Draga SlovenijaDraga Slovenija

Drinking water: Jezersko - Zgornje water system

All samples compliant

The Jezersko - Zgornje water system (operator Komunala Kranj, d.o.o.) supplies 575 users in the municipality of Jezersko. In 2024–2026 the state monitoring took 9 samples and all were compliant.

These are state monitoring results from 2024–2026, not a notice about the water today. Current notices (boil-water, do-not-use) are published by the water-system operator on its website.

Samples 2024–202691 supply area
Non-compliant00%
Hardness (estimate)7.8 °dHsoft
Users575Komunala Kranj, d.o.o.

Supply areas

JEZERSKO - ZGORNJE

All samples compliant

Operator: Komunala Kranj · 575 users · water system Jezersko - Zgornje

Samples 2024–2026
9, all compliant
Water source
Influenced by surface water
Treatment
Regular disinfection, UV disinfection
Hardness (estimate)
≈7.8 °dH, soft
Latest sample
4 May 2026
E. coli0 per 100 mLlimit 0 per 100 mL · 9 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 9 samples
Nitrate2.7 mg/Llimit 50 mg/L · 2 samples
Arsenicbelow 1 µg/Llimit 10 µg/L · 2 samples
Manganesebelow 10 µg/Llimit 50 µg/L · 2 samples
Iron28 µg/Llimit 200 µg/L · 2 samples

Measured values 2024–2026

ParameterHighest valueAgainst the limit
E. coli0 per 100 mLlimit 0 per 100 mL · 9 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 9 samples
Coliform bacteria0 per 100 mLlimit 0 per 100 mL · 9 samples
Clostridium perfringens0 per 100 mLlimit 0 per 100 mL · 9 samples
Nitrate2.7 mg/Llimit 50 mg/L · 2 samples
Nitritebelow 0.01 mg/Llimit 0.5 mg/L · 2 samples
Nitrate/50 + nitrite/30.054limit 1 · 2 samples
Arsenicbelow 1 µg/Llimit 10 µg/L · 2 samples
Uraniumbelow 10 µg/Llimit 30 µg/L · 1 sample
Copperbelow 0.01 mg/Llimit 2 mg/L · 2 samples
Nickelbelow 10 µg/Llimit 20 µg/L · 1 sample
Cadmiumbelow 1 µg/Llimit 5 µg/L · 2 samples
Chromiumbelow 10 µg/Llimit 50 µg/L · 2 samples
Antimonybelow 1 µg/Llimit 10 µg/L · 2 samples
Seleniumbelow 1 µg/Llimit 20 µg/L · 2 samples
Boronbelow 0.01 mg/Llimit 1.5 mg/L · 2 samples
Fluoridebelow 1 mg/Llimit 1.5 mg/L · 2 samples
Trihalomethanes, totalbelow 2 µg/Llimit 100 µg/L · 1 sample
Chloratebelow 0.002 mg/Llimit 0.25 mg/L · 1 sample
Chloritebelow 0 mg/Llimit 0.25 mg/L · 1 sample
Free chlorinebelow 0.05 mg/Lno limit value · 6 samples
Manganesebelow 10 µg/Llimit 50 µg/L · 2 samples
Iron28 µg/Llimit 200 µg/L · 2 samples
Aluminiumbelow 10 µg/Llimit 200 µg/L · 2 samples
Ammoniumbelow 0.02 mg/Llimit 0.5 mg/L · 2 samples
Chloridebelow 1 mg/Llimit 250 mg/L · 2 samples
Sulphate7 mg/Llimit 250 mg/L · 2 samples
Sodium0.5 mg/Llimit 200 mg/L · 2 samples
pH7.7–7.9limit 6.5–9.5 · 9 samples
Electrical conductivity253 µS/cmlimit 2,500 µS/cm · 9 samples

Samples by year

0352016: 5 samples, all compliant’162017: 5 samples, all compliant’172018: 5 samples, all compliant’182019: 5 samples, all compliant’192020: 4 samples, 1 non-compliant’202021: 4 samples, all compliant’212022: 4 samples, all compliant’222023: 4 samples, all compliant’232024: 4 samples, all compliant’242025: 4 samples, all compliant’252026: 1 sample, all compliant’26
compliant non-compliant · Samples from the Jezersko - Zgornje water system

Municipalities

Drinking water in Jezersko

What you can do

How to read the results

The ratings are a Draga Slovenija summary, not an official NIJZ rating.

Follow the results for your address

When the state monitoring publishes a non-compliant result for the area by your address, we e-mail you (results come out about once a month). One address is free. This is not an urgent boil-water alert; the operator announces those.

Find your address and turn on following →

Source: NIJZ and NLZOH, mpv.si; latest sample 31 Aug 2026. Processing: Draga Slovenija.

Frequently asked questions

Is the water from the Jezersko - Zgornje water system safe to drink?

The Jezersko - Zgornje water system (operator Komunala Kranj, d.o.o.) supplies 575 users in the municipality of Jezersko. In 2024–2026 the state monitoring took 9 samples and all were compliant. The operator announces current restrictions on use.

How hard is the water from the Jezersko - Zgornje water system?

Estimated from electrical conductivity at 7.8 °dH, which is soft water.

AI chat

Ask the data, in plain language

The AI chat finds the answer in the official register and shows it with a table you can download and a link into the map. Free; it only needs an account.

For example: Which municipalities issued the most building permits last year?

Open the AI chat

AI chat