Draga SlovenijaDraga Slovenija

Drinking water: Studenice - Poljčane water system

Faecal bacteria in 1 sample

The Studenice - Poljčane water system (operator OKP Rogaška Slatina) supplies 1,057 users in the municipality of Poljčane. In 2024–2026 the state monitoring took 9 samples, of which 1 was not compliant.

These are state monitoring results from 2024–2026, not a notice about the water today. Current notices (boil-water, do-not-use) are published by the water-system operator on its website.

Samples 2024–202691 supply area
Non-compliant111%
Hardness (estimate)12.4 °dHmoderately hard
Users1,057OKP Rogaška Slatina

Supply areas

STUDENICE - POLJČANE

Faecal bacteria in 1 sample

Operator: OKP Rogaška Slatina · 1,057 users · water system Studenice - Poljčane

Samples 2024–2026
9, 1 non-compliant
Water source
Influenced by surface water
Treatment
Regular disinfection, chlorine gas disinfection
Hardness (estimate)
≈12.4 °dH, moderately hard
Latest sample
11 Jun 2026
E. coli0 per 100 mLlimit 0 per 100 mL · 9 samples
Enterococci1 per 100 mLlimit 0 per 100 mL · 9 samples · 1× over the limit
Nitrate6.2 mg/Llimit 50 mg/L · 2 samples
Arsenicbelow 1 µg/Llimit 10 µg/L · 2 samples
Manganesebelow 1 µg/Llimit 50 µg/L · 2 samples
Iron33 µg/Llimit 200 µg/L · 2 samples
Non-compliant samples (1)
  • · Enterococci 1 per 100 mL limit 0 per 100 mL

Measured values 2024–2026

ParameterHighest valueAgainst the limit
E. coli0 per 100 mLlimit 0 per 100 mL · 9 samples
Enterococci1 per 100 mLlimit 0 per 100 mL · 9 samples · 1× over the limit
Coliform bacteria0 per 100 mLlimit 0 per 100 mL · 9 samples
Clostridium perfringens0 per 100 mLlimit 0 per 100 mL · 9 samples
Nitrate6.2 mg/Llimit 50 mg/L · 2 samples
Nitritebelow 0.007 mg/Llimit 0.5 mg/L · 2 samples
Nitrate/50 + nitrite/30.12limit 1 · 2 samples
Arsenicbelow 1 µg/Llimit 10 µg/L · 2 samples
Uranium0.41 µg/Llimit 30 µg/L · 1 sample
Copper0.014 mg/Llimit 2 mg/L · 2 samples
Nickelbelow 1 µg/Llimit 20 µg/L · 1 sample
Cadmiumbelow 0.1 µg/Llimit 5 µg/L · 2 samples
Chromiumbelow 1 µg/Llimit 50 µg/L · 2 samples
Antimonybelow 1 µg/Llimit 10 µg/L · 2 samples
Selenium1.1 µg/Llimit 20 µg/L · 2 samples
Boronbelow 0.01 mg/Llimit 1.5 mg/L · 2 samples
Fluoridebelow 0.1 mg/Llimit 1.5 mg/L · 2 samples
Trihalomethanes, total4.6 µg/Llimit 100 µg/L · 2 samples
Free chlorine0.21 mg/Lno limit value · 5 samples
Manganesebelow 1 µg/Llimit 50 µg/L · 2 samples
Iron33 µg/Llimit 200 µg/L · 2 samples
Aluminium46 µg/Llimit 200 µg/L · 2 samples
Ammoniumbelow 0.013 mg/Llimit 0.5 mg/L · 2 samples
Chloride1.9 mg/Llimit 250 mg/L · 2 samples
Sulphate18 mg/Llimit 250 mg/L · 2 samples
Sodium1.4 mg/Llimit 200 mg/L · 2 samples
pH7.3–7.7limit 6.5–9.5 · 9 samples
Electrical conductivity444 µS/cmlimit 2,500 µS/cm · 9 samples

Non-compliant samples

Samples by year

0352016: 5 samples, all compliant’162017: 5 samples, all compliant’172018: 5 samples, all compliant’182019: 5 samples, all compliant’192020: 4 samples, all compliant’202021: 4 samples, all compliant’212022: 4 samples, all compliant’222023: 4 samples, all compliant’232024: 3 samples, all compliant’242025: 4 samples, 1 non-compliant’252026: 2 samples, all compliant’26
compliant non-compliant · Samples from the Studenice - Poljčane water system

Municipalities

Drinking water in Poljčane

What you can do

How to read the results

The ratings are a Draga Slovenija summary, not an official NIJZ rating.

Follow the results for your address

When the state monitoring publishes a non-compliant result for the area by your address, we e-mail you (results come out about once a month). One address is free. This is not an urgent boil-water alert; the operator announces those.

Find your address and turn on following →

Source: NIJZ and NLZOH, mpv.si; latest sample 31 Aug 2026. Processing: Draga Slovenija.

Frequently asked questions

Is the water from the Studenice - Poljčane water system safe to drink?

The Studenice - Poljčane water system (operator OKP Rogaška Slatina) supplies 1,057 users in the municipality of Poljčane. In 2024–2026 the state monitoring took 9 samples, of which 1 was not compliant. The operator announces current restrictions on use.

How hard is the water from the Studenice - Poljčane water system?

Estimated from electrical conductivity at 12.4 °dH, which is moderately hard water.