Drinking water: Občina Kanal ob Soči
Občina Kanal ob Soči supplies drinking water to 5,781 users in the municipality of Kanal ob Soči. In 2024–2026 the state monitoring sampled 24 water systems of this operator and took 102 samples, of which 16 were not compliant. Water hardness differs between systems, 8.3–13.1 °dH; most customers get moderately hard water (≈9.9 °dH).
These are state monitoring results from 2024–2026, not a notice about the water today. Current notices (boil-water, do-not-use) are published by the water-system operator on its website.
Notices from Občina Kanal ob Soči
Boil-water notices, bans on use and supply interruptions are published by Občina Kanal ob Soči on its website and in local media. This page shows state monitoring results, not current notices. What a boil-water notice means is explained on Boiling water.
Water systems run by Občina Kanal ob Soči
| Water system | Municipalities | Users | Hardness (°dH) | Assessment |
|---|---|---|---|---|
| Kanal | Kanal ob Soči | 2,029 | ≈9.9 | Faecal bacteria in 1 sample |
| Deskle | Kanal ob Soči | 1,329 | ≈8.3 | Occasional non-compliance |
| Industrijska Cona Anhovo | Kanal ob Soči | 600 | ≈8.7 | compliant |
| Ročinj - Doblar | Kanal ob Soči | 369 | ≈10.8 | compliant |
| Gorenje Deskle | Kanal ob Soči | 279 | ≈11.3 | compliant |
| Ložice | Kanal ob Soči | 264 | ≈12.5 | Occasional non-compliance |
| Kal nad Kanalom - Levpa | Kanal ob Soči | 151 | ≈11.5 | compliant |
| Plave | Kanal ob Soči | 148 | ≈12.8 | Occasional non-compliance |
| Lig | Kanal ob Soči | 87 | ≈11.3 | compliant |
| Levpa | Kanal ob Soči | 72 | ≈8.8 | Faecal bacteria in 1 sample |
| Ajba | Kanal ob Soči | 70 | ≈12.1 | Faecal bacteria in 1 sample |
| Kanalski Vrh | Kanal ob Soči | 69 | ≈12.7 | compliant |
| Kambreško | Kanal ob Soči | 60 | ≈9.2 | Faecal bacteria in 1 sample |
| Prilesje 2 | Kanal ob Soči | 57 | ≈9.4 | compliant |
| Goljevica | Kanal ob Soči | 33 | ≈11.7 | Faecal bacteria in 1 sample |
| Krstenica | Kanal ob Soči | 32 | ≈13.1 | Faecal bacteria in 1 sample |
| Gorenji Doblar | Kanal ob Soči | 28 | ≈10.9 | Faecal bacteria in 1 sample |
| Srednje | Kanal ob Soči | 26 | ≈8.7 | Faecal bacteria in 1 sample |
| Dermota - Zagora | Kanal ob Soči | 21 | ≈11.3 | compliant |
| Čolnica | Kanal ob Soči | 17 | ≈12.8 | compliant |
| Zamedveje | Kanal ob Soči | 15 | ≈11.4 | compliant |
| Gorenje Nekovo | Kanal ob Soči | 13 | ≈12.9 | Faecal bacteria in 1 sample |
| Paljevo | Kanal ob Soči | 7 | ≈12.1 | compliant |
| Melinki | Kanal ob Soči | 5 | ≈12 | compliant |
Measured values 2024–2026
| Parameter | Highest value | Against the limit |
|---|---|---|
| E. coli | >80 per 100 mL | limit 0 per 100 mL · 102 samples · 8× over the limit |
| Enterococci | >80 per 100 mL | limit 0 per 100 mL · 102 samples · 5× over the limit |
| Coliform bacteria | >80 per 100 mL | limit 0 per 100 mL · 102 samples · 13× over the limit |
| Clostridium perfringens | 15 per 100 mL | limit 0 per 100 mL · 91 samples · 2× over the limit |
| Nitrate | 8.2 mg/L | limit 50 mg/L · 23 samples |
| Nitrite | below 0.013 mg/L | limit 0.5 mg/L · 23 samples |
| Nitrate/50 + nitrite/3 | 0.16 | limit 1 · 23 samples |
| Arsenic | 0.13 µg/L | limit 10 µg/L · 3 samples |
| Uranium | below 0.1 µg/L | limit 30 µg/L · 1 sample |
| Copper | 0.0012 mg/L | limit 2 mg/L · 3 samples |
| Nickel | 0.13 µg/L | limit 20 µg/L · 2 samples |
| Cadmium | below 0.02 µg/L | limit 5 µg/L · 3 samples |
| Chromium | below 0.4 µg/L | limit 50 µg/L · 3 samples |
| Mercury | below 0.01 µg/L | limit 1 µg/L · 8 samples |
| Antimony | 0.39 µg/L | limit 10 µg/L · 3 samples |
| Selenium | 0.17 µg/L | limit 20 µg/L · 3 samples |
| Boron | 0.0054 mg/L | limit 1.5 mg/L · 3 samples |
| Fluoride | below 1 mg/L | limit 1.5 mg/L · 23 samples |
| Trihalomethanes, total | 5.7 µg/L | limit 100 µg/L · 8 samples |
| Chlorate | 0.23 mg/L | limit 0.25 mg/L · 13 samples |
| Chlorite | below 0.05 mg/L | limit 0.25 mg/L · 13 samples |
| PAHs, total | below 0.01 µg/L | limit 0.1 µg/L · 1 sample |
| Benzo(a)pyrene | below 0.01 µg/L | limit 0.01 µg/L · 1 sample |
| Bisphenol A | below 0.025 µg/L | limit 2.5 µg/L · 1 sample |
| Free chlorine | 0.29 mg/L | no limit value · 70 samples |
| Manganese | below 0.1 µg/L | limit 50 µg/L · 3 samples |
| Iron | below 40 µg/L | limit 200 µg/L · 3 samples |
| Aluminium | 46 µg/L | limit 200 µg/L · 9 samples |
| Ammonium | below 0.02 mg/L | limit 0.5 mg/L · 23 samples |
| Chloride | 6.6 mg/L | limit 250 mg/L · 23 samples |
| Sulphate | 9.4 mg/L | limit 250 mg/L · 23 samples |
| Sodium | 1.6 mg/L | limit 200 mg/L · 3 samples |
| pH | 7.4–8.4 | limit 6.5–9.5 · 102 samples |
| Electrical conductivity | 434 µS/cm | limit 2,500 µS/cm · 102 samples |
Non-compliant samples
- · GORENJE POLJE - MOČILA · marked non-compliant; the published data gives no reason
- · KANAL · E. coli >80 per 100 mL limit 0 per 100 mL, Coliform bacteria >80 per 100 mL limit 0 per 100 mL
- · LOŽICE · Coliform bacteria 2 per 100 mL limit 0 per 100 mL
- · LOŽICE · Coliform bacteria 1 per 100 mL limit 0 per 100 mL
- · SREDNJE · E. coli 2 per 100 mL limit 0 per 100 mL, Coliform bacteria 51 per 100 mL limit 0 per 100 mL
- · GORENJI DOBLAR · E. coli 4 per 100 mL limit 0 per 100 mL, Coliform bacteria 22 per 100 mL limit 0 per 100 mL
- · KRSTENICA · E. coli 7 per 100 mL limit 0 per 100 mL, Enterococci 2 per 100 mL limit 0 per 100 mL, Coliform bacteria 53 per 100 mL limit 0 per 100 mL, Clostridium perfringens 15 per 100 mL limit 0 per 100 mL
- · GOLJEVICA · Enterococci 1 per 100 mL limit 0 per 100 mL, Coliform bacteria 50 per 100 mL limit 0 per 100 mL
- · GORENJE NEKOVO · E. coli 13 per 100 mL limit 0 per 100 mL, Enterococci 3 per 100 mL limit 0 per 100 mL, Coliform bacteria >80 per 100 mL limit 0 per 100 mL
- · PRILESJE · marked non-compliant; the published data gives no reason
- · PLAVE · Coliform bacteria 3 per 100 mL limit 0 per 100 mL
- · LOŽICE · Coliform bacteria 1 per 100 mL limit 0 per 100 mL
- · KANAL · marked non-compliant; the published data gives no reason
- · AJBA · E. coli 51 per 100 mL limit 0 per 100 mL, Enterococci 35 per 100 mL limit 0 per 100 mL, Coliform bacteria >80 per 100 mL limit 0 per 100 mL, Clostridium perfringens 5 per 100 mL limit 0 per 100 mL
- · LEVPA · E. coli >80 per 100 mL limit 0 per 100 mL, Enterococci >80 per 100 mL limit 0 per 100 mL, Coliform bacteria >80 per 100 mL limit 0 per 100 mL
- · KAMBREŠKO · E. coli 1 per 100 mL limit 0 per 100 mL, Coliform bacteria 36 per 100 mL limit 0 per 100 mL
Samples by year
Municipalities
What you can do
- Check which system supplies you. The operator is named on your water bill; the address search only shows the nearest sampling points.
- Follow the operator’s notices. Boil-water notices and bans on use are announced by the operator, usually on its website and in local media.
- Mind the building’s own pipes. The samples show the water in the network. In older buildings (before about 1970) let the water run for a while in the morning; an analysis of your own tap can be ordered from NLZOH or another accredited laboratory.
- Filters and softeners. A softener reduces limescale but removes neither bacteria nor other contaminants. A carbon filter improves taste and needs regular replacement. Against bacteria, boil the water as the operator instructs.
- Own wells and springs are not part of the state monitoring; their owner is responsible for them and for testing the water.
- Before buying a property ask whether it is connected to the public supply or has its own source, who the operator is, and look at the operator’s recent notices.
How to read the results
- All samples compliant all samples in this period met the Drinking Water Decree.
- Mostly compliant (municipality) non-compliant samples came only from smaller systems that together supply less than a quarter of the users there.
- Occasional non-compliance individual samples were not compliant on indicator parameters (iron, manganese, turbidity, coliform bacteria), which point to a problem in treatment or the network but are not a health limit.
- Faecal bacteria in 1 sample E. coli or enterococci were found in one sample. That is a serious finding, but a single one; check its date and the later samples.
- Repeated or health-relevant non-compliance faecal bacteria (E. coli, enterococci) in two or more samples, or a health-based chemical limit (nitrate, pesticides, lead, arsenic …) exceeded at least once.
The ratings are a Draga Slovenija summary, not an official NIJZ rating.
Source: NIJZ and NLZOH, mpv.si; latest sample 31 Aug 2026. Processing: Draga Slovenija.
Frequently asked questions
Is the water from Občina Kanal ob Soči safe to drink?
Občina Kanal ob Soči supplies drinking water to 5,781 users in the municipality of Kanal ob Soči. In 2024–2026 the state monitoring sampled 24 water systems of this operator and took 102 samples, of which 16 were not compliant. The operator announces current restrictions on use.
How hard is the water from Občina Kanal ob Soči?
Water hardness differs between systems, 8.3–13.1 °dH; most customers get moderately hard water (≈9.9 °dH).
Where does Občina Kanal ob Soči publish boil-water notices?
On its website and in local media. A boil-water notice applies until the operator lifts it.