Draga SlovenijaDraga Slovenija

Drinking water: Struge water system

Repeated or health-relevant non-compliance

The Struge water system (operator OBČINA LUČE) supplies 80 users in the municipality of Luče. In 2024–2026 the state monitoring took 5 samples, of which 2 were not compliant.

These are state monitoring results from 2024–2026, not a notice about the water today. Current notices (boil-water, do-not-use) are published by the water-system operator on its website.

Samples 2024–202651 supply area
Non-compliant240%
Hardness (estimate)3.2 °dHsoft
Users80OBČINA LUČE

Supply areas

STRUGE

Repeated or health-relevant non-compliance

Operator: OBČINA LUČE · 80 users · water system Struge

Samples 2024–2026
5, 2 non-compliant
Water source
Influenced by surface water
Treatment
Disinfection with Izosan chlorine tablets, occasional disinfection
Hardness (estimate)
≈3.2 °dH, soft
Latest sample
23 Mar 2026
E. coli>27 per 100 mLlimit 0 per 100 mL · 5 samples · 1× over the limit
Enterococci5 per 100 mLlimit 0 per 100 mL · 5 samples · 1× over the limit
Nitrate3 mg/Llimit 50 mg/L · 1 sample
Lead12 µg/Llimit 10 µg/L · 3 samples · 1× over the limit
Non-compliant samples (2)
  • · Lead 12 µg/L limit 10 µg/L
  • · E. coli >27 per 100 mL limit 0 per 100 mL, Enterococci 5 per 100 mL limit 0 per 100 mL, Coliform bacteria >80 per 100 mL limit 0 per 100 mL

Measured values 2024–2026

ParameterHighest valueAgainst the limit
E. coli>27 per 100 mLlimit 0 per 100 mL · 5 samples · 1× over the limit
Enterococci5 per 100 mLlimit 0 per 100 mL · 5 samples · 1× over the limit
Coliform bacteria>80 per 100 mLlimit 0 per 100 mL · 5 samples · 1× over the limit
Clostridium perfringens0 per 100 mLlimit 0 per 100 mL · 5 samples
Nitrate3 mg/Llimit 50 mg/L · 1 sample
Nitritebelow 0.007 mg/Llimit 0.5 mg/L · 1 sample
Nitrate/50 + nitrite/30.06limit 1 · 1 sample
Lead12 µg/Llimit 10 µg/L · 3 samples · 1× over the limit
Fluoridebelow 0.1 mg/Llimit 1.5 mg/L · 1 sample
Free chlorine0.09 mg/Lno limit value · 3 samples
Ammoniumbelow 0.013 mg/Llimit 0.5 mg/L · 1 sample
Chloride0.9 mg/Llimit 250 mg/L · 1 sample
Sulphate11 mg/Llimit 250 mg/L · 1 sample
pH7.4–7.6limit 6.5–9.5 · 5 samples
Electrical conductivity112 µS/cmlimit 2,500 µS/cm · 5 samples

Non-compliant samples

Samples by year

0122016: 2 samples, all compliant’162017: 2 samples, all compliant’172018: 2 samples, all compliant’182019: 2 samples, all compliant’192020: 2 samples, 1 non-compliant’202021: 2 samples, all compliant’212022: 2 samples, all compliant’222023: 2 samples, all compliant’232024: 2 samples, all compliant’242025: 2 samples, 1 non-compliant’252026: 1 sample, 1 non-compliant’26
compliant non-compliant · Samples from the Struge water system

Municipalities

Drinking water in Luče

What you can do

How to read the results

The ratings are a Draga Slovenija summary, not an official NIJZ rating.

Follow the results for your address

When the state monitoring publishes a non-compliant result for the area by your address, we e-mail you (results come out about once a month). One address is free. This is not an urgent boil-water alert; the operator announces those.

Find your address and turn on following →

Source: NIJZ and NLZOH, mpv.si; latest sample 31 Aug 2026. Processing: Draga Slovenija.

Frequently asked questions

Is the water from the Struge water system safe to drink?

The Struge water system (operator OBČINA LUČE) supplies 80 users in the municipality of Luče. In 2024–2026 the state monitoring took 5 samples, of which 2 were not compliant. The operator announces current restrictions on use.

How hard is the water from the Struge water system?

Estimated from electrical conductivity at 3.2 °dH, which is soft water.

AI chat

Ask the data, in plain language

The AI chat finds the answer in the official register and shows it with a table you can download and a link into the map. Free; it only needs an account.

For example: Which municipalities issued the most building permits last year?

Open the AI chat

AI chat