Draga SlovenijaDraga Slovenija

Drinking water: Šentrupert 2 water system

Repeated or health-relevant non-compliance

The Šentrupert 2 water system (operator Komunala Trebnje) supplies 580 users in the municipality of Šentrupert. In 2024–2026 the state monitoring took 9 samples, of which 2 were not compliant.

These are state monitoring results from 2024–2026, not a notice about the water today. Current notices (boil-water, do-not-use) are published by the water-system operator on its website.

Samples 2024–202691 supply area
Non-compliant222%
Hardness (operator)18.7 °dHhard
Users580Komunala Trebnje

Supply areas

ŠENTRUPERT

Repeated or health-relevant non-compliance

Operator: Komunala Trebnje · 580 users · water system Šentrupert 2

Samples 2024–2026
9, 2 non-compliant
Water source
Groundwater, not influenced by surface water
Treatment
Sodium hypochlorite disinfection
Hardness (operator)
16.3–21.1 °dH, hard source 2025
Latest sample
17 Apr 2026
E. coli0 per 100 mLlimit 0 per 100 mL · 9 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 9 samples
Nitrate14 mg/Llimit 50 mg/L · 3 samples
Single pesticide (highest)0.13 µg/L (Desetil-atrazin)limit 0.1 µg/L · 2 samples · 1× over the limit
Arsenic0.34 µg/Llimit 10 µg/L · 2 samples
Manganese0.33 µg/Llimit 50 µg/L · 2 samples
Ironbelow 40 µg/Llimit 200 µg/L · 2 samples
Non-compliant samples (2)
  • · Coliform bacteria 2 per 100 mL limit 0 per 100 mL
  • · Single pesticide (highest) (Desetil-atrazin) 0.13 µg/L limit 0.1 µg/L

Measured values 2024–2026

ParameterHighest valueAgainst the limit
E. coli0 per 100 mLlimit 0 per 100 mL · 9 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 9 samples
Coliform bacteria2 per 100 mLlimit 0 per 100 mL · 9 samples · 1× over the limit
Nitrate14 mg/Llimit 50 mg/L · 3 samples
Nitrite0.015 mg/Llimit 0.5 mg/L · 3 samples
Nitrate/50 + nitrite/30.28limit 1 · 3 samples
Single pesticide (highest)0.13 µg/L (Desetil-atrazin)limit 0.1 µg/L · 2 samples · 1× over the limit
Arsenic0.34 µg/Llimit 10 µg/L · 2 samples
Uranium1.2 µg/Llimit 30 µg/L · 1 sample
Copper0.0024 mg/Llimit 2 mg/L · 2 samples
Nickel0.1 µg/Llimit 20 µg/L · 1 sample
Cadmiumbelow 0.02 µg/Llimit 5 µg/L · 2 samples
Chromiumbelow 0.4 µg/Llimit 50 µg/L · 2 samples
Antimony0.1 µg/Llimit 10 µg/L · 2 samples
Selenium0.26 µg/Llimit 20 µg/L · 2 samples
Boron0.026 mg/Llimit 1.5 mg/L · 2 samples
Fluoride0.076 mg/Llimit 1.5 mg/L · 3 samples
Trihalomethanes, total1 µg/Llimit 100 µg/L · 2 samples
Chloratebelow 0.05 mg/Llimit 0.25 mg/L · 1 sample
Chloritebelow 0.05 mg/Llimit 0.25 mg/L · 1 sample
Free chlorine0.24 mg/Lno limit value · 7 samples
Manganese0.33 µg/Llimit 50 µg/L · 2 samples
Ironbelow 40 µg/Llimit 200 µg/L · 2 samples
Aluminiumbelow 0.9 µg/Llimit 200 µg/L · 2 samples
Ammoniumbelow 0.01 mg/Llimit 0.5 mg/L · 3 samples
Chloride8.2 mg/Llimit 250 mg/L · 3 samples
Sulphate12.3 mg/Llimit 250 mg/L · 3 samples
Sodium5 mg/Llimit 200 mg/L · 2 samples
pH7.2–7.5limit 6.5–9.5 · 9 samples
Electrical conductivity671 µS/cmlimit 2,500 µS/cm · 9 samples

Non-compliant samples

Samples by year

0352016: 5 samples, 1 non-compliant’162017: 5 samples, 1 non-compliant’172018: 5 samples, all compliant’182019: 5 samples, 1 non-compliant’192020: 4 samples, 1 non-compliant’202021: 4 samples, 2 non-compliant’212022: 4 samples, 1 non-compliant’222023: 4 samples, 1 non-compliant’232024: 4 samples, 2 non-compliant’242025: 4 samples, all compliant’252026: 1 sample, all compliant’26
compliant non-compliant · Samples from the Šentrupert 2 water system

Municipalities

Drinking water in Šentrupert

What you can do

How to read the results

The ratings are a Draga Slovenija summary, not an official NIJZ rating.

Follow the results for your address

When the state monitoring publishes a non-compliant result for the area by your address, we e-mail you (results come out about once a month). One address is free. This is not an urgent boil-water alert; the operator announces those.

Find your address and turn on following →

Source: NIJZ and NLZOH, mpv.si; latest sample 31 Aug 2026. Processing: Draga Slovenija.

Frequently asked questions

Is the water from the Šentrupert 2 water system safe to drink?

The Šentrupert 2 water system (operator Komunala Trebnje) supplies 580 users in the municipality of Šentrupert. In 2024–2026 the state monitoring took 9 samples, of which 2 were not compliant. The operator announces current restrictions on use.

How hard is the water from the Šentrupert 2 water system?

According to the operator 18.7 °dH, which is hard water.

AI chat

Ask the data, in plain language

The AI chat finds the answer in the official register and shows it with a table you can download and a link into the map. Free; it only needs an account.

For example: Which municipalities issued the most building permits last year?

Open the AI chat

AI chat