Draga SlovenijaDraga Slovenija

Drinking water: Hydrovod

Occasional non-compliance

Hydrovod supplies drinking water to 36,861 users in the municipalities of Ribnica, Kočevje, Sodražica, Loški Potok, Kostel, Črnomelj. In 2024–2026 the state monitoring sampled 16 water systems of this operator and took 141 samples, of which 8 were not compliant. Water hardness differs between systems, 10.9–20.1 °dH; most customers get moderately hard water (≈11.9 °dH).

These are state monitoring results from 2024–2026, not a notice about the water today. Current notices (boil-water, do-not-use) are published by the water-system operator on its website.

Samples 2024–202614116 water systems
Non-compliant85.7%
Hardness10.9–20.1 °dHmoderately hard
Users36,8616 municipalities

Notices from Hydrovod

Boil-water notices, bans on use and supply interruptions are published by Hydrovod on its website (hydrovod.si) and in local media. This page shows state monitoring results, not current notices. What a boil-water notice means is explained on Boiling water.

Water systems run by Hydrovod

Water systemMunicipalitiesUsersHardness (°dH)Assessment
Kočevje - Ribnica - SodražicaKočevje, Ribnica, Sodražica32,44811.7Occasional non-compliance
Loški PotokLoški Potok1,80511.9compliant
Kot - Jurjevica - BrežeRibnica54013.9Occasional non-compliance
Kočevska RekaKočevje31313.2Occasional non-compliance
Sajevec - DaneRibnica30413.5compliant
ŽimariceSodražica288≈13.6Occasional non-compliance
Jakšiči - FaraKostel28114.2compliant
Predgrad - DolČrnomelj18813.9compliant
Kostel - Kaptol - DelačKostel16816.7compliant
Brezovica - VimoljKočevje14610.9Occasional non-compliance
GoraSodražica14120.1compliant
Trava - Srednja VasLoški Potok7814.1Occasional non-compliance
Vrh - KrkovoKostel7712.9compliant
KoprivnikKočevje6517.2compliant
ŽagaKostel1415compliant
BilpaČrnomelj511.3compliant

Measured values 2024–2026

ParameterHighest valueAgainst the limit
E. coli0 per 100 mLlimit 0 per 100 mL · 141 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 141 samples
Coliform bacteria2 per 100 mLlimit 0 per 100 mL · 141 samples · 2× over the limit
Clostridium perfringens1 per 100 mLlimit 0 per 100 mL · 114 samples · 1× over the limit
Nitrate5.71 mg/Llimit 50 mg/L · 27 samples
Nitrite0.0075 mg/Llimit 0.5 mg/L · 27 samples
Nitrate/50 + nitrite/30.11limit 1 · 27 samples
PFAS, totalbelow 0.03 µg/Llimit 0.5 µg/L · 3 samples
PFOAbelow 0.0005 µg/Lpart of the 20-PFAS sum, limit 0.1 µg/L · 3 samples
PFOS0.0006 µg/Lpart of the 20-PFAS sum, limit 0.1 µg/L · 3 samples
Arsenic0.24 µg/Llimit 10 µg/L · 18 samples
Uranium1.1 µg/Llimit 30 µg/L · 10 samples
Copper0.0067 mg/Llimit 2 mg/L · 18 samples
Nickel0.19 µg/Llimit 20 µg/L · 10 samples
Cadmium0.059 µg/Llimit 5 µg/L · 18 samples
Chromiumbelow 0.4 µg/Llimit 50 µg/L · 18 samples
Antimony0.068 µg/Llimit 10 µg/L · 18 samples
Selenium0.23 µg/Llimit 20 µg/L · 18 samples
Boron0.0043 mg/Llimit 1.5 mg/L · 18 samples
Fluoride0.096 mg/Llimit 1.5 mg/L · 27 samples
Trihalomethanes, total42 µg/Llimit 100 µg/L · 21 samples
Haloacetic acids7.1 µg/Llimit 60 µg/L · 3 samples
Chlorate0.26 mg/Llimit 0.25 mg/L · 8 samples · 1× over the limit
Chloritebelow 0.05 mg/Llimit 0.25 mg/L · 8 samples
Free chlorine0.31 mg/Lno limit value · 84 samples
Manganese0.64 µg/Llimit 50 µg/L · 18 samples
Ironbelow 40 µg/Llimit 200 µg/L · 18 samples
Aluminium18 µg/Llimit 200 µg/L · 18 samples
Ammonium0.081 mg/Llimit 0.5 mg/L · 27 samples
Chloride29 mg/Llimit 250 mg/L · 27 samples
Sulphate16 mg/Llimit 250 mg/L · 27 samples
Sodium3.6 mg/Llimit 200 mg/L · 18 samples
pH6.9–8.2limit 6.5–9.5 · 141 samples
Electrical conductivity559 µS/cmlimit 2,500 µS/cm · 141 samples

Non-compliant samples

Samples by year

033652016: 65 samples, 3 non-compliant’162017: 65 samples, 1 non-compliant’172018: 65 samples, 3 non-compliant’182019: 65 samples, 3 non-compliant’192020: 57 samples, 4 non-compliant’202021: 57 samples, 1 non-compliant’212022: 57 samples, 1 non-compliant’222023: 57 samples, 1 non-compliant’232024: 57 samples, 4 non-compliant’242025: 59 samples, 4 non-compliant’252026: 25 samples, all compliant’26
compliant non-compliant · Samples from Hydrovod systems

Municipalities

Drinking water in Ribnica · Drinking water in Kočevje · Drinking water in Sodražica · Drinking water in Loški Potok · Drinking water in Kostel · Drinking water in Črnomelj

What you can do

How to read the results

The ratings are a Draga Slovenija summary, not an official NIJZ rating.

Source: NIJZ and NLZOH, mpv.si; latest sample 31 Aug 2026. Processing: Draga Slovenija.

Frequently asked questions

Is the water from Hydrovod safe to drink?

Hydrovod supplies drinking water to 36,861 users in the municipalities of Ribnica, Kočevje, Sodražica, Loški Potok, Kostel, Črnomelj. In 2024–2026 the state monitoring sampled 16 water systems of this operator and took 141 samples, of which 8 were not compliant. The operator announces current restrictions on use.

How hard is the water from Hydrovod?

Water hardness differs between systems, 10.9–20.1 °dH; most customers get moderately hard water (≈11.9 °dH).

Where does Hydrovod publish boil-water notices?

On its website (https://hydrovod.si/) and in local media. A boil-water notice applies until the operator lifts it.

AI chat

Ask the data, in plain language

The AI chat finds the answer in the official register and shows it with a table you can download and a link into the map. Free; it only needs an account.

For example: Which municipalities issued the most building permits last year?