Draga SlovenijaDraga Slovenija

Drinking water: Mrzlek water system

Occasional non-compliance

The Mrzlek water system (operator VIK NG) supplies 35,223 users in the municipalities of Brda, Nova Gorica, Miren - Kostanjevica. In 2024–2026 the state monitoring took 66 samples, of which 3 were not compliant.

These are state monitoring results from 2024–2026, not a notice about the water today. Current notices (boil-water, do-not-use) are published by the water-system operator on its website.

Samples 2024–2026662 supply areas
Non-compliant34.5%
Hardness (operator)7.5 °dHsoft
Users35,223VIK NG

Supply areas

NOVA GORICA

Occasional non-compliance

Operator: VIK Nova Gorica · 29,670 users · water system Mrzlek

Samples 2024–2026
50, 1 non-compliant
Water source
Influenced by surface water
Treatment
Filters, coagulation, flocculation, chlorine gas disinfection, ozone disinfection, UV disinfection
Hardness (operator)
7–8 °dH, soft source
Latest sample
27 Aug 2026
E. coli0 per 100 mLlimit 0 per 100 mL · 50 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 50 samples
Nitrate4.3 mg/Llimit 50 mg/L · 7 samples
PFAS, totalbelow 0.03 µg/Llimit 0.5 µg/L · 1 sample
Arsenic0.1 µg/Llimit 10 µg/L · 7 samples
Manganese0.15 µg/Llimit 50 µg/L · 7 samples
Ironbelow 40 µg/Llimit 200 µg/L · 7 samples
Non-compliant samples (1)
  • · Coliform bacteria 1 per 100 mL limit 0 per 100 mL

BRDA

Occasional non-compliance

Operator: VIK Nova Gorica · 5,553 users · water system Mrzlek

Samples 2024–2026
16, 2 non-compliant
Water source
Influenced by surface water
Treatment
Filters, coagulation, flocculation, regular disinfection, chlorine gas disinfection, ozone disinfection, UV disinfection
Hardness (operator)
7–8 °dH, soft source
Latest sample
26 Aug 2026
E. coli0 per 100 mLlimit 0 per 100 mL · 16 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 16 samples
Nitrate4.4 mg/Llimit 50 mg/L · 4 samples
PFAS, totalbelow 0.03 µg/Llimit 0.5 µg/L · 1 sample
Arsenicbelow 0.1 µg/Llimit 10 µg/L · 5 samples
Manganese0.33 µg/Llimit 50 µg/L · 5 samples
Ironbelow 40 µg/Llimit 200 µg/L · 5 samples
Non-compliant samples (2)
  • · marked non-compliant; the published data gives no reason
  • · Coliform bacteria 80 per 100 mL limit 0 per 100 mL

Measured values 2024–2026

ParameterHighest valueAgainst the limit
E. coli0 per 100 mLlimit 0 per 100 mL · 66 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 66 samples
Coliform bacteria80 per 100 mLlimit 0 per 100 mL · 66 samples · 2× over the limit
Clostridium perfringens0 per 100 mLlimit 0 per 100 mL · 66 samples
Nitrate4.4 mg/Llimit 50 mg/L · 11 samples
Nitritebelow 0.013 mg/Llimit 0.5 mg/L · 11 samples
Nitrate/50 + nitrite/30.09limit 1 · 11 samples
PFAS, totalbelow 0.03 µg/Llimit 0.5 µg/L · 2 samples
PFOAbelow 0.0005 µg/Lpart of the 20-PFAS sum, limit 0.1 µg/L · 2 samples
PFOSbelow 0.0005 µg/Lpart of the 20-PFAS sum, limit 0.1 µg/L · 2 samples
Arsenic0.1 µg/Llimit 10 µg/L · 12 samples
Uranium0.18 µg/Llimit 30 µg/L · 7 samples
Copper0.014 mg/Llimit 2 mg/L · 12 samples
Nickel3.3 µg/Llimit 20 µg/L · 7 samples
Cadmiumbelow 0.02 µg/Llimit 5 µg/L · 12 samples
Chromium3.6 µg/Llimit 50 µg/L · 12 samples
Mercury0.012 µg/Llimit 1 µg/L · 13 samples
Antimony0.2 µg/Llimit 10 µg/L · 12 samples
Selenium0.14 µg/Llimit 20 µg/L · 12 samples
Boron0.0057 mg/Llimit 1.5 mg/L · 12 samples
Fluoridebelow 1 mg/Llimit 1.5 mg/L · 11 samples
Trihalomethanes, total9.6 µg/Llimit 100 µg/L · 10 samples
Haloacetic acidsbelow 5 µg/Llimit 60 µg/L · 2 samples
Bromatebelow 3 µg/Llimit 10 µg/L · 24 samples
Free chlorine0.22 mg/Lno limit value · 40 samples
Manganese0.33 µg/Llimit 50 µg/L · 12 samples
Ironbelow 40 µg/Llimit 200 µg/L · 12 samples
Aluminium76 µg/Llimit 200 µg/L · 47 samples
Ammoniumbelow 0.02 mg/Llimit 0.5 mg/L · 11 samples
Chloride2.4 mg/Llimit 250 mg/L · 11 samples
Sulphate3.2 mg/Llimit 250 mg/L · 11 samples
Sodium1.8 mg/Llimit 200 mg/L · 12 samples
pH7.6–8.2limit 6.5–9.5 · 66 samples
Electrical conductivity365 µS/cmlimit 2,500 µS/cm · 66 samples

Non-compliant samples

Samples by year

016312016: 31 samples, all compliant’162017: 31 samples, all compliant’172018: 31 samples, 1 non-compliant’182019: 31 samples, all compliant’192020: 26 samples, all compliant’202021: 26 samples, all compliant’212022: 26 samples, all compliant’222023: 20 samples, all compliant’232024: 26 samples, 2 non-compliant’242025: 26 samples, 1 non-compliant’252026: 14 samples, all compliant’26
compliant non-compliant · Samples from the Mrzlek water system

Municipalities

Drinking water in Brda · Drinking water in Nova Gorica · Drinking water in Miren - Kostanjevica

What you can do

How to read the results

The ratings are a Draga Slovenija summary, not an official NIJZ rating.

Follow the results for your address

When the state monitoring publishes a non-compliant result for the area by your address, we e-mail you (results come out about once a month). One address is free. This is not an urgent boil-water alert; the operator announces those.

Find your address and turn on following →

Source: NIJZ and NLZOH, mpv.si; latest sample 31 Aug 2026. Processing: Draga Slovenija.

Frequently asked questions

Is the water from the Mrzlek water system safe to drink?

The Mrzlek water system (operator VIK NG) supplies 35,223 users in the municipalities of Brda, Nova Gorica, Miren - Kostanjevica. In 2024–2026 the state monitoring took 66 samples, of which 3 were not compliant. The operator announces current restrictions on use.

How hard is the water from the Mrzlek water system?

According to the operator 7.5 °dH, which is soft water.

AI chat

Ask the data, in plain language

The AI chat finds the answer in the official register and shows it with a table you can download and a link into the map. Free; it only needs an account.

For example: Which municipalities issued the most building permits last year?

Open the AI chat

AI chat