 May 2026
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 9 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 9 samples
Nitrate3.9 mg/Llimit 50 mg/L · 3 samples
Arsenicbelow 1 µg/Llimit 10 µg/L · 2 samples
Manganesebelow 1 µg/Llimit 50 µg/L · 2 samples
Iron17 µg/Llimit 200 µg/L · 2 samples

ZREČE 2 (spodnji sistem)

All samples compliant

Operator: Komunala Slovenska Bistrica · 1,160 users · water system Zreče

Samples 2024–2026
10, all compliant
Water source
Groundwater, not influenced by surface water
Treatment
Regular disinfection, sodium hypochlorite disinfection
Hardness (estimate)
≈12.5 °dH, moderately hard
Latest sample
14 May 2026
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 10 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 10 samples
Nitrate6.2 mg/Llimit 50 mg/L · 2 samples
Arsenicbelow 1 µg/Llimit 10 µg/L · 2 samples
Manganesebelow 1 µg/Llimit 50 µg/L · 2 samples
Ironbelow 10 µg/Llimit 200 µg/L · 2 samples

RESNIK

All samples compliant

Operator: Komunala Slovenska Bistrica · 172 users · water system Resnik

Samples 2024–2026
5, all compliant
Water source
Groundwater, not influenced by surface water
Treatment
Other agent, regular disinfection, calcium hypochlorite disinfection
Hardness (estimate)
≈6.2 °dH, soft
Latest sample
28 Apr 2026
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 5 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 5 samples
Nitrate3.3 mg/Llimit 50 mg/L · 2 samples

BRINJEVA GORA

All samples compliant

Operator: Komunala Slovenska Bistrica · 168 users · water system Brinjeva Gora

Samples 2024–2026
5, all compliant
Water source
Groundwater, not influenced by surface water
Treatment
Other agent, regular disinfection, calcium hypochlorite disinfection
Hardness (estimate)
≈6.9 °dH, soft
Latest sample
14 May 2026
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 5 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 5 samples
Nitrate7.1 mg/Llimit 50 mg/L · 2 samples

ZLAKOVA

All samples compliant

Operator: Komunala Slovenska Bistrica · 150 users · water system Zlakova

Samples 2024–2026
5, all compliant
Water source
Groundwater, not influenced by surface water
Treatment
Other agent, regular disinfection, calcium hypochlorite disinfection
Hardness (estimate)
≈4.5 °dH, soft
Latest sample
16 Mar 2026
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 5 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 5 samples

SKOMARJE

All samples compliant

Operator: Komunala Slovenska Bistrica · 126 users · water system Skomarje

Samples 2024–2026
5, all compliant
Water source
Groundwater, not influenced by surface water
Treatment
Other agent, regular disinfection, calcium hypochlorite disinfection
Hardness (estimate)
≈2.3 °dH, soft
Latest sample
16 Mar 2026
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 5 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 5 samples
Nitrate2.1 mg/Llimit 50 mg/L · 2 samples

Padeški vrh

Occasional non-compliance

Operator: KS Gorenje - Padeški vrh · 122 users · water system Padeški vrh

Samples 2024–2026
5, 1 non-compliant
Water source
Influenced by surface water
Hardness (estimate)
≈4.4 °dH, soft
Latest sample
30 Mar 2026
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 5 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 5 samples
Nitrate1.3 mg/Llimit 50 mg/L · 1 sample
Lead0.35 µg/Llimit 10 µg/L · 3 samples
Non-compliant samples (1)
  • · Coliform bacteria 21 per 100 mL limit 0 per 100 mL

GORENJE

All samples compliant

Operator: KS Gorenje - Padeški vrh · 100 users · water system Gorenje

Samples 2024–2026
5, all compliant
Water source
Groundwater, not influenced by surface water
Treatment
Other agent, regular disinfection, calcium hypochlorite disinfection
Hardness (estimate)
≈3.6 °dH, soft
Latest sample
16 Mar 2026
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 5 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 5 samples
Nitrate7.5 mg/Llimit 50 mg/L · 1 sample

Sistem za oskrbo s pitno vodo FIJAVŽ

All samples compliant

Operator: Komunala Slovenska Bistrica · 92 users · water system Zreče

Samples 2024–2026
5, all compliant
Water source
Groundwater, not influenced by surface water
Treatment
Regular disinfection, sodium hypochlorite disinfection
Hardness (estimate)
≈10.2 °dH, moderately hard
Latest sample
16 Mar 2026
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 5 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 5 samples

HOTEL PLANJA ROGLA

All samples compliant

Operator: UNIOR d.d. - Program Turizem · 20 users · water system Hotel Planja Rogla

Samples 2024–2026
5, all compliant
Water source
Influenced by surface water
Treatment
Filters, regular disinfection, chlorine gas disinfection
Hardness (estimate)
≈2 °dH, soft
Latest sample
28 Apr 2026
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 5 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 5 samples
Nitrate2.3 mg/Llimit 50 mg/L · 1 sample

TURISTIČNA KMETIJA KOVŠE - KOČNIK

Occasional non-compliance

Operator: TK KOVŠE - KOČNIK · 1 user · water system Turistična Kmetija Kovše - Kočnik

Samples 2024–2026
3, 2 non-compliant
Water source
Influenced by surface water
Hardness (estimate)
≈11.7 °dH, moderately hard
Latest sample
18 Jun 2026
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 3 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 3 samples
Non-compliant samples (2)
  • · Coliform bacteria 2 per 100 mL limit 0 per 100 mL
  • · Coliform bacteria 33 per 100 mL limit 0 per 100 mL

Measured values 2024–2026

The highest measured value of each parameter in the samples from the water systems that supply the municipality, and the share of the limit it reaches.

ParameterHighest valueAgainst the limit
E. coli0 per 100 mLlimit 0 per 100 mL · 72 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 72 samples
Coliform bacteria33 per 100 mLlimit 0 per 100 mL · 72 samples · 3× over the limit
Clostridium perfringens0 per 100 mLlimit 0 per 100 mL · 12 samples
Nitrate7.5 mg/Llimit 50 mg/L · 16 samples
Nitritebelow 0.01 mg/Llimit 0.5 mg/L · 16 samples
Nitrate/50 + nitrite/30.15limit 1 · 16 samples
Single pesticide (highest)below 0.05 µg/Llimit 0.1 µg/L · 1 sample
Lead0.35 µg/Llimit 10 µg/L · 3 samples
Arsenicbelow 1 µg/Llimit 10 µg/L · 6 samples
Uranium1.1 µg/Llimit 30 µg/L · 3 samples
Copper0.0062 mg/Llimit 2 mg/L · 6 samples
Nickelbelow 1 µg/Llimit 20 µg/L · 3 samples
Cadmium0.073 µg/Llimit 5 µg/L · 6 samples
Chromiumbelow 1 µg/Llimit 50 µg/L · 6 samples
Antimonybelow 1 µg/Llimit 10 µg/L · 6 samples
Selenium1.3 µg/Llimit 20 µg/L · 6 samples
Boronbelow 0.01 mg/Llimit 1.5 mg/L · 6 samples
Fluoridebelow 0.1 mg/Llimit 1.5 mg/L · 16 samples
Trihalomethanes, total3.2 µg/Llimit 100 µg/L · 10 samples
Chloratebelow 0.05 mg/Llimit 0.25 mg/L · 11 samples
Chloritebelow 0.05 mg/Llimit 0.25 mg/L · 11 samples
Free chlorine0.67 mg/Lno limit value · 50 samples
Manganesebelow 1 µg/Llimit 50 µg/L · 6 samples
Iron17 µg/Llimit 200 µg/L · 6 samples
Aluminium26 µg/Llimit 200 µg/L · 6 samples
Ammoniumbelow 0.05 mg/Llimit 0.5 mg/L · 16 samples
Chloride22 mg/Llimit 250 mg/L · 16 samples
Sulphate13 mg/Llimit 250 mg/L · 16 samples
Sodium7.7 mg/Llimit 200 mg/L · 6 samples
pH6.5–8.2limit 6.5–9.5 · 72 samples
Electrical conductivity522 µS/cmlimit 2,500 µS/cm · 72 samples

Non-compliant samples

What the laboratory found in the samples that were not compliant:

Samples by year

016312016: 22 samples, 1 non-compliant’162017: 22 samples, all compliant’172018: 29 samples, all compliant’182019: 31 samples, 2 non-compliant’192020: 28 samples, all compliant’202021: 28 samples, 2 non-compliant’212022: 28 samples, 1 non-compliant’222023: 28 samples, 2 non-compliant’232024: 28 samples, 1 non-compliant’242025: 30 samples, 1 non-compliant’252026: 14 samples, 1 non-compliant’26
compliant non-compliant · Drinking-water samples in Zreče since 2016

What you can do

How to read the results

The ratings are a Draga Slovenija summary, not an official NIJZ rating.

More about water and property in Zreče

Estimate a property’s valueProperty prices in Zreče

Drinking water in neighbouring municipalities in the Savinjska region: Laško, Celje, Vojnik, Štore, Velenje, Šoštanj, Dobrna, Šentjur, Šmarje pri Jelšah, Gornji Grad, Nazarje, Žalec, Kozje, Dobje, Šmartno ob Paki, Slovenske Konjice, Ljubno, Luče, Prebold, Braslovče, Polzela, Rogaška Slatina, Mozirje, Rečica ob Savinji, Vitanje, Podčetrtek, Rogatec, Vransko, Solčava, Tabor.

Explanations of the parameters:

Follow the results for your address

When the state monitoring publishes a non-compliant result for the area by your address, we e-mail you (results come out about once a month). One address is free. This is not an urgent boil-water alert; the operator announces those.

Find your address and turn on following →

Monthly e-mail roundup: drinking water and the property market

Once a month: new drinking-water results and how the property market moved, in one e-mail. This is our existing monthly newsletter; we do not send a report for a single municipality. Unsubscribe with one click in every e-mail.

Email address only. Privacy statement.

Source: NIJZ and NLZOH, mpv.si; latest sample 31 Aug 2026. Processing: Draga Slovenija.

Frequently asked questions

Is the water in Zreče safe to drink?

These are past results, not a verdict on the water today; the operator announces current restrictions (boil-water notices). In 2024–2026 the state monitoring took 72 samples of drinking water on the 12 supply areas serving the municipality, of which 3 were not compliant. The non-compliant samples came from smaller systems; most residents get water from systems without any. Details by water system are above.

How hard is the water in Zreče?

Estimated from electrical conductivity at 14.1 °dH, which is hard water. The operator publishes the exact value for its network.

Who operates the water supply in Zreče?

Komunala Slovenska Bistrica d.o.o., KS Gorenje - Padeški vrh, UNIOR d.d. - Program Turizem, TK KOVŠE - KOČNIK. The largest supply area is ZREČE 1 (zgornji sistem).

Where are the official drinking-water test results?

The state monitoring publishes its results at mpv.si, and the operator publishes an annual report on internal control on its website. This page summarises the state monitoring since 2016.

AI chat

Ask the data, in plain language

The AI chat finds the answer in the official register and shows it with a table you can download and a link into the map. Free; it only needs an account.

For example: Which municipalities issued the most building permits last year?

Open the AI chat

AI chat