JEZERSKO - ZGORNJE
All samples compliant- Samples 2024–2026
- 9, all compliant
- Water source
- Influenced by surface water
- Treatment
- Regular disinfection, UV disinfection
- Hardness (estimate)
- ≈7.8 °dH, soft
- Latest sample
- 4 May 2026
The Jezersko - Zgornje water system (operator Komunala Kranj, d.o.o.) supplies 575 users in the municipality of Jezersko. In 2024–2026 the state monitoring took 9 samples and all were compliant.
These are state monitoring results from 2024–2026, not a notice about the water today. Current notices (boil-water, do-not-use) are published by the water-system operator on its website.
| Parameter | Highest value | Against the limit |
|---|---|---|
| E. coli | 0 per 100 mL | limit 0 per 100 mL · 9 samples |
| Enterococci | 0 per 100 mL | limit 0 per 100 mL · 9 samples |
| Coliform bacteria | 0 per 100 mL | limit 0 per 100 mL · 9 samples |
| Clostridium perfringens | 0 per 100 mL | limit 0 per 100 mL · 9 samples |
| Nitrate | 2.7 mg/L | limit 50 mg/L · 2 samples |
| Nitrite | below 0.01 mg/L | limit 0.5 mg/L · 2 samples |
| Nitrate/50 + nitrite/3 | 0.054 | limit 1 · 2 samples |
| Arsenic | below 1 µg/L | limit 10 µg/L · 2 samples |
| Uranium | below 10 µg/L | limit 30 µg/L · 1 sample |
| Copper | below 0.01 mg/L | limit 2 mg/L · 2 samples |
| Nickel | below 10 µg/L | limit 20 µg/L · 1 sample |
| Cadmium | below 1 µg/L | limit 5 µg/L · 2 samples |
| Chromium | below 10 µg/L | limit 50 µg/L · 2 samples |
| Antimony | below 1 µg/L | limit 10 µg/L · 2 samples |
| Selenium | below 1 µg/L | limit 20 µg/L · 2 samples |
| Boron | below 0.01 mg/L | limit 1.5 mg/L · 2 samples |
| Fluoride | below 1 mg/L | limit 1.5 mg/L · 2 samples |
| Trihalomethanes, total | below 2 µg/L | limit 100 µg/L · 1 sample |
| Chlorate | below 0.002 mg/L | limit 0.25 mg/L · 1 sample |
| Chlorite | below 0 mg/L | limit 0.25 mg/L · 1 sample |
| Free chlorine | below 0.05 mg/L | no limit value · 6 samples |
| Manganese | below 10 µg/L | limit 50 µg/L · 2 samples |
| Iron | 28 µg/L | limit 200 µg/L · 2 samples |
| Aluminium | below 10 µg/L | limit 200 µg/L · 2 samples |
| Ammonium | below 0.02 mg/L | limit 0.5 mg/L · 2 samples |
| Chloride | below 1 mg/L | limit 250 mg/L · 2 samples |
| Sulphate | 7 mg/L | limit 250 mg/L · 2 samples |
| Sodium | 0.5 mg/L | limit 200 mg/L · 2 samples |
| pH | 7.7–7.9 | limit 6.5–9.5 · 9 samples |
| Electrical conductivity | 253 µS/cm | limit 2,500 µS/cm · 9 samples |
The ratings are a Draga Slovenija summary, not an official NIJZ rating.
When the state monitoring publishes a non-compliant result for the area by your address, we e-mail you (results come out about once a month). One address is free. This is not an urgent boil-water alert; the operator announces those.
Source: NIJZ and NLZOH, mpv.si; latest sample 31 Aug 2026. Processing: Draga Slovenija.
The Jezersko - Zgornje water system (operator Komunala Kranj, d.o.o.) supplies 575 users in the municipality of Jezersko. In 2024–2026 the state monitoring took 9 samples and all were compliant. The operator announces current restrictions on use.
Estimated from electrical conductivity at 7.8 °dH, which is soft water.