Draga SlovenijaDraga Slovenija

Drinking water: Dobrna water system

Faecal bacteria in 1 sample

The Dobrna water system (operator VOKA CELJE, d.o.o.) supplies 2,034 users in the municipality of Dobrna. In 2024–2026 the state monitoring took 20 samples, of which 1 was not compliant.

These are state monitoring results from 2024–2026, not a notice about the water today. Current notices (boil-water, do-not-use) are published by the water-system operator on its website.

Samples 2024–2026203 supply areas
Non-compliant15%
Hardness (operator)15.6 °dHhard
Users2,034VOKA CELJE, d.o.o.

Supply areas

Hudičev graben - Landšperg

Faecal bacteria in 1 sample

Operator: VOKA Celje · 1,209 users · water system Dobrna

Samples 2024–2026
10, 1 non-compliant
Water source
Influenced by surface water
Treatment
Ultrafiltration, activated carbon adsorption, regular disinfection, sodium hypochlorite disinfection
Hardness (operator)
12.2–18.1 °dH, hard source 2025
Latest sample
2 Jul 2026
E. coli0 per 100 mLlimit 0 per 100 mL · 10 samples
Enterococci1 per 100 mLlimit 0 per 100 mL · 10 samples · 1× over the limit
Nitrate12 mg/Llimit 50 mg/L · 2 samples
Arsenicbelow 1 µg/Llimit 10 µg/L · 2 samples
Manganesebelow 1 µg/Llimit 50 µg/L · 2 samples
Ironbelow 10 µg/Llimit 200 µg/L · 2 samples
Non-compliant samples (1)
  • · Enterococci 1 per 100 mL limit 0 per 100 mL

PAROŽ

All samples compliant

Operator: VOKA Celje · 789 users · water system Dobrna

Samples 2024–2026
9, all compliant
Water source
Groundwater, not influenced by surface water
Treatment
Regular disinfection, sodium hypochlorite disinfection
Hardness (operator)
16.3 °dH, hard source 2025
Latest sample
31 Mar 2026
E. coli0 per 100 mLlimit 0 per 100 mL · 9 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 9 samples
Nitrate3.8 mg/Llimit 50 mg/L · 3 samples
Arsenicbelow 1 µg/Llimit 10 µg/L · 2 samples
Manganesebelow 1 µg/Llimit 50 µg/L · 2 samples
Ironbelow 10 µg/Llimit 200 µg/L · 2 samples

BRDCE

All samples compliant

Operator: VOKA Celje · 36 users · water system Dobrna

Samples 2024–2026
1, all compliant
Water source
Groundwater, not influenced by surface water
Treatment
Rapid sand filters, regular disinfection, sodium hypochlorite disinfection
Hardness (operator)
17.3 °dH, hard source 2025
Latest sample
20 Apr 2026
E. coli0 per 100 mLlimit 0 per 100 mL · 1 sample
Enterococci0 per 100 mLlimit 0 per 100 mL · 1 sample
Nitrate8 mg/Llimit 50 mg/L · 1 sample

Measured values 2024–2026

ParameterHighest valueAgainst the limit
E. coli0 per 100 mLlimit 0 per 100 mL · 20 samples
Enterococci1 per 100 mLlimit 0 per 100 mL · 20 samples · 1× over the limit
Coliform bacteria0 per 100 mLlimit 0 per 100 mL · 20 samples
Clostridium perfringens0 per 100 mLlimit 0 per 100 mL · 2 samples
Nitrate12 mg/Llimit 50 mg/L · 6 samples
Nitritebelow 0.01 mg/Llimit 0.5 mg/L · 6 samples
Nitrate/50 + nitrite/30.24limit 1 · 6 samples
Arsenicbelow 1 µg/Llimit 10 µg/L · 4 samples
Uranium0.61 µg/Llimit 30 µg/L · 2 samples
Copper0.0054 mg/Llimit 2 mg/L · 4 samples
Nickelbelow 1 µg/Llimit 20 µg/L · 2 samples
Cadmiumbelow 0.1 µg/Llimit 5 µg/L · 4 samples
Chromiumbelow 1 µg/Llimit 50 µg/L · 4 samples
Antimonybelow 1 µg/Llimit 10 µg/L · 4 samples
Selenium1.3 µg/Llimit 20 µg/L · 4 samples
Boronbelow 0.01 mg/Llimit 1.5 mg/L · 4 samples
Fluoridebelow 0.1 mg/Llimit 1.5 mg/L · 6 samples
Trihalomethanes, total2.3 µg/Llimit 100 µg/L · 3 samples
Chloratebelow 0.05 mg/Llimit 0.25 mg/L · 2 samples
Chloritebelow 0.05 mg/Llimit 0.25 mg/L · 2 samples
Free chlorine0.29 mg/Lno limit value · 17 samples
Manganesebelow 1 µg/Llimit 50 µg/L · 4 samples
Ironbelow 10 µg/Llimit 200 µg/L · 4 samples
Aluminiumbelow 10 µg/Llimit 200 µg/L · 4 samples
Ammoniumbelow 0.05 mg/Llimit 0.5 mg/L · 6 samples
Chloride5.6 mg/Llimit 250 mg/L · 6 samples
Sulphate19.1 mg/Llimit 250 mg/L · 6 samples
Sodium6.4 mg/Llimit 200 mg/L · 4 samples
pH7.3–8.3limit 6.5–9.5 · 20 samples
Electrical conductivity525 µS/cmlimit 2,500 µS/cm · 20 samples

Non-compliant samples

Samples by year

05102016: 10 samples, all compliant’162017: 10 samples, 1 non-compliant’172018: 10 samples, all compliant’182019: 10 samples, all compliant’192020: 8 samples, all compliant’202021: 8 samples, all compliant’212022: 8 samples, all compliant’222023: 8 samples, all compliant’232024: 8 samples, all compliant’242025: 8 samples, 1 non-compliant’252026: 4 samples, all compliant’26
compliant non-compliant · Samples from the Dobrna water system

Municipalities

Drinking water in Dobrna

What you can do

How to read the results

The ratings are a Draga Slovenija summary, not an official NIJZ rating.

Follow the results for your address

When the state monitoring publishes a non-compliant result for the area by your address, we e-mail you (results come out about once a month). One address is free. This is not an urgent boil-water alert; the operator announces those.

Find your address and turn on following →

Source: NIJZ and NLZOH, mpv.si; latest sample 31 Aug 2026. Processing: Draga Slovenija.

Frequently asked questions

Is the water from the Dobrna water system safe to drink?

The Dobrna water system (operator VOKA CELJE, d.o.o.) supplies 2,034 users in the municipality of Dobrna. In 2024–2026 the state monitoring took 20 samples, of which 1 was not compliant. The operator announces current restrictions on use.

How hard is the water from the Dobrna water system?

According to the operator 15.6 °dH, which is hard water.

AI chat

Ask the data, in plain language

The AI chat finds the answer in the official register and shows it with a table you can download and a link into the map. Free; it only needs an account.

For example: Which municipalities issued the most building permits last year?

Open the AI chat

AI chat