Draga SlovenijaDraga Slovenija

Drinking water: Niževec Dražica water system

Repeated or health-relevant non-compliance

The Niževec Dražica water system (operator Občina Borovnica) supplies 77 users in the municipality of Borovnica. In 2024–2026 the state monitoring took 5 samples, of which 4 were not compliant.

These are state monitoring results from 2024–2026, not a notice about the water today. Current notices (boil-water, do-not-use) are published by the water-system operator on its website.

Samples 2024–202651 supply area
Non-compliant480%
Hardness (estimate)13.2 °dHmoderately hard
Users77Občina Borovnica

Supply areas

NIŽEVEC DRAŽICA

Repeated or health-relevant non-compliance

Operator: Občina Borovnica · 77 users · water system Niževec Dražica

Samples 2024–2026
5, 4 non-compliant
Water source
Influenced by surface water
Treatment
No treatment
Hardness (estimate)
≈13.2 °dH, moderately hard
Latest sample
1 Apr 2026
E. coli>80 per 100 mLlimit 0 per 100 mL · 5 samples · 3× over the limit
Enterococci72 per 100 mLlimit 0 per 100 mL · 5 samples · 4× over the limit
Nitrate5.3 mg/Llimit 50 mg/L · 1 sample
Lead0.59 µg/Llimit 10 µg/L · 3 samples
Non-compliant samples (4)
  • · E. coli >43 per 100 mL limit 0 per 100 mL, Enterococci 32 per 100 mL limit 0 per 100 mL, Coliform bacteria >80 per 100 mL limit 0 per 100 mL
  • · Enterococci 14 per 100 mL limit 0 per 100 mL, Coliform bacteria >80 per 100 mL limit 0 per 100 mL
  • · E. coli >80 per 100 mL limit 0 per 100 mL, Enterococci 72 per 100 mL limit 0 per 100 mL, Coliform bacteria >80 per 100 mL limit 0 per 100 mL
  • · E. coli >10 per 100 mL limit 0 per 100 mL, Enterococci 2 per 100 mL limit 0 per 100 mL, Coliform bacteria >80 per 100 mL limit 0 per 100 mL, Clostridium perfringens 2 per 100 mL limit 0 per 100 mL

Measured values 2024–2026

ParameterHighest valueAgainst the limit
E. coli>80 per 100 mLlimit 0 per 100 mL · 5 samples · 3× over the limit
Enterococci72 per 100 mLlimit 0 per 100 mL · 5 samples · 4× over the limit
Coliform bacteria>80 per 100 mLlimit 0 per 100 mL · 5 samples · 4× over the limit
Clostridium perfringens2 per 100 mLlimit 0 per 100 mL · 5 samples · 1× over the limit
Nitrate5.3 mg/Llimit 50 mg/L · 1 sample
Nitritebelow 0.007 mg/Llimit 0.5 mg/L · 1 sample
Nitrate/50 + nitrite/30.11limit 1 · 1 sample
Lead0.59 µg/Llimit 10 µg/L · 3 samples
Fluoridebelow 0.1 mg/Llimit 1.5 mg/L · 1 sample
Ammoniumbelow 0.013 mg/Llimit 0.5 mg/L · 1 sample
Chloride2 mg/Llimit 250 mg/L · 1 sample
Sulphate3.6 mg/Llimit 250 mg/L · 1 sample
pH7.7–8.1limit 6.5–9.5 · 5 samples
Electrical conductivity413 µS/cmlimit 2,500 µS/cm · 5 samples

Non-compliant samples

Samples by year

0122016: 2 samples, 2 non-compliant’162017: 2 samples, 1 non-compliant’172018: 2 samples, 2 non-compliant’182019: 2 samples, 1 non-compliant’192020: 2 samples, 2 non-compliant’202021: 2 samples, 2 non-compliant’212022: 2 samples, 1 non-compliant’222023: 2 samples, 2 non-compliant’232024: 2 samples, 2 non-compliant’242025: 2 samples, 2 non-compliant’252026: 1 sample, all compliant’26
compliant non-compliant · Samples from the Niževec Dražica water system

Municipalities

Drinking water in Borovnica

What you can do

How to read the results

The ratings are a Draga Slovenija summary, not an official NIJZ rating.

Follow the results for your address

When the state monitoring publishes a non-compliant result for the area by your address, we e-mail you (results come out about once a month). One address is free. This is not an urgent boil-water alert; the operator announces those.

Find your address and turn on following →

Source: NIJZ and NLZOH, mpv.si; latest sample 31 Aug 2026. Processing: Draga Slovenija.

Frequently asked questions

Is the water from the Niževec Dražica water system safe to drink?

The Niževec Dražica water system (operator Občina Borovnica) supplies 77 users in the municipality of Borovnica. In 2024–2026 the state monitoring took 5 samples, of which 4 were not compliant. The operator announces current restrictions on use.

How hard is the water from the Niževec Dražica water system?

Estimated from electrical conductivity at 13.2 °dH, which is moderately hard water.

AI chat

Ask the data, in plain language

The AI chat finds the answer in the official register and shows it with a table you can download and a link into the map. Free; it only needs an account.

For example: Which municipalities issued the most building permits last year?

Open the AI chat

AI chat