Draga SlovenijaDraga Slovenija

Drinking water: JKP Grosuplje

Occasional non-compliance

JKP Grosuplje supplies drinking water to 37,428 users in the municipalities of Grosuplje, Ivančna Gorica, Dobrepolje, Žužemberk, Šmartno pri Litiji. In 2024–2026 the state monitoring sampled 11 water systems of this operator and took 119 samples, of which 4 were not compliant. Water hardness differs between systems, 14.4–20.5 °dH; most customers get hard water (≈17.2 °dH).

These are state monitoring results from 2024–2026, not a notice about the water today. Current notices (boil-water, do-not-use) are published by the water-system operator on its website.

Samples 2024–202611911 water systems
Non-compliant43.4%
Hardness14.4–20.5 °dHhard
Users37,4285 municipalities

Notices from JKP Grosuplje

Boil-water notices, bans on use and supply interruptions are published by JKP Grosuplje on its website and in local media. This page shows state monitoring results, not current notices. What a boil-water notice means is explained on Boiling water.

Water systems run by JKP Grosuplje

Water systemMunicipalitiesUsersHardness (°dH)Assessment
GrosupljeGrosuplje14,500≈17.5compliant
StičnaIvančna Gorica13,150≈16.9Occasional non-compliance
Dobrepolje - RobDobrepolje3,705≈16.3Occasional non-compliance
Šmarje SapGrosuplje2,808≈18compliant
GlobočecŽužemberk, Ivančna Gorica1,000≈14.4compliant
Debeli HribŠmartno pri Litiji484≈20.5Faecal bacteria in 1 sample
MetnajIvančna Gorica422≈17.5compliant
Velike LipljeneGrosuplje406≈18.6Occasional non-compliance
ŽalnaGrosuplje375≈18.8compliant
SevnikGrosuplje358≈15.9compliant
TroščineGrosuplje220≈18compliant

Measured values 2024–2026

ParameterHighest valueAgainst the limit
E. coli1 per 100 mLlimit 0 per 100 mL · 119 samples · 1× over the limit
Enterococci13 per 100 mLlimit 0 per 100 mL · 119 samples · 1× over the limit
Coliform bacteria>80 per 100 mLlimit 0 per 100 mL · 119 samples · 2× over the limit
Clostridium perfringens6 per 100 mLlimit 0 per 100 mL · 23 samples · 1× over the limit
Nitrate8.9 mg/Llimit 50 mg/L · 24 samples
Nitritebelow 0.007 mg/Llimit 0.5 mg/L · 24 samples
Nitrate/50 + nitrite/30.18limit 1 · 24 samples
Single pesticide (highest)0.052 µg/L (Desetil-atrazin)limit 0.1 µg/L · 2 samples
Pesticides, totalbelow 0.02 µg/Llimit 0.5 µg/L · 1 sample
PFAS, totalbelow 0.03 µg/Llimit 0.5 µg/L · 2 samples
PFOAbelow 0.0005 µg/Lpart of the 20-PFAS sum, limit 0.1 µg/L · 2 samples
PFOSbelow 0.0005 µg/Lpart of the 20-PFAS sum, limit 0.1 µg/L · 2 samples
Lead0.32 µg/Llimit 10 µg/L · 3 samples
Arsenicbelow 1 µg/Llimit 10 µg/L · 14 samples
Uranium0.61 µg/Llimit 30 µg/L · 8 samples
Copper0.0052 mg/Llimit 2 mg/L · 14 samples
Nickelbelow 1 µg/Llimit 20 µg/L · 8 samples
Cadmium0.06 µg/Llimit 5 µg/L · 14 samples
Chromium1.8 µg/Llimit 50 µg/L · 14 samples
Antimonybelow 1 µg/Llimit 10 µg/L · 14 samples
Selenium1.8 µg/Llimit 20 µg/L · 14 samples
Boronbelow 0.01 mg/Llimit 1.5 mg/L · 14 samples
Fluoride0.14 mg/Llimit 1.5 mg/L · 24 samples
Trihalomethanes, total8.2 µg/Llimit 100 µg/L · 12 samples
Haloacetic acidsbelow 5 µg/Llimit 60 µg/L · 2 samples
Tetrachloroethene + trichloroethenebelow 0.2 µg/Llimit 10 µg/L · 2 samples
Free chlorine0.31 mg/Lno limit value · 65 samples
Manganesebelow 1 µg/Llimit 50 µg/L · 14 samples
Iron11 µg/Llimit 200 µg/L · 14 samples
Aluminium23 µg/Llimit 200 µg/L · 14 samples
Ammonium0.026 mg/Llimit 0.5 mg/L · 24 samples
Chloride11 mg/Llimit 250 mg/L · 24 samples
Sulphate13 mg/Llimit 250 mg/L · 24 samples
Sodium6.2 mg/Llimit 200 mg/L · 14 samples
pH7.1–7.8limit 6.5–9.5 · 119 samples
Electrical conductivity626 µS/cmlimit 2,500 µS/cm · 119 samples

Non-compliant samples

Samples by year

029572016: 57 samples, 4 non-compliant’162017: 54 samples, 2 non-compliant’172018: 54 samples, 3 non-compliant’182019: 54 samples, 5 non-compliant’192020: 47 samples, 1 non-compliant’202021: 47 samples, 2 non-compliant’212022: 47 samples, 2 non-compliant’222023: 47 samples, 1 non-compliant’232024: 44 samples, 1 non-compliant’242025: 47 samples, 3 non-compliant’252026: 28 samples, all compliant’26
compliant non-compliant · Samples from JKP Grosuplje systems

Municipalities

Drinking water in Grosuplje · Drinking water in Ivančna Gorica · Drinking water in Dobrepolje · Drinking water in Žužemberk · Drinking water in Šmartno pri Litiji

What you can do

How to read the results

The ratings are a Draga Slovenija summary, not an official NIJZ rating.

Source: NIJZ and NLZOH, mpv.si; latest sample 31 Aug 2026. Processing: Draga Slovenija.

Frequently asked questions

Is the water from JKP Grosuplje safe to drink?

JKP Grosuplje supplies drinking water to 37,428 users in the municipalities of Grosuplje, Ivančna Gorica, Dobrepolje, Žužemberk, Šmartno pri Litiji. In 2024–2026 the state monitoring sampled 11 water systems of this operator and took 119 samples, of which 4 were not compliant. The operator announces current restrictions on use.

How hard is the water from JKP Grosuplje?

Water hardness differs between systems, 14.4–20.5 °dH; most customers get hard water (≈17.2 °dH).

Where does JKP Grosuplje publish boil-water notices?

On its website and in local media. A boil-water notice applies until the operator lifts it.

AI chat

Ask the data, in plain language

The AI chat finds the answer in the official register and shows it with a table you can download and a link into the map. Free; it only needs an account.

For example: Which municipalities issued the most building permits last year?

Open the AI chat

AI chat