Occasional non-compliance

The Sistem B water system (operator Vodovod sistema B) supplies 41,781 users in the municipalities of Murska Sobota, Moravske Toplice, Kuzma, Cankova, Rogašovci, Tišina, Ljutomer. In 2024–2026 the state monitoring took 78 samples, of which 2 were not compliant.

These are state monitoring results from 2024–2026, not a notice about the water today. Current notices (boil-water, do-not-use) are published by the water-system operator on its website.

Samples 2024–2026781 supply area
Non-compliant22.6%
Hardness (operator)14.8 °dHhard
Users41,781Vodovod sistema B

Supply areas

SISTEM B

Occasional non-compliance

Operator: Vodovod sistema B · 41,781 users · water system Sistem B

Samples 2024–2026
78, 2 non-compliant
Water source
Groundwater, not influenced by surface water
Treatment
Chlorine gas disinfection
Hardness (operator)
14.8 °dH, hard source 2015 (older figure)
Latest sample
17 Aug 2026
E. coli0 per 100 mLlimit 0 per 100 mL · 78 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 78 samples
Nitrate26 mg/Llimit 50 mg/L · 8 samples
Single pesticide (highest)0.034 µg/L (Metolaklor ESA)limit 0.1 µg/L · 4 samples
PFAS, totalbelow 0.03 µg/Llimit 0.5 µg/L · 1 sample
Lead2.5 µg/Llimit 10 µg/L · 4 samples
Arsenicbelow 1 µg/Llimit 10 µg/L · 7 samples
Manganese2.1 µg/Llimit 50 µg/L · 7 samples
Ironbelow 10 µg/Llimit 200 µg/L · 7 samples
Non-compliant samples (2)
  • · Coliform bacteria 1 per 100 mL limit 0 per 100 mL
  • · marked non-compliant; the published data gives no reason

Measured values 2024–2026

ParameterHighest valueAgainst the limit
E. coli0 per 100 mLlimit 0 per 100 mL · 78 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 78 samples
Coliform bacteria1 per 100 mLlimit 0 per 100 mL · 78 samples · 1× over the limit
Nitrate26 mg/Llimit 50 mg/L · 8 samples
Nitritebelow 0.007 mg/Llimit 0.5 mg/L · 8 samples
Nitrate/50 + nitrite/30.52limit 1 · 8 samples
Single pesticide (highest)0.034 µg/L (Metolaklor ESA)limit 0.1 µg/L · 4 samples
Pesticides, total0.03 µg/Llimit 0.5 µg/L · 1 sample
PFAS, totalbelow 0.03 µg/Llimit 0.5 µg/L · 1 sample
PFOAbelow 0.0005 µg/Lpart of the 20-PFAS sum, limit 0.1 µg/L · 1 sample
PFOSbelow 0.0005 µg/Lpart of the 20-PFAS sum, limit 0.1 µg/L · 1 sample
Lead2.5 µg/Llimit 10 µg/L · 4 samples
Arsenicbelow 1 µg/Llimit 10 µg/L · 7 samples
Uranium2.9 µg/Llimit 30 µg/L · 4 samples
Copper0.023 mg/Llimit 2 mg/L · 7 samples
Nickelbelow 1 µg/Llimit 20 µg/L · 4 samples
Cadmium0.03 µg/Llimit 5 µg/L · 7 samples
Chromiumbelow 1 µg/Llimit 50 µg/L · 7 samples
Antimonybelow 1 µg/Llimit 10 µg/L · 7 samples
Selenium1.1 µg/Llimit 20 µg/L · 7 samples
Boron0.023 mg/Llimit 1.5 mg/L · 7 samples
Fluoride0.11 mg/Llimit 1.5 mg/L · 8 samples
Trihalomethanes, total9.6 µg/Llimit 100 µg/L · 6 samples
Haloacetic acidsbelow 5 µg/Llimit 60 µg/L · 1 sample
Chloratebelow 0.01 mg/Llimit 0.25 mg/L · 3 samples
Chloritebelow 0.01 mg/Llimit 0.25 mg/L · 3 samples
Tetrachloroethene + trichloroethenebelow 0.2 µg/Llimit 10 µg/L · 5 samples
Benzenebelow 0.2 µg/Llimit 1 µg/L · 1 sample
PAHs, totalbelow 0.004 µg/Llimit 0.1 µg/L · 1 sample
Benzo(a)pyrenebelow 0.004 µg/Llimit 0.01 µg/L · 1 sample
Free chlorine0.18 mg/Lno limit value · 45 samples
Manganese2.1 µg/Llimit 50 µg/L · 7 samples
Ironbelow 10 µg/Llimit 200 µg/L · 7 samples
Aluminiumbelow 10 µg/Llimit 200 µg/L · 7 samples
Ammoniumbelow 0.013 mg/Llimit 0.5 mg/L · 8 samples
Chloride21 mg/Llimit 250 mg/L · 8 samples
Sulphate46 mg/Llimit 250 mg/L · 8 samples
Sodium14 mg/Llimit 200 mg/L · 7 samples
pH6.8–7.5limit 6.5–9.5 · 78 samples
Electrical conductivity610 µS/cmlimit 2,500 µS/cm · 78 samples

Non-compliant samples

Samples by year

021412016: 32 samples, 1 non-compliant’162017: 32 samples, all compliant’172018: 40 samples, all compliant’182019: 41 samples, 2 non-compliant’192020: 25 samples, 1 non-compliant’202021: 25 samples, 1 non-compliant’212022: 25 samples, 1 non-compliant’222023: 27 samples, all compliant’232024: 27 samples, 1 non-compliant’242025: 35 samples, 1 non-compliant’252026: 16 samples, all compliant’26
compliant non-compliant · Samples from the Sistem B water system

Municipalities

Drinking water in Murska Sobota · Drinking water in Moravske Toplice · Drinking water in Kuzma · Drinking water in Cankova · Drinking water in Rogašovci · Drinking water in Tišina · Drinking water in Ljutomer

What you can do

How to read the results

The ratings are a Draga Slovenija summary, not an official NIJZ rating.

Follow the results for your address

When the state monitoring publishes a non-compliant result for the area by your address, we e-mail you (results come out about once a month). One address is free. This is not an urgent boil-water alert; the operator announces those.

Find your address and turn on following →

Source: NIJZ and NLZOH, mpv.si; latest sample 31 Aug 2026. Processing: Draga Slovenija.

Frequently asked questions

Is the water from the Sistem B water system safe to drink?

The Sistem B water system (operator Vodovod sistema B) supplies 41,781 users in the municipalities of Murska Sobota, Moravske Toplice, Kuzma, Cankova, Rogašovci, Tišina, Ljutomer. In 2024–2026 the state monitoring took 78 samples, of which 2 were not compliant. The operator announces current restrictions on use.

How hard is the water from the Sistem B water system?

According to the operator 14.8 °dH, which is hard water.