Draga SlovenijaDraga Slovenija

Drinking water in Hrpelje - Kozina

Occasional non-compliance

In 2024–2026 the state monitoring took 75 samples of drinking water on the 5 supply areas serving the municipality, of which 16 were not compliant (E. coli or enterococci bacteria in 6 samples). By the operators’ figures and our estimate the water is moderately hard (≈12.9 °dH).

These are state monitoring results from 2024–2026, not a notice about the water today. Current notices (boil-water, do-not-use) are published by the water-system operator on its website.

Samples 2024–2026755 supply areas
Non-compliant1621%
Hardness (operator and estimate)12.9 °dHmoderately hard
Nitrate, median4.8 mg/Llimit 50 mg/L

Water systems in Hrpelje - Kozina

In 2024–2026 the state monitoring sampled 5 supply areas; the largest, VODOVOD BRESTOVICA, supplies 24,000 users. The address search shows the nearest sampling points, not necessarily your water system; the system that supplies you is named on your water bill.

Supply areas at a glance
AreaUsersRating
VODOVOD BRESTOVICA24,000occasional non-compliance
Povezava Ilirska Bistrica220occasional non-compliance
SLIVJE108Faecal bacteria in 1 sample
BREZOVICA86repeated non-compliance
HOTIČNA60occasional non-compliance
VODOVOD BRESTOVICA: occasional non-compliancePovezava Ilirska Bistrica: occasional non-complianceSLIVJE: occasional non-complianceBREZOVICA: repeated non-complianceHOTIČNA: occasional non-complianceSlivjeBrezovicaHrpeljeMaterijaBač pri MaterijiBekaGolacGradišče pri MaterijiIlirska BistricaDivačaKoperPivkaSežana5 km
  • occasional non-compliance
  • repeated non-compliance

Sampling points of the state monitoring in recent years, coloured by the result for the area. Click a dot for the area's figures. Place names © OpenStreetMap

VODOVOD BRESTOVICA

Occasional non-compliance

Operator: Kraški vodovod Sežana · 24,000 users · water system Brestovica

The area also extends into Divača, Komen, Sežana.

Samples 2024–2026
53, 5 non-compliant
Water source
Influenced by surface water
Treatment
Filters, regular disinfection, chlorine gas disinfection
Hardness (operator)
13 °dH, moderately hard source
Latest sample
10 Jun 2026
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 53 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 53 samples
Nitrate5.39 mg/Llimit 50 mg/L · 7 samples
Arsenic0.16 µg/Llimit 10 µg/L · 6 samples
Manganese1.2 µg/Llimit 50 µg/L · 6 samples
Iron40 µg/Llimit 200 µg/L · 6 samples
Non-compliant samples (5)
  • · marked non-compliant; the published data gives no reason
  • · marked non-compliant; the published data gives no reason
  • · marked non-compliant; the published data gives no reason
  • · marked non-compliant; the published data gives no reason
  • · marked non-compliant; the published data gives no reason

Povezava Ilirska Bistrica

Occasional non-compliance

Operator: Kraški vodovod Sežana · 220 users · water system Povezava Ilirska Bistrica

Samples 2024–2026
5, 1 non-compliant
Water source
Influenced by surface water
Treatment
Chlorine gas disinfection
Hardness (operator)
12 °dH, moderately hard source
Latest sample
27 Feb 2026
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 5 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 5 samples
Nitrate6.2 mg/Llimit 50 mg/L · 2 samples
Non-compliant samples (1)
  • · Coliform bacteria 4 per 100 mL limit 0 per 100 mL

SLIVJE

Faecal bacteria in 1 sample

Operator: OBČINA HRPELJE - KOZINA · 108 users · water system Slivje

Samples 2024–2026
6, 3 non-compliant
Water source
Influenced by surface water
Treatment
Filters, sodium hypochlorite disinfection
Hardness (estimate)
≈9.7 °dH, moderately hard
Latest sample
6 Aug 2026
Measured values
E. coli>100 per 100 mLlimit 0 per 100 mL · 6 samples · 1× over the limit
Enterococci>100 per 100 mLlimit 0 per 100 mL · 6 samples · 1× over the limit
Nitrate3.4 mg/Llimit 50 mg/L · 1 sample
Lead0.34 µg/Llimit 10 µg/L · 3 samples
Non-compliant samples (3)
  • · E. coli >100 per 100 mL limit 0 per 100 mL, Enterococci >100 per 100 mL limit 0 per 100 mL, Coliform bacteria >100 per 100 mL limit 0 per 100 mL, Clostridium perfringens 51 per 100 mL limit 0 per 100 mL
  • · Coliform bacteria 4 per 100 mL limit 0 per 100 mL, Clostridium perfringens 1 per 100 mL limit 0 per 100 mL
  • · Coliform bacteria 3 per 100 mL limit 0 per 100 mL

BREZOVICA

Repeated or health-relevant non-compliance

Operator: OBČINA HRPELJE - KOZINA · 86 users · water system Brezovica

Samples 2024–2026
6, 6 non-compliant
Water source
Influenced by surface water
Treatment
No treatment
Hardness (estimate)
≈5.6 °dH, soft
Latest sample
6 Aug 2026
Measured values
E. coli>100 per 100 mLlimit 0 per 100 mL · 6 samples · 4× over the limit
Enterococci>100 per 100 mLlimit 0 per 100 mL · 6 samples · 5× over the limit
Nitratebelow 1.8 mg/Llimit 50 mg/L · 1 sample
Lead0.56 µg/Llimit 10 µg/L · 3 samples
Non-compliant samples (6)
  • · E. coli >80 per 100 mL limit 0 per 100 mL, Enterococci >80 per 100 mL limit 0 per 100 mL, Coliform bacteria >80 per 100 mL limit 0 per 100 mL
  • · Coliform bacteria 17 per 100 mL limit 0 per 100 mL
  • · E. coli >100 per 100 mL limit 0 per 100 mL, Enterococci >100 per 100 mL limit 0 per 100 mL, Coliform bacteria >100 per 100 mL limit 0 per 100 mL, Clostridium perfringens 5 per 100 mL limit 0 per 100 mL
  • · E. coli 11 per 100 mL limit 0 per 100 mL, Enterococci 1 per 100 mL limit 0 per 100 mL, Coliform bacteria 26 per 100 mL limit 0 per 100 mL
  • · E. coli 18 per 100 mL limit 0 per 100 mL, Enterococci 15 per 100 mL limit 0 per 100 mL, Coliform bacteria 84 per 100 mL limit 0 per 100 mL
  • · Enterococci 1 per 100 mL limit 0 per 100 mL, Coliform bacteria 2 per 100 mL limit 0 per 100 mL

HOTIČNA

Occasional non-compliance

Operator: Kraški vodovod Sežana · 60 users · water system Hotična

Samples 2024–2026
5, 1 non-compliant
Water source
Influenced by surface water
Treatment
No treatment
Hardness (operator)
11 °dH, moderately hard source
Latest sample
10 Jun 2026
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 5 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 5 samples
Nitrate2.9 mg/Llimit 50 mg/L · 1 sample
Non-compliant samples (1)
  • · marked non-compliant; the published data gives no reason

Measured values 2024–2026

The highest measured value of each parameter in the samples from the water systems that supply the municipality, and the share of the limit it reaches.

ParameterHighest valueAgainst the limit
E. coli>100 per 100 mLlimit 0 per 100 mL · 75 samples · 5× over the limit
Enterococci>100 per 100 mLlimit 0 per 100 mL · 75 samples · 6× over the limit
Coliform bacteria>100 per 100 mLlimit 0 per 100 mL · 75 samples · 10× over the limit
Clostridium perfringens51 per 100 mLlimit 0 per 100 mL · 75 samples · 3× over the limit
Nitrate6.2 mg/Llimit 50 mg/L · 12 samples
Nitrite0.0076 mg/Llimit 0.5 mg/L · 12 samples
Nitrate/50 + nitrite/30.12limit 1 · 12 samples
Lead0.56 µg/Llimit 10 µg/L · 6 samples
Arsenic0.16 µg/Llimit 10 µg/L · 6 samples
Uranium0.51 µg/Llimit 30 µg/L · 3 samples
Copper0.022 mg/Llimit 2 mg/L · 6 samples
Nickel0.23 µg/Llimit 20 µg/L · 3 samples
Cadmiumbelow 0.02 µg/Llimit 5 µg/L · 6 samples
Chromiumbelow 0.4 µg/Llimit 50 µg/L · 6 samples
Antimony0.087 µg/Llimit 10 µg/L · 6 samples
Selenium0.16 µg/Llimit 20 µg/L · 6 samples
Boron0.02 mg/Llimit 1.5 mg/L · 6 samples
Fluoridebelow 0.15 mg/Llimit 1.5 mg/L · 12 samples
Trihalomethanes, total23 µg/Llimit 100 µg/L · 6 samples
Chlorate0.084 mg/Llimit 0.25 mg/L · 1 sample
Chloritebelow 0.05 mg/Llimit 0.25 mg/L · 1 sample
Free chlorine0.25 mg/Lno limit value · 41 samples
Manganese1.2 µg/Llimit 50 µg/L · 6 samples
Iron40 µg/Llimit 200 µg/L · 6 samples
Aluminium4.5 µg/Llimit 200 µg/L · 6 samples
Ammoniumbelow 0.026 mg/Llimit 0.5 mg/L · 12 samples
Chloride56.1 mg/Llimit 250 mg/L · 12 samples
Sulphate13.5 mg/Llimit 250 mg/L · 12 samples
Sodium31 mg/Llimit 200 mg/L · 6 samples
pH7–8.1limit 6.5–9.5 · 75 samples
Electrical conductivity624 µS/cmlimit 2,500 µS/cm · 75 samples

Non-compliant samples

What the laboratory found in the samples that were not compliant:

Samples by year

019382016: 33 samples, 3 non-compliant’162017: 33 samples, 2 non-compliant’172018: 38 samples, 2 non-compliant’182019: 38 samples, 4 non-compliant’192020: 35 samples, 2 non-compliant’202021: 30 samples, 2 non-compliant’212022: 30 samples, 6 non-compliant’222023: 30 samples, 4 non-compliant’232024: 30 samples, 7 non-compliant’242025: 30 samples, 7 non-compliant’252026: 15 samples, 2 non-compliant’26
compliant non-compliant · Drinking-water samples in Hrpelje - Kozina since 2016

What you can do

How to read the results

The ratings are a Draga Slovenija summary, not an official NIJZ rating.

More about water and property in Hrpelje - Kozina

Estimate a property’s valueProperty prices in Hrpelje - Kozina

Drinking water in neighbouring municipalities in the Obalno-kraška region: Koper, Izola, Piran, Ankaran, Divača, Komen, Sežana.

Explanations of the parameters:

Follow the results for your address

When the state monitoring publishes a non-compliant result for the area by your address, we e-mail you (results come out about once a month). One address is free. This is not an urgent boil-water alert; the operator announces those.

Find your address and turn on following →

Monthly e-mail roundup: drinking water and the property market

Once a month: new drinking-water results and how the property market moved, in one e-mail. This is our existing monthly newsletter; we do not send a report for a single municipality. Unsubscribe with one click in every e-mail.

Email address only. Privacy statement.

Source: NIJZ and NLZOH, mpv.si; latest sample 31 Aug 2026. Processing: Draga Slovenija.

Frequently asked questions

Is the water in Hrpelje - Kozina safe to drink?

These are past results, not a verdict on the water today; the operator announces current restrictions (boil-water notices). In 2024–2026 the state monitoring took 75 samples of drinking water on the 5 supply areas serving the municipality, of which 16 were not compliant (E. coli or enterococci bacteria in 6 samples). Details by water system are above.

How hard is the water in Hrpelje - Kozina?

By the operators’ figures and, where there are none, our estimate 12.9 °dH (averaged over the water systems, weighted by users), which is moderately hard water. To set appliances, use your own system’s figure.

Who operates the water supply in Hrpelje - Kozina?

KRAŠKI VODOVOD SEŽANA D.O.O., OBČINA HRPELJE - KOZINA. The largest supply area is VODOVOD BRESTOVICA.

Where are the official drinking-water test results?

The state monitoring publishes its results at mpv.si, and the operator publishes an annual report on internal control on its website. This page summarises the state monitoring since 2016.

AI chat

Ask the data, in plain language

The AI chat finds the answer in the official register and shows it with a table you can download and a link into the map. Free; it only needs an account.

For example: Which municipalities issued the most building permits last year?