Draga SlovenijaDraga Slovenija

Drinking water: Stari Trg - Lož water system

All samples compliant

The Stari Trg - Lož water system (operator JP Komunala Cerknica d.o.o.) supplies 3,497 users in the municipality of Loška dolina. In 2024–2026 the state monitoring took 10 samples and all were compliant.

These are state monitoring results from 2024–2026, not a notice about the water today. Current notices (boil-water, do-not-use) are published by the water-system operator on its website.

Samples 2024–2026101 supply area
Non-compliant00%
Hardness (estimate)15.9 °dHhard
Users3,497JP Komunala Cerknica d.o.o.

Supply areas

STARI TRG - LOŽ

All samples compliant

Operator: Komunala Cerknica · 3,497 users · water system Stari Trg - Lož

Samples 2024–2026
10, all compliant
Water source
Influenced by surface water
Treatment
Ultrafiltration, sodium hypochlorite disinfection, chlorine dioxide disinfection, UV disinfection
Hardness (estimate)
≈15.9 °dH, hard
Latest sample
5 Jun 2026
E. coli0 per 100 mLlimit 0 per 100 mL · 10 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 10 samples
Nitrate4.4 mg/Llimit 50 mg/L · 2 samples
Arsenicbelow 1 µg/Llimit 10 µg/L · 2 samples
Manganesebelow 1 µg/Llimit 50 µg/L · 2 samples
Ironbelow 10 µg/Llimit 200 µg/L · 2 samples

Measured values 2024–2026

ParameterHighest valueAgainst the limit
E. coli0 per 100 mLlimit 0 per 100 mL · 10 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 10 samples
Coliform bacteria0 per 100 mLlimit 0 per 100 mL · 10 samples
Clostridium perfringens0 per 100 mLlimit 0 per 100 mL · 2 samples
Nitrate4.4 mg/Llimit 50 mg/L · 2 samples
Nitritebelow 0.007 mg/Llimit 0.5 mg/L · 2 samples
Nitrate/50 + nitrite/30.09limit 1 · 2 samples
Arsenicbelow 1 µg/Llimit 10 µg/L · 2 samples
Uranium0.74 µg/Llimit 30 µg/L · 1 sample
Copper0.0044 mg/Llimit 2 mg/L · 2 samples
Nickel19 µg/Llimit 20 µg/L · 1 sample
Cadmiumbelow 0.1 µg/Llimit 5 µg/L · 2 samples
Chromiumbelow 1 µg/Llimit 50 µg/L · 2 samples
Antimonybelow 1 µg/Llimit 10 µg/L · 2 samples
Seleniumbelow 1 µg/Llimit 20 µg/L · 2 samples
Boronbelow 0.01 mg/Llimit 1.5 mg/L · 2 samples
Fluoridebelow 0.1 mg/Llimit 1.5 mg/L · 2 samples
Trihalomethanes, totalbelow 0.2 µg/Llimit 100 µg/L · 1 sample
Free chlorine0.19 mg/Lno limit value · 5 samples
Manganesebelow 1 µg/Llimit 50 µg/L · 2 samples
Ironbelow 10 µg/Llimit 200 µg/L · 2 samples
Aluminium35 µg/Llimit 200 µg/L · 2 samples
Ammoniumbelow 0.013 mg/Llimit 0.5 mg/L · 2 samples
Chloride6.1 mg/Llimit 250 mg/L · 2 samples
Sulphate3.4 mg/Llimit 250 mg/L · 2 samples
Sodium3 mg/Llimit 200 mg/L · 2 samples
pH7.3–7.8limit 6.5–9.5 · 10 samples
Electrical conductivity498 µS/cmlimit 2,500 µS/cm · 10 samples

Samples by year

0352016: 5 samples, all compliant’162017: 5 samples, all compliant’172018: 5 samples, all compliant’182019: 5 samples, all compliant’192020: 4 samples, all compliant’202021: 4 samples, all compliant’212022: 4 samples, all compliant’222023: 4 samples, all compliant’232024: 4 samples, all compliant’242025: 4 samples, all compliant’252026: 2 samples, all compliant’26
compliant non-compliant · Samples from the Stari Trg - Lož water system

Municipalities

Drinking water in Loška dolina

What you can do

How to read the results

The ratings are a Draga Slovenija summary, not an official NIJZ rating.

Follow the results for your address

When the state monitoring publishes a non-compliant result for the area by your address, we e-mail you (results come out about once a month). One address is free. This is not an urgent boil-water alert; the operator announces those.

Find your address and turn on following →

Source: NIJZ and NLZOH, mpv.si; latest sample 31 Aug 2026. Processing: Draga Slovenija.

Frequently asked questions

Is the water from the Stari Trg - Lož water system safe to drink?

The Stari Trg - Lož water system (operator JP Komunala Cerknica d.o.o.) supplies 3,497 users in the municipality of Loška dolina. In 2024–2026 the state monitoring took 10 samples and all were compliant. The operator announces current restrictions on use.

How hard is the water from the Stari Trg - Lož water system?

Estimated from electrical conductivity at 15.9 °dH, which is hard water.

AI chat