Draga SlovenijaDraga Slovenija

Drinking water: Podmolnik water system

All samples compliant

The Podmolnik water system (operator MOL) supplies 620 users in the municipality of Ljubljana. In 2024–2026 the state monitoring took 9 samples and all were compliant.

These are state monitoring results from 2024–2026, not a notice about the water today. Current notices (boil-water, do-not-use) are published by the water-system operator on its website.

Samples 2024–202691 supply area
Non-compliant00%
Hardness (estimate)18.8 °dHhard
Users620MOL

Supply areas

PODMOLNIK

All samples compliant

Operator: MOL · 620 users · water system Podmolnik

Samples 2024–2026
9, all compliant
Water source
Groundwater, not influenced by surface water
Treatment
No treatment
Hardness (estimate)
≈18.8 °dH, hard
Latest sample
21 May 2026
E. coli0 per 100 mLlimit 0 per 100 mL · 9 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 9 samples
Nitrate3.5 mg/Llimit 50 mg/L · 3 samples
Arsenicbelow 1 µg/Llimit 10 µg/L · 2 samples
Manganesebelow 1 µg/Llimit 50 µg/L · 2 samples
Iron11 µg/Llimit 200 µg/L · 2 samples

Measured values 2024–2026

ParameterHighest valueAgainst the limit
E. coli0 per 100 mLlimit 0 per 100 mL · 9 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 9 samples
Coliform bacteria0 per 100 mLlimit 0 per 100 mL · 9 samples
Nitrate3.5 mg/Llimit 50 mg/L · 3 samples
Nitritebelow 0.007 mg/Llimit 0.5 mg/L · 3 samples
Nitrate/50 + nitrite/30.07limit 1 · 3 samples
Arsenicbelow 1 µg/Llimit 10 µg/L · 2 samples
Uranium0.27 µg/Llimit 30 µg/L · 1 sample
Copper0.0035 mg/Llimit 2 mg/L · 2 samples
Nickelbelow 1 µg/Llimit 20 µg/L · 1 sample
Cadmiumbelow 0.1 µg/Llimit 5 µg/L · 2 samples
Chromiumbelow 1 µg/Llimit 50 µg/L · 2 samples
Antimonybelow 1 µg/Llimit 10 µg/L · 2 samples
Seleniumbelow 1 µg/Llimit 20 µg/L · 2 samples
Boronbelow 0.01 mg/Llimit 1.5 mg/L · 2 samples
Fluoridebelow 0.1 mg/Llimit 1.5 mg/L · 3 samples
Manganesebelow 1 µg/Llimit 50 µg/L · 2 samples
Iron11 µg/Llimit 200 µg/L · 2 samples
Aluminiumbelow 10 µg/Llimit 200 µg/L · 2 samples
Ammoniumbelow 0.013 mg/Llimit 0.5 mg/L · 3 samples
Chloride1.7 mg/Llimit 250 mg/L · 3 samples
Sulphate7.2 mg/Llimit 250 mg/L · 3 samples
Sodium0.84 mg/Llimit 200 mg/L · 2 samples
pH7.3–7.5limit 6.5–9.5 · 9 samples
Electrical conductivity585 µS/cmlimit 2,500 µS/cm · 9 samples

Samples by year

0352016: 5 samples, all compliant’162017: 5 samples, 1 non-compliant’172018: 5 samples, all compliant’182019: 5 samples, 1 non-compliant’192020: 4 samples, all compliant’202021: 4 samples, 1 non-compliant’212022: 4 samples, all compliant’222023: 4 samples, all compliant’232024: 4 samples, all compliant’242025: 4 samples, all compliant’252026: 1 sample, all compliant’26
compliant non-compliant · Samples from the Podmolnik water system

Municipalities

Drinking water in Ljubljana

What you can do

How to read the results

The ratings are a Draga Slovenija summary, not an official NIJZ rating.

Follow the results for your address

When the state monitoring publishes a non-compliant result for the area by your address, we e-mail you (results come out about once a month). One address is free. This is not an urgent boil-water alert; the operator announces those.

Find your address and turn on following →

Source: NIJZ and NLZOH, mpv.si; latest sample 31 Aug 2026. Processing: Draga Slovenija.

Frequently asked questions

Is the water from the Podmolnik water system safe to drink?

The Podmolnik water system (operator MOL) supplies 620 users in the municipality of Ljubljana. In 2024–2026 the state monitoring took 9 samples and all were compliant. The operator announces current restrictions on use.

How hard is the water from the Podmolnik water system?

Estimated from electrical conductivity at 18.8 °dH, which is hard water.

AI chat

Ask the data, in plain language

The AI chat finds the answer in the official register and shows it with a table you can download and a link into the map. Free; it only needs an account.

For example: Which municipalities issued the most building permits last year?

Open the AI chat

AI chat