Draga SlovenijaDraga Slovenija

Drinking water: Selca water system

Faecal bacteria in 1 sample

The Selca water system (operator Občina Železniki) supplies 800 users in the municipality of Železniki. In 2024–2026 the state monitoring took 10 samples, of which 1 was not compliant.

These are state monitoring results from 2024–2026, not a notice about the water today. Current notices (boil-water, do-not-use) are published by the water-system operator on its website.

Samples 2024–2026101 supply area
Non-compliant110%
Hardness (estimate)4.7 °dHsoft
Users800Občina Železniki

Supply areas

SELCA

Faecal bacteria in 1 sample

Operator: Občina Železniki · 800 users · water system Selca

Samples 2024–2026
10, 1 non-compliant
Water source
Groundwater, not influenced by surface water
Treatment
Sodium hypochlorite disinfection, UV disinfection
Hardness (estimate)
≈4.7 °dH, soft
Latest sample
4 May 2026
E. coli25 per 100 mLlimit 0 per 100 mL · 10 samples · 1× over the limit
Enterococci0 per 100 mLlimit 0 per 100 mL · 10 samples
Nitratebelow 1 mg/Llimit 50 mg/L · 3 samples
Arsenicbelow 1 µg/Llimit 10 µg/L · 2 samples
Manganesebelow 10 µg/Llimit 50 µg/L · 2 samples
Iron20 µg/Llimit 200 µg/L · 2 samples
Non-compliant samples (1)
  • · E. coli 25 per 100 mL limit 0 per 100 mL, Coliform bacteria 28 per 100 mL limit 0 per 100 mL

Measured values 2024–2026

ParameterHighest valueAgainst the limit
E. coli25 per 100 mLlimit 0 per 100 mL · 10 samples · 1× over the limit
Enterococci0 per 100 mLlimit 0 per 100 mL · 10 samples
Coliform bacteria28 per 100 mLlimit 0 per 100 mL · 10 samples · 1× over the limit
Nitratebelow 1 mg/Llimit 50 mg/L · 3 samples
Nitritebelow 0.01 mg/Llimit 0.5 mg/L · 1 sample
Nitrate/50 + nitrite/3below 0.02limit 1 · 3 samples
Arsenicbelow 1 µg/Llimit 10 µg/L · 2 samples
Uraniumbelow 10 µg/Llimit 30 µg/L · 1 sample
Copperbelow 0.01 mg/Llimit 2 mg/L · 2 samples
Nickelbelow 10 µg/Llimit 20 µg/L · 1 sample
Cadmiumbelow 1 µg/Llimit 5 µg/L · 2 samples
Chromiumbelow 10 µg/Llimit 50 µg/L · 2 samples
Antimonybelow 1 µg/Llimit 10 µg/L · 2 samples
Seleniumbelow 1 µg/Llimit 20 µg/L · 2 samples
Boronbelow 0.01 mg/Llimit 1.5 mg/L · 2 samples
Fluoridebelow 1 mg/Llimit 1.5 mg/L · 3 samples
Trihalomethanes, totalbelow 2 µg/Llimit 100 µg/L · 2 samples
Chlorate0.009 mg/Llimit 0.25 mg/L · 1 sample
Chloritebelow 0 mg/Llimit 0.25 mg/L · 1 sample
Free chlorine0.17 mg/Lno limit value · 8 samples
Manganesebelow 10 µg/Llimit 50 µg/L · 2 samples
Iron20 µg/Llimit 200 µg/L · 2 samples
Aluminiumbelow 10 µg/Llimit 200 µg/L · 2 samples
Ammoniumbelow 0.02 mg/Llimit 0.5 mg/L · 3 samples
Chloride1.2 mg/Llimit 250 mg/L · 3 samples
Sulphate7.7 mg/Llimit 250 mg/L · 3 samples
Sodium2.9 mg/Llimit 200 mg/L · 2 samples
pH7.7–8limit 6.5–9.5 · 10 samples
Electrical conductivity274 µS/cmlimit 2,500 µS/cm · 10 samples

Non-compliant samples

Samples by year

0352016: 5 samples, all compliant’162017: 5 samples, 1 non-compliant’172018: 5 samples, all compliant’182019: 5 samples, all compliant’192020: 4 samples, all compliant’202021: 4 samples, all compliant’212022: 4 samples, all compliant’222023: 4 samples, 1 non-compliant’232024: 4 samples, all compliant’242025: 4 samples, all compliant’252026: 2 samples, 1 non-compliant’26
compliant non-compliant · Samples from the Selca water system

Municipalities

Drinking water in Železniki

What you can do

How to read the results

The ratings are a Draga Slovenija summary, not an official NIJZ rating.

Follow the results for your address

When the state monitoring publishes a non-compliant result for the area by your address, we e-mail you (results come out about once a month). One address is free. This is not an urgent boil-water alert; the operator announces those.

Find your address and turn on following →

Source: NIJZ and NLZOH, mpv.si; latest sample 31 Aug 2026. Processing: Draga Slovenija.

Frequently asked questions

Is the water from the Selca water system safe to drink?

The Selca water system (operator Občina Železniki) supplies 800 users in the municipality of Železniki. In 2024–2026 the state monitoring took 10 samples, of which 1 was not compliant. The operator announces current restrictions on use.

How hard is the water from the Selca water system?

Estimated from electrical conductivity at 4.7 °dH, which is soft water.