All samples compliant

The Dokležovje water system (operator Vodovod sistema B) supplies 795 users in the municipality of Beltinci. In 2024–2026 the state monitoring took 10 samples and all were compliant.

These are state monitoring results from 2024–2026, not a notice about the water today. Current notices (boil-water, do-not-use) are published by the water-system operator on its website.

Samples 2024–2026101 supply area
Non-compliant00%
Hardness (estimate)15.7 °dHhard
Users795Vodovod sistema B

Supply areas

DOKLEŽOVJE

All samples compliant

Operator: Vodovod sistema B · 795 users · water system Dokležovje

Samples 2024–2026
10, all compliant
Water source
Groundwater, not influenced by surface water
Treatment
Sodium hypochlorite disinfection
Hardness (estimate)
≈15.7 °dH, hard
Latest sample
12 May 2026
E. coli0 per 100 mLlimit 0 per 100 mL · 10 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 10 samples
Nitrate30 mg/Llimit 50 mg/L · 3 samples
Single pesticide (highest)below 0.05 µg/Llimit 0.1 µg/L · 2 samples
Arsenicbelow 1 µg/Llimit 10 µg/L · 2 samples
Manganesebelow 1 µg/Llimit 50 µg/L · 2 samples
Ironbelow 10 µg/Llimit 200 µg/L · 2 samples

Measured values 2024–2026

ParameterHighest valueAgainst the limit
E. coli0 per 100 mLlimit 0 per 100 mL · 10 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 10 samples
Coliform bacteria0 per 100 mLlimit 0 per 100 mL · 10 samples
Nitrate30 mg/Llimit 50 mg/L · 3 samples
Nitritebelow 0.007 mg/Llimit 0.5 mg/L · 3 samples
Nitrate/50 + nitrite/30.6limit 1 · 3 samples
Single pesticide (highest)below 0.05 µg/Llimit 0.1 µg/L · 2 samples
Arsenicbelow 1 µg/Llimit 10 µg/L · 2 samples
Uranium0.75 µg/Llimit 30 µg/L · 1 sample
Copper0.0088 mg/Llimit 2 mg/L · 2 samples
Nickelbelow 1 µg/Llimit 20 µg/L · 1 sample
Cadmiumbelow 0.1 µg/Llimit 5 µg/L · 2 samples
Chromiumbelow 1 µg/Llimit 50 µg/L · 2 samples
Antimonybelow 1 µg/Llimit 10 µg/L · 2 samples
Seleniumbelow 1 µg/Llimit 20 µg/L · 2 samples
Boron0.047 mg/Llimit 1.5 mg/L · 2 samples
Fluoridebelow 0.1 mg/Llimit 1.5 mg/L · 3 samples
Trihalomethanes, total0.72 µg/Llimit 100 µg/L · 2 samples
Chloratebelow 0.01 mg/Llimit 0.25 mg/L · 1 sample
Chloritebelow 0.01 mg/Llimit 0.25 mg/L · 1 sample
Tetrachloroethene + trichloroethenebelow 0.2 µg/Llimit 10 µg/L · 2 samples
Free chlorine0.12 mg/Lno limit value · 8 samples
Manganesebelow 1 µg/Llimit 50 µg/L · 2 samples
Ironbelow 10 µg/Llimit 200 µg/L · 2 samples
Aluminiumbelow 10 µg/Llimit 200 µg/L · 2 samples
Ammoniumbelow 0.013 mg/Llimit 0.5 mg/L · 3 samples
Chloride29 mg/Llimit 250 mg/L · 3 samples
Sulphate35 mg/Llimit 250 mg/L · 3 samples
Sodium18 mg/Llimit 200 mg/L · 2 samples
pH6.7–7.1limit 6.5–9.5 · 10 samples
Electrical conductivity530 µS/cmlimit 2,500 µS/cm · 10 samples

Samples by year

0352016: 5 samples, 2 non-compliant’162017: 5 samples, all compliant’172018: 5 samples, all compliant’182019: 5 samples, all compliant’192020: 4 samples, all compliant’202021: 4 samples, all compliant’212022: 4 samples, all compliant’222023: 3 samples, all compliant’232024: 4 samples, all compliant’242025: 4 samples, all compliant’252026: 2 samples, all compliant’26
compliant non-compliant · Samples from the Dokležovje water system

Municipalities

Drinking water in Beltinci

What you can do

How to read the results

The ratings are a Draga Slovenija summary, not an official NIJZ rating.

Follow the results for your address

When the state monitoring publishes a non-compliant result for the area by your address, we e-mail you (results come out about once a month). One address is free. This is not an urgent boil-water alert; the operator announces those.

Find your address and turn on following →

Source: NIJZ and NLZOH, mpv.si; latest sample 31 Aug 2026. Processing: Draga Slovenija.

Frequently asked questions

Is the water from the Dokležovje water system safe to drink?

The Dokležovje water system (operator Vodovod sistema B) supplies 795 users in the municipality of Beltinci. In 2024–2026 the state monitoring took 10 samples and all were compliant. The operator announces current restrictions on use.

How hard is the water from the Dokležovje water system?