Draga SlovenijaDraga Slovenija

Drinking water: Celje water system

Occasional non-compliance

The Celje water system (operator VOKA CELJE, d.o.o.) supplies 59,239 users in the municipalities of Celje, Vojnik, Štore. In 2024–2026 the state monitoring took 137 samples, of which 3 were not compliant.

These are state monitoring results from 2024–2026, not a notice about the water today. Current notices (boil-water, do-not-use) are published by the water-system operator on its website.

Samples 2024–20261378 supply areas
Non-compliant32.2%
Hardness (operator and estimate)17 °dHhard
Users59,239VOKA CELJE, d.o.o.

Supply areas

Celje - osrednje območje

Occasional non-compliance

Operator: VOKA Celje · 55,177 users · water system Celje

Samples 2024–2026
83, 2 non-compliant
Water source
Influenced by surface water
Treatment
Coagulation, flocculation, ultrafiltration, rapid sand filters, activated carbon adsorption, regular disinfection, chlorine gas disinfection, sodium hypochlorite disinfection, ozone disinfection, UV disinfection
Hardness (operator)
13.7–20.9 °dH, hard source 2025
Latest sample
2 Jul 2026
E. coli0 per 100 mLlimit 0 per 100 mL · 83 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 83 samples
Nitrate34 mg/Llimit 50 mg/L · 7 samples
Single pesticide (highest)below 0.05 µg/Llimit 0.1 µg/L · 3 samples
Arsenicbelow 1 µg/Llimit 10 µg/L · 6 samples
Manganesebelow 1 µg/Llimit 50 µg/L · 6 samples
Iron22 µg/Llimit 200 µg/L · 6 samples
Non-compliant samples (2)
  • · Coliform bacteria 1 per 100 mL limit 0 per 100 mL
  • · marked non-compliant; the published data gives no reason

KOŠNICA - TREMERJE

All samples compliant

Operator: VOKA Celje · 963 users · water system Celje

Samples 2024–2026
10, all compliant
Water source
Influenced by surface water
Treatment
Regular disinfection, sodium hypochlorite disinfection
Hardness (operator)
7.3–15.8 °dH, moderately hard source 2025
Latest sample
2 Jul 2026
E. coli0 per 100 mLlimit 0 per 100 mL · 10 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 10 samples
Nitrate3.2 mg/Llimit 50 mg/L · 2 samples
Arsenic1.4 µg/Llimit 10 µg/L · 2 samples
Manganesebelow 1 µg/Llimit 50 µg/L · 2 samples
Ironbelow 10 µg/Llimit 200 µg/L · 2 samples

Toplica

All samples compliant

Operator: VOKA Celje · 934 users · water system Celje

Samples 2024–2026
10, all compliant
Water source
Influenced by surface water
Treatment
Ultrafiltration, activated carbon adsorption, regular disinfection, sodium hypochlorite disinfection
Hardness (operator)
15.6 °dH, hard source 2025
Latest sample
2 Jul 2026
E. coli0 per 100 mLlimit 0 per 100 mL · 10 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 10 samples
Nitrate4.9 mg/Llimit 50 mg/L · 3 samples
Arsenicbelow 1 µg/Llimit 10 µg/L · 2 samples
Manganesebelow 1 µg/Llimit 50 µg/L · 2 samples
Ironbelow 10 µg/Llimit 200 µg/L · 2 samples

Kapelca

Occasional non-compliance

Operator: VOKA Celje · 661 users · water system Celje

Samples 2024–2026
9, 1 non-compliant
Water source
Groundwater, not influenced by surface water
Treatment
Regular disinfection, sodium hypochlorite disinfection
Hardness (operator)
10 °dH, moderately hard source 2025
Latest sample
13 Apr 2026
E. coli0 per 100 mLlimit 0 per 100 mL · 9 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 9 samples
Nitrate3.3 mg/Llimit 50 mg/L · 3 samples
Arsenicbelow 1 µg/Llimit 10 µg/L · 2 samples
Manganesebelow 1 µg/Llimit 50 µg/L · 2 samples
Iron36 µg/Llimit 200 µg/L · 2 samples
Non-compliant samples (1)
  • · Coliform bacteria 1 per 100 mL limit 0 per 100 mL

Beli potok

All samples compliant

Operator: VOKA Celje · 626 users · water system Celje

Samples 2024–2026
9, all compliant
Water source
Influenced by surface water
Treatment
Ultrafiltration, regular disinfection, sodium hypochlorite disinfection
Hardness (operator)
14.2 °dH, hard source 2025
Latest sample
13 Apr 2026
E. coli0 per 100 mLlimit 0 per 100 mL · 9 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 9 samples
Nitrate4.2 mg/Llimit 50 mg/L · 2 samples
Arsenicbelow 1 µg/Llimit 10 µg/L · 2 samples
Manganesebelow 1 µg/Llimit 50 µg/L · 2 samples
Ironbelow 10 µg/Llimit 200 µg/L · 2 samples

Laška vas - Bojansko

All samples compliant

Operator: VOKA Celje · 462 users · water system Celje

Samples 2024–2026
9, all compliant
Water source
Influenced by surface water
Treatment
Coagulation, flocculation, rapid sand filters, regular disinfection, sodium hypochlorite disinfection
Hardness (operator)
14.7 °dH, hard source 2025
Latest sample
13 Apr 2026
E. coli0 per 100 mLlimit 0 per 100 mL · 9 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 9 samples
Nitrate3.2 mg/Llimit 50 mg/L · 3 samples
Arsenicbelow 1 µg/Llimit 10 µg/L · 2 samples
Manganesebelow 1 µg/Llimit 50 µg/L · 2 samples
Ironbelow 10 µg/Llimit 200 µg/L · 2 samples

SVETINA

All samples compliant

Operator: VOKA Celje · 289 users · water system Celje

Samples 2024–2026
5, all compliant
Water source
Influenced by surface water
Treatment
Rapid sand filters, activated carbon adsorption, regular disinfection, sodium hypochlorite disinfection
Hardness (operator)
17.8 °dH, hard source 2025
Latest sample
6 Mar 2026
E. coli0 per 100 mLlimit 0 per 100 mL · 5 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 5 samples
Nitrate5.3 mg/Llimit 50 mg/L · 1 sample

LAHKA PEČ

All samples compliant

Operator: VOKA Celje · 127 users · water system Celje

Samples 2024–2026
2, all compliant
Water source
Groundwater springs with surface inflow
Treatment
Regular disinfection, sodium hypochlorite disinfection
Hardness (estimate)
≈17.9 °dH, hard
Latest sample
30 Sep 2025
E. coli0 per 100 mLlimit 0 per 100 mL · 2 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 2 samples
Lead0.6 µg/Llimit 10 µg/L · 1 sample

Measured values 2024–2026

ParameterHighest valueAgainst the limit
E. coli0 per 100 mLlimit 0 per 100 mL · 137 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 137 samples
Coliform bacteria1 per 100 mLlimit 0 per 100 mL · 137 samples · 2× over the limit
Clostridium perfringens0 per 100 mLlimit 0 per 100 mL · 118 samples
Nitrate34 mg/Llimit 50 mg/L · 21 samples
Nitritebelow 0.01 mg/Llimit 0.5 mg/L · 21 samples
Nitrate/50 + nitrite/30.68limit 1 · 21 samples
Single pesticide (highest)below 0.05 µg/Llimit 0.1 µg/L · 3 samples
Pesticides, totalbelow 0.05 µg/Llimit 0.5 µg/L · 1 sample
Lead0.6 µg/Llimit 10 µg/L · 1 sample
Arsenic1.4 µg/Llimit 10 µg/L · 16 samples
Uranium0.91 µg/Llimit 30 µg/L · 8 samples
Copper0.0075 mg/Llimit 2 mg/L · 16 samples
Nickelbelow 1 µg/Llimit 20 µg/L · 8 samples
Cadmium0.042 µg/Llimit 5 µg/L · 16 samples
Chromiumbelow 1 µg/Llimit 50 µg/L · 16 samples
Antimonybelow 1 µg/Llimit 10 µg/L · 16 samples
Selenium1.8 µg/Llimit 20 µg/L · 16 samples
Boron0.051 mg/Llimit 1.5 mg/L · 16 samples
Fluoridebelow 0.1 mg/Llimit 1.5 mg/L · 21 samples
Trihalomethanes, total3.1 µg/Llimit 100 µg/L · 14 samples
Bromatebelow 3 µg/Llimit 10 µg/L · 21 samples
Chloratebelow 0.05 mg/Llimit 0.25 mg/L · 9 samples
Chloritebelow 0.05 mg/Llimit 0.25 mg/L · 9 samples
Tetrachloroethene + trichloroethenebelow 0.2 µg/Llimit 10 µg/L · 1 sample
Free chlorine0.33 mg/Lno limit value · 109 samples
Manganesebelow 1 µg/Llimit 50 µg/L · 16 samples
Iron36 µg/Llimit 200 µg/L · 16 samples
Aluminiumbelow 10 µg/Llimit 200 µg/L · 21 samples
Ammoniumbelow 0.05 mg/Llimit 0.5 mg/L · 21 samples
Chloride25 mg/Llimit 250 mg/L · 21 samples
Sulphate17.8 mg/Llimit 250 mg/L · 21 samples
Sodium12 mg/Llimit 200 mg/L · 16 samples
pH6.9–8.9limit 6.5–9.5 · 137 samples
Electrical conductivity628 µS/cmlimit 2,500 µS/cm · 137 samples

Non-compliant samples

Samples by year

033652016: 65 samples, 3 non-compliant’162017: 65 samples, all compliant’172018: 65 samples, 3 non-compliant’182019: 65 samples, 1 non-compliant’192020: 56 samples, 1 non-compliant’202021: 56 samples, all compliant’212022: 56 samples, 1 non-compliant’222023: 56 samples, 1 non-compliant’232024: 56 samples, 3 non-compliant’242025: 58 samples, all compliant’252026: 23 samples, all compliant’26
compliant non-compliant · Samples from the Celje water system

Municipalities

Drinking water in Celje · Drinking water in Vojnik · Drinking water in Štore

What you can do

How to read the results

The ratings are a Draga Slovenija summary, not an official NIJZ rating.

Follow the results for your address

When the state monitoring publishes a non-compliant result for the area by your address, we e-mail you (results come out about once a month). One address is free. This is not an urgent boil-water alert; the operator announces those.

Find your address and turn on following →

Source: NIJZ and NLZOH, mpv.si; latest sample 31 Aug 2026. Processing: Draga Slovenija.

Frequently asked questions

Is the water from the Celje water system safe to drink?

The Celje water system (operator VOKA CELJE, d.o.o.) supplies 59,239 users in the municipalities of Celje, Vojnik, Štore. In 2024–2026 the state monitoring took 137 samples, of which 3 were not compliant. The operator announces current restrictions on use.

How hard is the water from the Celje water system?

Estimated from electrical conductivity at 17 °dH, which is hard water.

AI chat

Ask the data, in plain language

The AI chat finds the answer in the official register and shows it with a table you can download and a link into the map. Free; it only needs an account.

For example: Which municipalities issued the most building permits last year?

Open the AI chat

AI chat