Draga SlovenijaDraga Slovenija

Drinking water: Somešca water system

Faecal bacteria in 1 sample

The Somešca water system (operator Somešca) supplies 570 users in the municipality of Kamnik. In 2024–2026 the state monitoring took 11 samples, of which 4 were not compliant.

These are state monitoring results from 2024–2026, not a notice about the water today. Current notices (boil-water, do-not-use) are published by the water-system operator on its website.

Samples 2024–2026111 supply area
Non-compliant436%
Hardness (estimate)10.5 °dHmoderately hard
Users570Somešca

Supply areas

SOMEŠCA

Faecal bacteria in 1 sample

Operator: Somešca · 570 users · water system Somešca

Samples 2024–2026
11, 4 non-compliant
Water source
Undetermined
Hardness (estimate)
≈10.5 °dH, moderately hard
Latest sample
21 Aug 2026
E. coli1 per 100 mLlimit 0 per 100 mL · 11 samples · 1× over the limit
Enterococci0 per 100 mLlimit 0 per 100 mL · 11 samples
Nitrate3.5 mg/Llimit 50 mg/L · 2 samples
Lead1 µg/Llimit 10 µg/L · 2 samples
Arsenicbelow 1 µg/Llimit 10 µg/L · 2 samples
Manganesebelow 10 µg/Llimit 50 µg/L · 2 samples
Ironbelow 10 µg/Llimit 200 µg/L · 2 samples
Non-compliant samples (4)
  • · Coliform bacteria 9 per 100 mL limit 0 per 100 mL
  • · Coliform bacteria 7 per 100 mL limit 0 per 100 mL
  • · E. coli 1 per 100 mL limit 0 per 100 mL, Coliform bacteria 1 per 100 mL limit 0 per 100 mL
  • · Coliform bacteria 3 per 100 mL limit 0 per 100 mL

Measured values 2024–2026

ParameterHighest valueAgainst the limit
E. coli1 per 100 mLlimit 0 per 100 mL · 11 samples · 1× over the limit
Enterococci0 per 100 mLlimit 0 per 100 mL · 11 samples
Coliform bacteria9 per 100 mLlimit 0 per 100 mL · 11 samples · 4× over the limit
Clostridium perfringens0 per 100 mLlimit 0 per 100 mL · 11 samples
Nitrate3.5 mg/Llimit 50 mg/L · 2 samples
Nitritebelow 0.01 mg/Llimit 0.5 mg/L · 2 samples
Nitrate/50 + nitrite/30.07limit 1 · 2 samples
Lead1 µg/Llimit 10 µg/L · 2 samples
Arsenicbelow 1 µg/Llimit 10 µg/L · 2 samples
Uraniumbelow 10 µg/Llimit 30 µg/L · 1 sample
Copperbelow 0.01 mg/Llimit 2 mg/L · 2 samples
Nickelbelow 10 µg/Llimit 20 µg/L · 1 sample
Cadmiumbelow 1 µg/Llimit 5 µg/L · 2 samples
Chromiumbelow 10 µg/Llimit 50 µg/L · 2 samples
Antimonybelow 1 µg/Llimit 10 µg/L · 2 samples
Seleniumbelow 1 µg/Llimit 20 µg/L · 2 samples
Boronbelow 0.01 mg/Llimit 1.5 mg/L · 2 samples
Fluoridebelow 1 mg/Llimit 1.5 mg/L · 2 samples
Manganesebelow 10 µg/Llimit 50 µg/L · 2 samples
Ironbelow 10 µg/Llimit 200 µg/L · 2 samples
Aluminiumbelow 10 µg/Llimit 200 µg/L · 2 samples
Ammoniumbelow 0.02 mg/Llimit 0.5 mg/L · 2 samples
Chloride1.8 mg/Llimit 250 mg/L · 2 samples
Sulphate7.9 mg/Llimit 250 mg/L · 2 samples
Sodium1.1 mg/Llimit 200 mg/L · 2 samples
pH7.2–7.5limit 6.5–9.5 · 11 samples
Electrical conductivity319 µS/cmlimit 2,500 µS/cm · 11 samples

Non-compliant samples

Samples by year

0242020: 4 samples, all compliant’202021: 4 samples, all compliant’212022: 4 samples, all compliant’222023: 4 samples, all compliant’232024: 4 samples, 1 non-compliant’242025: 4 samples, 1 non-compliant’252026: 3 samples, 2 non-compliant’26
compliant non-compliant · Samples from the Somešca water system

Municipalities

Drinking water in Kamnik

What you can do

How to read the results

The ratings are a Draga Slovenija summary, not an official NIJZ rating.

Follow the results for your address

When the state monitoring publishes a non-compliant result for the area by your address, we e-mail you (results come out about once a month). One address is free. This is not an urgent boil-water alert; the operator announces those.

Find your address and turn on following →

Source: NIJZ and NLZOH, mpv.si; latest sample 31 Aug 2026. Processing: Draga Slovenija.

Frequently asked questions

Is the water from the Somešca water system safe to drink?

The Somešca water system (operator Somešca) supplies 570 users in the municipality of Kamnik. In 2024–2026 the state monitoring took 11 samples, of which 4 were not compliant. The operator announces current restrictions on use.

How hard is the water from the Somešca water system?

Estimated from electrical conductivity at 10.5 °dH, which is moderately hard water.

AI chat

Ask the data, in plain language

The AI chat finds the answer in the official register and shows it with a table you can download and a link into the map. Free; it only needs an account.

For example: Which municipalities issued the most building permits last year?

Open the AI chat

AI chat