Draga SlovenijaDraga Slovenija

Drinking water: VS Slovenj Gradec - Suhi Dol water system

Occasional non-compliance

The VS Slovenj Gradec - Suhi Dol water system (operator JKP SLOVENJ GRADEC) supplies 10,500 users in the municipality of Slovenj Gradec. In 2024–2026 the state monitoring took 45 samples, of which 1 was not compliant.

These are state monitoring results from 2024–2026, not a notice about the water today. Current notices (boil-water, do-not-use) are published by the water-system operator on its website.

Samples 2024–2026453 supply areas
Non-compliant12.2%
Hardness (operator)12.1 °dHmoderately hard
Users10,500JKP SLOVENJ GRADEC

Supply areas

SLOVENJ GRADEC

All samples compliant

Operator: JKP Slovenj Gradec · 7,500 users · water system VS Slovenj Gradec - Suhi Dol

Samples 2024–2026
25, all compliant
Water source
Groundwater, not influenced by surface water
Treatment
Regular disinfection, chlorine gas disinfection
Hardness (operator)
12.1 °dH, moderately hard source
Latest sample
11 Aug 2026
E. coli0 per 100 mLlimit 0 per 100 mL · 25 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 25 samples
Nitrate3.3 mg/Llimit 50 mg/L · 4 samples
Arsenicbelow 1 µg/Llimit 10 µg/L · 4 samples
Manganese1 µg/Llimit 50 µg/L · 4 samples
Iron27 µg/Llimit 200 µg/L · 4 samples

ŠMARTNO

Occasional non-compliance

Operator: JKP Slovenj Gradec · 2,000 users · water system VS Slovenj Gradec - Suhi Dol

Samples 2024–2026
10, 1 non-compliant
Water source
Groundwater, not influenced by surface water
Treatment
Regular disinfection, chlorine gas disinfection
Hardness (operator)
12.1 °dH, moderately hard source
Latest sample
20 Apr 2026
E. coli0 per 100 mLlimit 0 per 100 mL · 10 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 10 samples
Nitrate3.1 mg/Llimit 50 mg/L · 2 samples
Arsenicbelow 1 µg/Llimit 10 µg/L · 2 samples
Manganesebelow 1 µg/Llimit 50 µg/L · 2 samples
Ironbelow 10 µg/Llimit 200 µg/L · 2 samples
Non-compliant samples (1)
  • · marked non-compliant; the published data gives no reason

PODGORJE - SG

All samples compliant

Operator: JKP Slovenj Gradec · 1,000 users · water system VS Slovenj Gradec - Suhi Dol

Samples 2024–2026
10, all compliant
Water source
Groundwater, not influenced by surface water
Treatment
Regular disinfection, chlorine gas disinfection
Hardness (operator)
12.1 °dH, moderately hard source
Latest sample
9 Apr 2026
E. coli0 per 100 mLlimit 0 per 100 mL · 10 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 10 samples
Nitrate3.2 mg/Llimit 50 mg/L · 2 samples
Arsenicbelow 1 µg/Llimit 10 µg/L · 2 samples
Manganesebelow 1 µg/Llimit 50 µg/L · 2 samples
Ironbelow 10 µg/Llimit 200 µg/L · 2 samples

Measured values 2024–2026

ParameterHighest valueAgainst the limit
E. coli0 per 100 mLlimit 0 per 100 mL · 45 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 45 samples
Coliform bacteria0 per 100 mLlimit 0 per 100 mL · 45 samples
Nitrate3.3 mg/Llimit 50 mg/L · 8 samples
Nitritebelow 0.007 mg/Llimit 0.5 mg/L · 8 samples
Nitrate/50 + nitrite/30.07limit 1 · 8 samples
Arsenicbelow 1 µg/Llimit 10 µg/L · 8 samples
Uranium2.4 µg/Llimit 30 µg/L · 4 samples
Copper0.015 mg/Llimit 2 mg/L · 8 samples
Nickel1.4 µg/Llimit 20 µg/L · 4 samples
Cadmium0.028 µg/Llimit 5 µg/L · 8 samples
Chromiumbelow 1 µg/Llimit 50 µg/L · 8 samples
Antimonybelow 1 µg/Llimit 10 µg/L · 8 samples
Selenium1 µg/Llimit 20 µg/L · 8 samples
Boronbelow 0.01 mg/Llimit 1.5 mg/L · 8 samples
Fluoridebelow 0.1 mg/Llimit 1.5 mg/L · 8 samples
Trihalomethanes, total11 µg/Llimit 100 µg/L · 8 samples
Free chlorine0.21 mg/Lno limit value · 30 samples
Manganese1 µg/Llimit 50 µg/L · 8 samples
Iron27 µg/Llimit 200 µg/L · 8 samples
Aluminiumbelow 10 µg/Llimit 200 µg/L · 8 samples
Ammoniumbelow 0.013 mg/Llimit 0.5 mg/L · 8 samples
Chloride1.5 mg/Llimit 250 mg/L · 8 samples
Sulphate14 mg/Llimit 250 mg/L · 8 samples
Sodium1.1 mg/Llimit 200 mg/L · 8 samples
pH7.3–7.9limit 6.5–9.5 · 45 samples
Electrical conductivity457 µS/cmlimit 2,500 µS/cm · 45 samples

Non-compliant samples

Samples by year

011222016: 22 samples, 1 non-compliant’162017: 22 samples, all compliant’172018: 22 samples, 1 non-compliant’182019: 22 samples, all compliant’192020: 18 samples, all compliant’202021: 18 samples, all compliant’212022: 18 samples, all compliant’222023: 18 samples, all compliant’232024: 18 samples, all compliant’242025: 18 samples, 1 non-compliant’252026: 9 samples, all compliant’26
compliant non-compliant · Samples from the VS Slovenj Gradec - Suhi Dol water system

Municipalities

Drinking water in Slovenj Gradec

What you can do

How to read the results

The ratings are a Draga Slovenija summary, not an official NIJZ rating.

Follow the results for your address

When the state monitoring publishes a non-compliant result for the area by your address, we e-mail you (results come out about once a month). One address is free. This is not an urgent boil-water alert; the operator announces those.

Find your address and turn on following →

Source: NIJZ and NLZOH, mpv.si; latest sample 31 Aug 2026. Processing: Draga Slovenija.

Frequently asked questions

Is the water from the VS Slovenj Gradec - Suhi Dol water system safe to drink?

The VS Slovenj Gradec - Suhi Dol water system (operator JKP SLOVENJ GRADEC) supplies 10,500 users in the municipality of Slovenj Gradec. In 2024–2026 the state monitoring took 45 samples, of which 1 was not compliant. The operator announces current restrictions on use.

How hard is the water from the VS Slovenj Gradec - Suhi Dol water system?

According to the operator 12.1 °dH, which is moderately hard water.

AI chat

Ask the data, in plain language

The AI chat finds the answer in the official register and shows it with a table you can download and a link into the map. Free; it only needs an account.

For example: Which municipalities issued the most building permits last year?