Drinking water: Komunala Tolmin
Komunala Tolmin supplies drinking water to 17,780 users in the municipalities of Tolmin, Kobarid, Bovec. In 2024–2026 the state monitoring sampled 47 water systems of this operator and took 263 samples, of which 17 were not compliant. Water hardness differs between systems, 4.8–13.7 °dH; most customers get soft water (≈7.5 °dH).
These are state monitoring results from 2024–2026, not a notice about the water today. Current notices (boil-water, do-not-use) are published by the water-system operator on its website.
Notices from Komunala Tolmin
Boil-water notices, bans on use and supply interruptions are published by Komunala Tolmin on its website (komunala-tolmin.si) and in local media. This page shows state monitoring results, not current notices. What a boil-water notice means is explained on Boiling water.
Water systems run by Komunala Tolmin
| Water system | Municipalities | Users | Hardness (°dH) | Assessment |
|---|---|---|---|---|
| Zadlaščica | Tolmin | 5,429 | 5.7 | Occasional non-compliance |
| Bovec - Čezsoča | Bovec | 1,929 | 7.8 | compliant |
| Kobarid | Kobarid | 1,489 | 7.6 | compliant |
| Sedlo - Staro Selo | Kobarid | 800 | ≈9.1 | Faecal bacteria in 1 sample |
| Podbrdo | Tolmin | 752 | 6.7 | compliant |
| Šentviška Planota | Tolmin | 677 | 13.7 | Occasional non-compliance |
| Volče | Tolmin | 589 | 7.5 | compliant |
| Kamno - Volarje | Tolmin | 514 | 6.8 | Occasional non-compliance |
| Zatolmin - Dolje | Tolmin | 505 | ≈7.9 | compliant |
| Ladra - Smast | Kobarid | 375 | ≈7 | compliant |
| Idrsko | Kobarid | 355 | ≈7.5 | compliant |
| Žaga 2 | Bovec | 330 | ≈8.7 | compliant |
| Breginj - Logje | Bovec, Kobarid | 315 | ≈8.9 | Occasional non-compliance |
| Slap ob Idrijci | Tolmin | 306 | ≈10.6 | compliant |
| Drežnica | Kobarid | 256 | ≈6.7 | Faecal bacteria in 1 sample |
| Kneža | Tolmin | 213 | ≈9.7 | compliant |
| Koritnica | Tolmin | 179 | ≈8 | compliant |
| Srpenica | Bovec | 177 | ≈6.8 | compliant |
| Čiginj | Tolmin | 176 | ≈8.6 | compliant |
| Podmelec - Klavže | Tolmin | 172 | ≈11.8 | compliant |
| Vrsno - Selce | Kobarid | 155 | ≈7.2 | compliant |
| Grahovo ob Bači | Tolmin | 153 | 10.2 | compliant |
| Livek | Kobarid | 146 | ≈8.4 | Occasional non-compliance |
| Kal Koritnica | Bovec | 145 | ≈6.6 | compliant |
| Trnovo ob Soči | Kobarid | 143 | ≈8.4 | Occasional non-compliance |
| Log pod Mangartom | Bovec | 139 | ≈7.3 | compliant |
| Ljubinj | Tolmin | 138 | ≈9.2 | compliant |
| Soča | Bovec | 130 | ≈7.3 | compliant |
| Sužid | Kobarid | 129 | ≈8.4 | compliant |
| Petrovo Brdo | Tolmin | 126 | ≈7 | compliant |
| Postaja 2 | Tolmin | 122 | 7.4 | compliant |
| Kozaršče | Tolmin | 98 | ≈8.7 | compliant |
| Sela pri Volčah | Tolmin | 89 | ≈8.4 | compliant |
| Svino | Kobarid | 85 | ≈6.9 | Occasional non-compliance |
| Trenta | Bovec | 80 | ≈5.5 | compliant |
| Koseč | Kobarid | 68 | ≈7.3 | compliant |
| Log Čezsoški | Bovec | 56 | ≈6.4 | compliant |
| Hudajužna | Tolmin | 56 | ≈10.6 | compliant |
| Plužna | Bovec | 53 | ≈10.7 | compliant |
| Logaršče | Tolmin | 35 | ≈12.1 | Faecal bacteria in 1 sample |
| Jevšček | Kobarid | 25 | ≈6.7 | Faecal bacteria in 1 sample |
| Stržišče | Tolmin | 24 | ≈7 | compliant |
| Livške Ravne | Kobarid | 21 | ≈10.2 | compliant |
| Robidišče | Kobarid | 13 | ≈7 | compliant |
| Tolminske Ravne | Tolmin | 6 | ≈4.8 | compliant |
| Kal | Tolmin | 4 | ≈7.1 | Faecal bacteria in 1 sample |
| Znojile | Tolmin | 3 | ≈8.1 | Faecal bacteria in 1 sample |
Measured values 2024–2026
| Parameter | Highest value | Against the limit |
|---|---|---|
| E. coli | 8 per 100 mL | limit 0 per 100 mL · 263 samples · 5× over the limit |
| Enterococci | 3 per 100 mL | limit 0 per 100 mL · 263 samples · 2× over the limit |
| Coliform bacteria | >80 per 100 mL | limit 0 per 100 mL · 263 samples · 13× over the limit |
| Clostridium perfringens | 2 per 100 mL | limit 0 per 100 mL · 261 samples · 5× over the limit |
| Nitrate | 7.6 mg/L | limit 50 mg/L · 59 samples |
| Nitrite | below 0.013 mg/L | limit 0.5 mg/L · 59 samples |
| Nitrate/50 + nitrite/3 | 0.15 | limit 1 · 59 samples |
| PFAS, total | below 0.03 µg/L | limit 0.5 µg/L · 2 samples |
| PFOA | below 0.0005 µg/L | part of the 20-PFAS sum, limit 0.1 µg/L · 2 samples |
| PFOS | below 0.0005 µg/L | part of the 20-PFAS sum, limit 0.1 µg/L · 2 samples |
| Arsenic | 0.16 µg/L | limit 10 µg/L · 20 samples |
| Uranium | 0.3 µg/L | limit 30 µg/L · 11 samples |
| Copper | 0.021 mg/L | limit 2 mg/L · 20 samples |
| Nickel | 0.34 µg/L | limit 20 µg/L · 10 samples |
| Cadmium | 0.025 µg/L | limit 5 µg/L · 20 samples |
| Chromium | 0.67 µg/L | limit 50 µg/L · 20 samples |
| Antimony | 0.27 µg/L | limit 10 µg/L · 20 samples |
| Selenium | 0.35 µg/L | limit 20 µg/L · 20 samples |
| Boron | 0.0076 mg/L | limit 1.5 mg/L · 20 samples |
| Fluoride | below 1 mg/L | limit 1.5 mg/L · 58 samples |
| Trihalomethanes, total | 14 µg/L | limit 100 µg/L · 26 samples |
| Haloacetic acids | below 5 µg/L | limit 60 µg/L · 2 samples |
| Chlorate | 0.16 mg/L | limit 0.25 mg/L · 38 samples |
| Chlorite | below 0.05 mg/L | limit 0.25 mg/L · 38 samples |
| Bisphenol A | below 0.025 µg/L | limit 2.5 µg/L · 1 sample |
| Free chlorine | 0.32 mg/L | no limit value · 201 samples |
| Manganese | 1.1 µg/L | limit 50 µg/L · 20 samples |
| Iron | 93 µg/L | limit 200 µg/L · 20 samples |
| Aluminium | 31 µg/L | limit 200 µg/L · 20 samples |
| Ammonium | below 0.02 mg/L | limit 0.5 mg/L · 59 samples |
| Chloride | 27 mg/L | limit 250 mg/L · 59 samples |
| Sulphate | 10 mg/L | limit 250 mg/L · 59 samples |
| Sodium | 1.9 mg/L | limit 200 mg/L · 20 samples |
| pH | 7.1–8.8 | limit 6.5–9.5 · 263 samples |
| Electrical conductivity | 495 µS/cm | limit 2,500 µS/cm · 263 samples |
Non-compliant samples
- · TRNOVO OB SOČI · Coliform bacteria 2 per 100 mL limit 0 per 100 mL
- · ŠENTVIŠKA PLANOTA · Clostridium perfringens 1 per 100 mL limit 0 per 100 mL
- · ZNOJILE · E. coli 2 per 100 mL limit 0 per 100 mL, Coliform bacteria 68 per 100 mL limit 0 per 100 mL
- · KAL · E. coli 8 per 100 mL limit 0 per 100 mL, Coliform bacteria 48 per 100 mL limit 0 per 100 mL, Clostridium perfringens 1 per 100 mL limit 0 per 100 mL
- · JEVŠČEK · E. coli 1 per 100 mL limit 0 per 100 mL, Coliform bacteria 38 per 100 mL limit 0 per 100 mL
- · DREŽNICA · E. coli 2 per 100 mL limit 0 per 100 mL, Coliform bacteria 23 per 100 mL limit 0 per 100 mL
- · LIVEK · Coliform bacteria 4 per 100 mL limit 0 per 100 mL
- · KAMNO - VOLARJE · Coliform bacteria 1 per 100 mL limit 0 per 100 mL
- · ŠENTVIŠKA PLANOTA · Clostridium perfringens 1 per 100 mL limit 0 per 100 mL
- · LOGARŠČE · Enterococci 2 per 100 mL limit 0 per 100 mL, Coliform bacteria 42 per 100 mL limit 0 per 100 mL
- · ŠENTVIŠKA PLANOTA · Clostridium perfringens 1 per 100 mL limit 0 per 100 mL
- · SVINO · Coliform bacteria 5 per 100 mL limit 0 per 100 mL
- · BREGINJ - LOGJE · Coliform bacteria 2 per 100 mL limit 0 per 100 mL
- · ŠENTVIŠKA PLANOTA · Clostridium perfringens 2 per 100 mL limit 0 per 100 mL
- · ZADLAŠČICA · Coliform bacteria 1 per 100 mL limit 0 per 100 mL
- · SEDLO - STARO SELO · E. coli 5 per 100 mL limit 0 per 100 mL, Enterococci 3 per 100 mL limit 0 per 100 mL, Coliform bacteria >80 per 100 mL limit 0 per 100 mL
- · TRNOVO OB SOČI · Coliform bacteria 5 per 100 mL limit 0 per 100 mL
Samples by year
Municipalities
Drinking water in Tolmin · Drinking water in Kobarid · Drinking water in Bovec
What you can do
- Check which system supplies you. The operator is named on your water bill; the address search only shows the nearest sampling points.
- Follow the operator’s notices. Boil-water notices and bans on use are announced by the operator, usually on its website and in local media.
- Mind the building’s own pipes. The samples show the water in the network. In older buildings (before about 1970) let the water run for a while in the morning; an analysis of your own tap can be ordered from NLZOH or another accredited laboratory.
- Filters and softeners. A softener reduces limescale but removes neither bacteria nor other contaminants. A carbon filter improves taste and needs regular replacement. Against bacteria, boil the water as the operator instructs.
- Own wells and springs are not part of the state monitoring; their owner is responsible for them and for testing the water.
- Before buying a property ask whether it is connected to the public supply or has its own source, who the operator is, and look at the operator’s recent notices.
How to read the results
- All samples compliant all samples in this period met the Drinking Water Decree.
- Mostly compliant (municipality) non-compliant samples came only from smaller systems that together supply less than a quarter of the users there.
- Occasional non-compliance individual samples were not compliant on indicator parameters (iron, manganese, turbidity, coliform bacteria), which point to a problem in treatment or the network but are not a health limit.
- Faecal bacteria in 1 sample E. coli or enterococci were found in one sample. That is a serious finding, but a single one; check its date and the later samples.
- Repeated or health-relevant non-compliance faecal bacteria (E. coli, enterococci) in two or more samples, or a health-based chemical limit (nitrate, pesticides, lead, arsenic …) exceeded at least once.
The ratings are a Draga Slovenija summary, not an official NIJZ rating.
Source: NIJZ and NLZOH, mpv.si; latest sample 31 Aug 2026. Processing: Draga Slovenija.
Frequently asked questions
Is the water from Komunala Tolmin safe to drink?
Komunala Tolmin supplies drinking water to 17,780 users in the municipalities of Tolmin, Kobarid, Bovec. In 2024–2026 the state monitoring sampled 47 water systems of this operator and took 263 samples, of which 17 were not compliant. The operator announces current restrictions on use.
How hard is the water from Komunala Tolmin?
Water hardness differs between systems, 4.8–13.7 °dH; most customers get soft water (≈7.5 °dH).
Where does Komunala Tolmin publish boil-water notices?
On its website (https://www.komunala-tolmin.si/) and in local media. A boil-water notice applies until the operator lifts it.