Draga SlovenijaDraga Slovenija

Drinking water in Sežana

Occasional non-compliance

In 2024–2026 the state monitoring took 63 samples of drinking water on the 3 supply areas serving the municipality, of which 10 were not compliant (E. coli or enterococci bacteria in 5 samples). By the operators’ figures and our estimate the water is moderately hard (≈13 °dH).

These are state monitoring results from 2024–2026, not a notice about the water today. Current notices (boil-water, do-not-use) are published by the water-system operator on its website.

Samples 2024–2026633 supply areas
Non-compliant1016%
Hardness (operator and estimate)13 °dHmoderately hard
Nitrate, median4.98 mg/Llimit 50 mg/L

Water systems in Sežana

In 2024–2026 the state monitoring sampled 3 supply areas; the largest, VODOVOD BRESTOVICA, supplies 24,000 users. The address search shows the nearest sampling points, not necessarily your water system; the system that supplies you is named on your water bill.

VODOVOD BRESTOVICA: occasional non-complianceVODOVOD BRESTOVICA: occasional non-complianceŠTJAK: compliantSELA: repeated non-complianceSežanaDutovljeKrižDane pri SežaniŠtorjePovirŠmarje pri SežaniPliskovicaKomenVipavaHrpelje-KozinaAjdovščina5 km
  • compliant
  • occasional non-compliance
  • repeated non-compliance

Sampling points of the state monitoring in recent years, coloured by the result for the area. Click a dot for the area's figures. Place names © OpenStreetMap

VODOVOD BRESTOVICA

Occasional non-compliance

Operator: Kraški vodovod Sežana · 24,000 users · water system Brestovica

The area also extends into Divača, Komen, Hrpelje - Kozina.

Samples 2024–2026
53, 5 non-compliant
Water source
Influenced by surface water
Treatment
Filters, regular disinfection, chlorine gas disinfection
Hardness (operator)
13 °dH, moderately hard source
Latest sample
10 Jun 2026
E. coli0 per 100 mLlimit 0 per 100 mL · 53 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 53 samples
Nitrate5.39 mg/Llimit 50 mg/L · 7 samples
Arsenic0.16 µg/Llimit 10 µg/L · 6 samples
Manganese1.2 µg/Llimit 50 µg/L · 6 samples
Iron40 µg/Llimit 200 µg/L · 6 samples
Non-compliant samples (5)
  • · marked non-compliant; the published data gives no reason
  • · marked non-compliant; the published data gives no reason
  • · marked non-compliant; the published data gives no reason
  • · marked non-compliant; the published data gives no reason
  • · marked non-compliant; the published data gives no reason

ŠTJAK

All samples compliant

Operator: Kraški vodovod Sežana · 156 users · water system Štjak

Samples 2024–2026
5, all compliant
Water source
Influenced by surface water
Treatment
Filters, sodium hypochlorite disinfection
Hardness (operator)
15 °dH, hard source
Latest sample
25 Feb 2026
E. coli0 per 100 mLlimit 0 per 100 mL · 5 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 5 samples

SELA

Repeated or health-relevant non-compliance

Operator: OBČINA SEŽANA · 50 users · water system Sela

Samples 2024–2026
5, 5 non-compliant
Water source
Influenced by surface water
Treatment
No treatment
Hardness (estimate)
≈15.7 °dH, hard
Latest sample
17 Apr 2026
E. coli>80 per 100 mLlimit 0 per 100 mL · 4 samples · 3× over the limit
Enterococci39 per 100 mLlimit 0 per 100 mL · 5 samples · 5× over the limit
Nitrate1.26 mg/Llimit 50 mg/L · 2 samples
Lead4.6 µg/Llimit 10 µg/L · 3 samples
Non-compliant samples (5)
  • · E. coli 1 per 100 mL limit 0 per 100 mL, Enterococci 4 per 100 mL limit 0 per 100 mL, Coliform bacteria 1 per 100 mL limit 0 per 100 mL, Clostridium perfringens 2 per 100 mL limit 0 per 100 mL
  • · E. coli 2 per 100 mL limit 0 per 100 mL, Enterococci 3 per 100 mL limit 0 per 100 mL, Coliform bacteria 20 per 100 mL limit 0 per 100 mL, Clostridium perfringens 1 per 100 mL limit 0 per 100 mL
  • · E. coli >80 per 100 mL limit 0 per 100 mL, Enterococci 39 per 100 mL limit 0 per 100 mL, Coliform bacteria >80 per 100 mL limit 0 per 100 mL
  • · Enterococci 24 per 100 mL limit 0 per 100 mL, Coliform bacteria >100 per 100 mL limit 0 per 100 mL
  • · Enterococci 1 per 100 mL limit 0 per 100 mL, Coliform bacteria 6 per 100 mL limit 0 per 100 mL

Measured values 2024–2026

The highest measured value of each parameter in the samples from the water systems that supply the municipality, and the share of the limit it reaches.

ParameterHighest valueAgainst the limit
E. coli>80 per 100 mLlimit 0 per 100 mL · 62 samples · 3× over the limit
Enterococci39 per 100 mLlimit 0 per 100 mL · 63 samples · 5× over the limit
Coliform bacteria>100 per 100 mLlimit 0 per 100 mL · 63 samples · 5× over the limit
Clostridium perfringens2 per 100 mLlimit 0 per 100 mL · 63 samples · 2× over the limit
Nitrate5.39 mg/Llimit 50 mg/L · 9 samples
Nitrite0.0076 mg/Llimit 0.5 mg/L · 9 samples
Nitrate/50 + nitrite/30.11limit 1 · 9 samples
Lead4.6 µg/Llimit 10 µg/L · 3 samples
Arsenic0.16 µg/Llimit 10 µg/L · 6 samples
Uranium0.51 µg/Llimit 30 µg/L · 3 samples
Copper0.022 mg/Llimit 2 mg/L · 6 samples
Nickel0.23 µg/Llimit 20 µg/L · 3 samples
Cadmiumbelow 0.02 µg/Llimit 5 µg/L · 6 samples
Chromiumbelow 0.4 µg/Llimit 50 µg/L · 6 samples
Antimony0.087 µg/Llimit 10 µg/L · 6 samples
Selenium0.16 µg/Llimit 20 µg/L · 6 samples
Boron0.02 mg/Llimit 1.5 mg/L · 6 samples
Fluoridebelow 0.15 mg/Llimit 1.5 mg/L · 9 samples
Trihalomethanes, total23 µg/Llimit 100 µg/L · 6 samples
Chlorate0.18 mg/Llimit 0.25 mg/L · 1 sample
Chloritebelow 0.05 mg/Llimit 0.25 mg/L · 1 sample
Free chlorine0.25 mg/Lno limit value · 37 samples
Manganese1.2 µg/Llimit 50 µg/L · 6 samples
Iron40 µg/Llimit 200 µg/L · 6 samples
Aluminium4.5 µg/Llimit 200 µg/L · 6 samples
Ammoniumbelow 0.026 mg/Llimit 0.5 mg/L · 9 samples
Chloride56.1 mg/Llimit 250 mg/L · 9 samples
Sulphate14 mg/Llimit 250 mg/L · 9 samples
Sodium31 mg/Llimit 200 mg/L · 6 samples
pH7–8limit 6.5–9.5 · 63 samples
Electrical conductivity624 µS/cmlimit 2,500 µS/cm · 63 samples

Non-compliant samples

What the laboratory found in the samples that were not compliant:

Samples by year

017342016: 29 samples, 2 non-compliant’162017: 29 samples, 2 non-compliant’172018: 34 samples, 2 non-compliant’182019: 34 samples, 2 non-compliant’192020: 31 samples, 2 non-compliant’202021: 26 samples, 2 non-compliant’212022: 26 samples, 4 non-compliant’222023: 26 samples, 4 non-compliant’232024: 26 samples, 5 non-compliant’242025: 26 samples, 4 non-compliant’252026: 11 samples, 1 non-compliant’26
compliant non-compliant · Drinking-water samples in Sežana since 2016

What you can do

How to read the results

The ratings are a Draga Slovenija summary, not an official NIJZ rating.

More about water and property in Sežana

Estimate a property’s valueProperty prices in Sežana

Drinking water in neighbouring municipalities in the Obalno-kraška region: Koper, Izola, Piran, Ankaran, Divača, Komen, Hrpelje - Kozina.

Explanations of the parameters:

Follow the results for your address

When the state monitoring publishes a non-compliant result for the area by your address, we e-mail you (results come out about once a month). One address is free. This is not an urgent boil-water alert; the operator announces those.

Find your address and turn on following →

Monthly e-mail roundup: drinking water and the property market

Once a month: new drinking-water results and how the property market moved, in one e-mail. This is our existing monthly newsletter; we do not send a report for a single municipality. Unsubscribe with one click in every e-mail.

Email address only. Privacy statement.

Source: NIJZ and NLZOH, mpv.si; latest sample 31 Aug 2026. Processing: Draga Slovenija.

Frequently asked questions

Is the water in Sežana safe to drink?

These are past results, not a verdict on the water today; the operator announces current restrictions (boil-water notices). In 2024–2026 the state monitoring took 63 samples of drinking water on the 3 supply areas serving the municipality, of which 10 were not compliant (E. coli or enterococci bacteria in 5 samples). Details by water system are above.

How hard is the water in Sežana?

By the operators’ figures and, where there are none, our estimate 13 °dH (averaged over the water systems, weighted by users), which is moderately hard water. To set appliances, use your own system’s figure.

Who operates the water supply in Sežana?

KRAŠKI VODOVOD SEŽANA D.O.O., OBČINA SEŽANA. The largest supply area is VODOVOD BRESTOVICA.

Where are the official drinking-water test results?

The state monitoring publishes its results at mpv.si, and the operator publishes an annual report on internal control on its website. This page summarises the state monitoring since 2016.

AI chat

Ask the data, in plain language

The AI chat finds the answer in the official register and shows it with a table you can download and a link into the map. Free; it only needs an account.

For example: Which municipalities issued the most building permits last year?

Open the AI chat

AI chat