Draga SlovenijaDraga Slovenija

Drinking water in Dravograd

Occasional non-compliance

In 2024–2026 the state monitoring took 48 samples of drinking water on the 9 supply areas serving the municipality, of which 3 were not compliant (E. coli or enterococci bacteria in 1 sample). The water is estimated to be soft (≈6 °dH).

These are state monitoring results from 2024–2026, not a notice about the water today. Current notices (boil-water, do-not-use) are published by the water-system operator on its website.

Samples 2024–2026489 supply areas
Non-compliant36.3%
Hardness (estimate)6 °dHsoft
Nitrate, median3.1 mg/Llimit 50 mg/L

Water systems in Dravograd

In 2024–2026 the state monitoring sampled 9 supply areas; the largest, DRAVOGRAD - ČRNEČE, supplies 4,770 users. The address search shows the nearest sampling points, not necessarily your water system; the system that supplies you is named on your water bill.

Supply areas at a glance
AreaUsersRating
DRAVOGRAD - ČRNEČE4,770occasional non-compliance
Gorče - Libeliče177compliant
SP. GORČE - TRIBEJ140compliant
LIBELIČE112compliant
Sv. Jedrt80compliant
DRAVČE, SV. DANIJEL57compliant
CŠOD Ajda50compliant
TURISTIČNA KMETIJA JEGLIJENK25Faecal bacteria in 1 sample
DVOREC BUKOVJE1occasional non-compliance
DRAVOGRAD - ČRNEČE: occasional non-complianceDRAVOGRAD - ČRNEČE: occasional non-complianceDRAVOGRAD - ČRNEČE: occasional non-complianceDRAVOGRAD - ČRNEČE: occasional non-complianceDRAVOGRAD - ČRNEČE: occasional non-complianceDRAVOGRAD - ČRNEČE: occasional non-complianceDRAVOGRAD - ČRNEČE: occasional non-complianceTRBONJE: no dataGorče - Libeliče: compliantŠENTJANŽ - NOVO NASELJE: no dataSP. GORČE - TRIBEJ: compliantŠENTJANŽ: no dataLIBELIČE: compliantBUKOVSKA VAS: no dataSv. Jedrt: compliantŠentjanž - jug: no dataDRAVČE, SV. DANIJEL: compliantCŠOD Ajda: compliantDravogradČrnečeTrbonjeŠentjanžLibeličeBukovska vasOtiški VrhTribejVuzenicaMutaPrevalje5 km
  • compliant
  • occasional non-compliance

Sampling points of the state monitoring in recent years, coloured by the result for the area. Click a dot for the area's figures. Place names © OpenStreetMap

DRAVOGRAD - ČRNEČE

Occasional non-compliance

Operator: JKP Dravograd · 4,770 users · water system Dravograd - Črneče

Samples 2024–2026
25, 1 non-compliant
Water source
Influenced by surface water
Treatment
Regular disinfection, chlorine gas disinfection
Hardness (estimate)
≈6 °dH, soft
Latest sample
7 May 2026
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 25 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 25 samples
Nitrate3.1 mg/Llimit 50 mg/L · 2 samples
PFAS, totalbelow 0.03 µg/Llimit 0.5 µg/L · 1 sample
Lead0.19 µg/Llimit 10 µg/L · 8 samples
Arsenicbelow 1 µg/Llimit 10 µg/L · 2 samples
Manganesebelow 1 µg/Llimit 50 µg/L · 2 samples
Iron12 µg/Llimit 200 µg/L · 2 samples
Non-compliant samples (1)
  • · Coliform bacteria 21 per 100 mL limit 0 per 100 mL

Gorče - Libeliče

All samples compliant

Operator: JKP Dravograd · 177 users · water system Gorče - Libeliče

Samples 2024–2026
5, all compliant
Water source
Influenced by surface water
Hardness (estimate)
≈4.4 °dH, soft
Latest sample
13 May 2026
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 5 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 5 samples
Leadbelow 1 µg/Llimit 10 µg/L · 3 samples

SP. GORČE - TRIBEJ

All samples compliant

Operator: JKP Radlje · 140 users · water system Sp. Gorče -Tribej

Samples 2024–2026
1, all compliant
Water source
Groundwater, not influenced by surface water
Treatment
No treatment
Hardness (estimate)
≈11.8 °dH, moderately hard
Latest sample
17 Oct 2024
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 1 sample
Enterococci0 per 100 mLlimit 0 per 100 mL · 1 sample
Leadbelow 1 µg/Llimit 10 µg/L · 1 sample

LIBELIČE

All samples compliant

Operator: JKP Dravograd · 112 users · water system Libeliče

Samples 2024–2026
5, all compliant
Water source
Influenced by surface water
Treatment
Sodium hypochlorite disinfection
Hardness (estimate)
≈6.1 °dH, soft
Latest sample
13 May 2026
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 5 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 5 samples
Leadbelow 1 µg/Llimit 10 µg/L · 3 samples

Sv. Jedrt

All samples compliant

Operator: Jedert - nova vas · 80 users · water system Sveti Jedrt

Samples 2024–2026
4, all compliant
Water source
Groundwater, not influenced by surface water
Treatment
No treatment
Hardness (estimate)
≈5.4 °dH, soft
Latest sample
13 Nov 2025
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 4 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 4 samples
Lead0.2 µg/Llimit 10 µg/L · 2 samples

DRAVČE, SV. DANIJEL

All samples compliant

Operator: OBČINA VUZENICA · 57 users · water system VS Dravče-Sv.Danijel

Samples 2024–2026
1, all compliant
Water source
Influenced by surface water
Treatment
Sodium hypochlorite disinfection
Hardness (estimate)
≈4.1 °dH, soft
Latest sample
15 Jul 2024
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 1 sample
Enterococci0 per 100 mLlimit 0 per 100 mL · 1 sample
Leadbelow 1 µg/Llimit 10 µg/L · 1 sample

CŠOD Ajda

All samples compliant

Operator: CSOD · 50 users · water system CŠOD Ajda

Samples 2024–2026
5, all compliant
Water source
Groundwater, not influenced by surface water
Treatment
Filters, chlorine gas disinfection, UV disinfection
Hardness (estimate)
≈2 °dH, soft
Latest sample
13 May 2026
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 5 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 5 samples
Nitrate4 mg/Llimit 50 mg/L · 1 sample
Lead1.6 µg/Llimit 10 µg/L · 3 samples

TURISTIČNA KMETIJA JEGLIJENK

Faecal bacteria in 1 sample

Operator: TK JEGLIJENK · 25 users · water system Tuuristična Kmetija Jeglijenk

Samples 2024–2026
1, 1 non-compliant
Water source
Groundwater, not influenced by surface water
Hardness (estimate)
≈3.9 °dH, soft
Latest sample
2 Jul 2025
Measured values
E. coli12 per 100 mLlimit 0 per 100 mL · 1 sample · 1× over the limit
Enterococci1 per 100 mLlimit 0 per 100 mL · 1 sample · 1× over the limit
Non-compliant samples (1)
  • · E. coli 12 per 100 mL limit 0 per 100 mL, Enterococci 1 per 100 mL limit 0 per 100 mL, Coliform bacteria 24 per 100 mL limit 0 per 100 mL

DVOREC BUKOVJE

Occasional non-compliance

Operator: JAVNI ZAVOD DRAVIT DRAVOGRAD · 1 user · water system Dvorec Bukovje

Samples 2024–2026
1, 1 non-compliant
Water source
Groundwater, not influenced by surface water
Hardness (estimate)
≈7.9 °dH, soft
Latest sample
4 Jul 2025
Measured values
E. coli0 per 100 mLlimit 0 per 100 mL · 1 sample
Enterococci0 per 100 mLlimit 0 per 100 mL · 1 sample
Non-compliant samples (1)
  • · Coliform bacteria 10 per 100 mL limit 0 per 100 mL

Areas with results only before 2024 (often the same water system under an older code): ČRNEČE, TRBONJE, ŠENTJANŽ - NOVO NASELJE, ŠENTJANŽ, BUKOVSKA VAS, OTIŠKI VRH - BAUH, Šentjanž - jug.

Measured values 2024–2026

The highest measured value of each parameter in the samples from the water systems that supply the municipality, and the share of the limit it reaches.

ParameterHighest valueAgainst the limit
E. coli12 per 100 mLlimit 0 per 100 mL · 48 samples · 1× over the limit
Enterococci1 per 100 mLlimit 0 per 100 mL · 48 samples · 1× over the limit
Coliform bacteria24 per 100 mLlimit 0 per 100 mL · 48 samples · 3× over the limit
Clostridium perfringens0 per 100 mLlimit 0 per 100 mL · 20 samples
Nitrate4 mg/Llimit 50 mg/L · 3 samples
Nitritebelow 0.007 mg/Llimit 0.5 mg/L · 3 samples
Nitrate/50 + nitrite/30.08limit 1 · 3 samples
PFAS, totalbelow 0.03 µg/Llimit 0.5 µg/L · 1 sample
PFOAbelow 0.0005 µg/Lpart of the 20-PFAS sum, limit 0.1 µg/L · 1 sample
PFOSbelow 0.0005 µg/Lpart of the 20-PFAS sum, limit 0.1 µg/L · 1 sample
Lead1.6 µg/Llimit 10 µg/L · 21 samples
Arsenicbelow 1 µg/Llimit 10 µg/L · 2 samples
Uranium0.17 µg/Llimit 30 µg/L · 1 sample
Copper0.0013 mg/Llimit 2 mg/L · 2 samples
Nickelbelow 1 µg/Llimit 20 µg/L · 1 sample
Cadmiumbelow 0.1 µg/Llimit 5 µg/L · 2 samples
Chromiumbelow 1 µg/Llimit 50 µg/L · 2 samples
Antimonybelow 1 µg/Llimit 10 µg/L · 2 samples
Seleniumbelow 1 µg/Llimit 20 µg/L · 2 samples
Boronbelow 0.01 mg/Llimit 1.5 mg/L · 2 samples
Fluoridebelow 0.1 mg/Llimit 1.5 mg/L · 3 samples
Trihalomethanes, total11 µg/Llimit 100 µg/L · 3 samples
Haloacetic acidsbelow 5 µg/Llimit 60 µg/L · 1 sample
Chloratebelow 0.01 mg/Llimit 0.25 mg/L · 3 samples
Chloritebelow 0.01 mg/Llimit 0.25 mg/L · 3 samples
Free chlorine0.25 mg/Lno limit value · 14 samples
Manganesebelow 1 µg/Llimit 50 µg/L · 2 samples
Iron12 µg/Llimit 200 µg/L · 2 samples
Aluminiumbelow 10 µg/Llimit 200 µg/L · 2 samples
Ammoniumbelow 0.013 mg/Llimit 0.5 mg/L · 3 samples
Chloride1 mg/Llimit 250 mg/L · 3 samples
Sulphate10 mg/Llimit 250 mg/L · 3 samples
Sodium2.5 mg/Llimit 200 mg/L · 2 samples
pH7.1–8.5limit 6.5–9.5 · 48 samples
Electrical conductivity733 µS/cmlimit 2,500 µS/cm · 48 samples

Non-compliant samples

What the laboratory found in the samples that were not compliant:

Samples by year

016312016: 29 samples, 9 non-compliant’162017: 27 samples, 7 non-compliant’172018: 28 samples, 10 non-compliant’182019: 31 samples, 10 non-compliant’192020: 30 samples, 7 non-compliant’202021: 26 samples, 6 non-compliant’212022: 18 samples, 4 non-compliant’222023: 23 samples, 1 non-compliant’232024: 22 samples, all compliant’242025: 22 samples, 3 non-compliant’252026: 4 samples, all compliant’26
compliant non-compliant · Drinking-water samples in Dravograd since 2016

What you can do

How to read the results

The ratings are a Draga Slovenija summary, not an official NIJZ rating.

More about water and property in Dravograd

Estimate a property’s valueProperty prices in Dravograd

Drinking water in neighbouring municipalities in the Koroška region: Mežica, Prevalje, Ravne na Koroškem, Muta, Ribnica na Pohorju, Črna na Koroškem, Radlje ob Dravi, Podvelka, Slovenj Gradec, Mislinja, Vuzenica.

Explanations of the parameters:

Follow the results for your address

When the state monitoring publishes a non-compliant result for the area by your address, we e-mail you (results come out about once a month). One address is free. This is not an urgent boil-water alert; the operator announces those.

Find your address and turn on following →

Monthly e-mail roundup: drinking water and the property market

Once a month: new drinking-water results and how the property market moved, in one e-mail. This is our existing monthly newsletter; we do not send a report for a single municipality. Unsubscribe with one click in every e-mail.

Email address only. Privacy statement.

Source: NIJZ and NLZOH, mpv.si; latest sample 31 Aug 2026. Processing: Draga Slovenija.

Frequently asked questions

Is the water in Dravograd safe to drink?

These are past results, not a verdict on the water today; the operator announces current restrictions (boil-water notices). In 2024–2026 the state monitoring took 48 samples of drinking water on the 9 supply areas serving the municipality, of which 3 were not compliant (E. coli or enterococci bacteria in 1 sample). Details by water system are above.

How hard is the water in Dravograd?

Estimated from electrical conductivity at 6 °dH, which is soft water. The operator publishes the exact value for its network.

Who operates the water supply in Dravograd?

JKP Dravograd, JKP RADLJE, Jedert - nova vas, OBČINA VUZENICA, CSOD. The largest supply area is DRAVOGRAD - ČRNEČE.

Where are the official drinking-water test results?

The state monitoring publishes its results at mpv.si, and the operator publishes an annual report on internal control on its website. This page summarises the state monitoring since 2016.

AI chat

Ask the data, in plain language

The AI chat finds the answer in the official register and shows it with a table you can download and a link into the map. Free; it only needs an account.

For example: Which municipalities issued the most building permits last year?

Open the AI chat

AI chat