Draga SlovenijaDraga Slovenija

Drinking water: Domanjševci water system

All samples compliant

The Domanjševci water system (operator Vodovod sistema B) supplies 837 users in the municipalities of Šalovci, Moravske Toplice. In 2024–2026 the state monitoring took 11 samples and all were compliant.

These are state monitoring results from 2024–2026, not a notice about the water today. Current notices (boil-water, do-not-use) are published by the water-system operator on its website.

Samples 2024–2026111 supply area
Non-compliant00%
Hardness (estimate)7.3 °dHsoft
Users837Vodovod sistema B

Supply areas

DOMANJŠEVCI

All samples compliant

Operator: Vodovod sistema B · 837 users · water system Domanjševci

Samples 2024–2026
11, all compliant
Water source
Groundwater, not influenced by surface water
Treatment
No treatment
Hardness (estimate)
≈7.3 °dH, soft
Latest sample
6 May 2026
E. coli0 per 100 mLlimit 0 per 100 mL · 11 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 11 samples
Nitrate18 mg/Llimit 50 mg/L · 4 samples
Single pesticide (highest)below 0.05 µg/Llimit 0.1 µg/L · 2 samples
Arsenicbelow 1 µg/Llimit 10 µg/L · 3 samples
Manganese2.1 µg/Llimit 50 µg/L · 3 samples
Ironbelow 10 µg/Llimit 200 µg/L · 3 samples

Measured values 2024–2026

ParameterHighest valueAgainst the limit
E. coli0 per 100 mLlimit 0 per 100 mL · 11 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 11 samples
Coliform bacteria0 per 100 mLlimit 0 per 100 mL · 11 samples
Nitrate18 mg/Llimit 50 mg/L · 4 samples
Nitritebelow 0.007 mg/Llimit 0.5 mg/L · 4 samples
Nitrate/50 + nitrite/30.36limit 1 · 4 samples
Single pesticide (highest)below 0.05 µg/Llimit 0.1 µg/L · 2 samples
Arsenicbelow 1 µg/Llimit 10 µg/L · 3 samples
Uranium1.7 µg/Llimit 30 µg/L · 2 samples
Copper0.017 mg/Llimit 2 mg/L · 3 samples
Nickelbelow 1 µg/Llimit 20 µg/L · 1 sample
Cadmiumbelow 0.1 µg/Llimit 5 µg/L · 3 samples
Chromiumbelow 1 µg/Llimit 50 µg/L · 3 samples
Antimonybelow 1 µg/Llimit 10 µg/L · 3 samples
Seleniumbelow 1 µg/Llimit 20 µg/L · 3 samples
Boron0.03 mg/Llimit 1.5 mg/L · 3 samples
Fluoride0.12 mg/Llimit 1.5 mg/L · 4 samples
Trihalomethanes, total15 µg/Llimit 100 µg/L · 1 sample
Tetrachloroethene + trichloroethenebelow 0.2 µg/Llimit 10 µg/L · 3 samples
Free chlorinebelow 0.1 mg/Lno limit value · 1 sample
Manganese2.1 µg/Llimit 50 µg/L · 3 samples
Ironbelow 10 µg/Llimit 200 µg/L · 3 samples
Aluminiumbelow 10 µg/Llimit 200 µg/L · 3 samples
Ammoniumbelow 0.013 mg/Llimit 0.5 mg/L · 4 samples
Chloride24 mg/Llimit 250 mg/L · 4 samples
Sulphate35 mg/Llimit 250 mg/L · 4 samples
Sodium15 mg/Llimit 200 mg/L · 3 samples
pH6.8–7.4limit 6.5–9.5 · 11 samples
Electrical conductivity542 µS/cmlimit 2,500 µS/cm · 11 samples

Samples by year

0362016: 5 samples, all compliant’162017: 5 samples, all compliant’172018: 5 samples, all compliant’182019: 5 samples, all compliant’192020: 4 samples, all compliant’202021: 4 samples, all compliant’212022: 4 samples, 1 non-compliant’222023: 4 samples, all compliant’232024: 3 samples, all compliant’242025: 6 samples, all compliant’252026: 2 samples, all compliant’26
compliant non-compliant · Samples from the Domanjševci water system

Municipalities

Drinking water in Šalovci · Drinking water in Moravske Toplice

What you can do

How to read the results

The ratings are a Draga Slovenija summary, not an official NIJZ rating.

Follow the results for your address

When the state monitoring publishes a non-compliant result for the area by your address, we e-mail you (results come out about once a month). One address is free. This is not an urgent boil-water alert; the operator announces those.

Find your address and turn on following →

Source: NIJZ and NLZOH, mpv.si; latest sample 31 Aug 2026. Processing: Draga Slovenija.

Frequently asked questions

Is the water from the Domanjševci water system safe to drink?

The Domanjševci water system (operator Vodovod sistema B) supplies 837 users in the municipalities of Šalovci, Moravske Toplice. In 2024–2026 the state monitoring took 11 samples and all were compliant. The operator announces current restrictions on use.

How hard is the water from the Domanjševci water system?

Estimated from electrical conductivity at 7.3 °dH, which is soft water.

AI chat

Ask the data, in plain language

The AI chat finds the answer in the official register and shows it with a table you can download and a link into the map. Free; it only needs an account.

For example: Which municipalities issued the most building permits last year?

Open the AI chat

AI chat