Draga SlovenijaDraga Slovenija

Drinking water: Eko-park

Repeated or health-relevant non-compliance

Eko-park supplies drinking water to 21,070 users in the municipalities of Lendava, Črenšovci, Odranci, Turnišče. In 2024–2026 the state monitoring sampled 1 water system of this operator and took 40 samples, of which 4 were not compliant. Water hardness is 9.1 °dH; most customers get moderately hard water (≈9.1 °dH).

These are state monitoring results from 2024–2026, not a notice about the water today. Current notices (boil-water, do-not-use) are published by the water-system operator on its website.

Samples 2024–2026401 water system
Non-compliant410%
Hardness9.1 °dHmoderately hard
Users21,0704 municipalities

Notices from Eko-park

Boil-water notices, bans on use and supply interruptions are published by Eko-park on its website and in local media. This page shows state monitoring results, not current notices. What a boil-water notice means is explained on Boiling water.

Water systems run by Eko-park

Water systemMunicipalitiesUsersHardness (°dH)Assessment
Pomurski vodovod - sistem ATurnišče, Lendava, Črenšovci, Odranci21,070≈9.1repeated non-compliance

Measured values 2024–2026

ParameterHighest valueAgainst the limit
E. coli0 per 100 mLlimit 0 per 100 mL · 40 samples
Enterococci0 per 100 mLlimit 0 per 100 mL · 40 samples
Coliform bacteria0 per 100 mLlimit 0 per 100 mL · 40 samples
Nitrate34 mg/Llimit 50 mg/L · 9 samples
Nitritebelow 0.007 mg/Llimit 0.5 mg/L · 9 samples
Nitrate/50 + nitrite/30.68limit 1 · 9 samples
Single pesticide (highest)0.15 µg/L (Metolaklor ESA)limit 0.1 µg/L · 10 samples · 4× over the limit
Pesticides, total0.12 µg/Llimit 0.5 µg/L · 4 samples
PFAS, totalbelow 0.03 µg/Llimit 0.5 µg/L · 3 samples
PFOAbelow 0.0005 µg/Lpart of the 20-PFAS sum, limit 0.1 µg/L · 3 samples
PFOSbelow 0.0005 µg/Lpart of the 20-PFAS sum, limit 0.1 µg/L · 3 samples
Arsenicbelow 1 µg/Llimit 10 µg/L · 8 samples
Uranium1.3 µg/Llimit 30 µg/L · 5 samples
Copper0.013 mg/Llimit 2 mg/L · 8 samples
Nickelbelow 1 µg/Llimit 20 µg/L · 5 samples
Cadmiumbelow 0.1 µg/Llimit 5 µg/L · 8 samples
Chromiumbelow 1 µg/Llimit 50 µg/L · 8 samples
Antimonybelow 1 µg/Llimit 10 µg/L · 8 samples
Selenium1.3 µg/Llimit 20 µg/L · 8 samples
Boron0.018 mg/Llimit 1.5 mg/L · 8 samples
Fluoridebelow 0.1 mg/Llimit 1.5 mg/L · 9 samples
Trihalomethanes, total2.1 µg/Llimit 100 µg/L · 6 samples
Haloacetic acidsbelow 5 µg/Llimit 60 µg/L · 3 samples
Chloratebelow 0.01 mg/Llimit 0.25 mg/L · 3 samples
Chloritebelow 0.01 mg/Llimit 0.25 mg/L · 3 samples
Tetrachloroethene + trichloroethenebelow 0.2 µg/Llimit 10 µg/L · 7 samples
Free chlorine0.11 mg/Lno limit value · 34 samples
Manganese3.1 µg/Llimit 50 µg/L · 8 samples
Iron10 µg/Llimit 200 µg/L · 8 samples
Aluminiumbelow 10 µg/Llimit 200 µg/L · 8 samples
Ammoniumbelow 0.013 mg/Llimit 0.5 mg/L · 9 samples
Chloride28 mg/Llimit 250 mg/L · 9 samples
Sulphate27 mg/Llimit 250 mg/L · 9 samples
Sodium14 mg/Llimit 200 mg/L · 8 samples
pH6.5–7.4limit 6.5–9.5 · 40 samples
Electrical conductivity586 µS/cmlimit 2,500 µS/cm · 40 samples

Non-compliant samples

Samples by year

09182018: 15 samples, all compliant’182019: 18 samples, all compliant’192020: 17 samples, all compliant’202021: 15 samples, all compliant’212022: 15 samples, all compliant’222023: 15 samples, all compliant’232024: 15 samples, 3 non-compliant’242025: 15 samples, 1 non-compliant’252026: 10 samples, all compliant’26
compliant non-compliant · Samples from Eko-park systems

Municipalities

Drinking water in Lendava · Drinking water in Črenšovci · Drinking water in Odranci · Drinking water in Turnišče

What you can do

How to read the results

The ratings are a Draga Slovenija summary, not an official NIJZ rating.

Source: NIJZ and NLZOH, mpv.si; latest sample 31 Aug 2026. Processing: Draga Slovenija.

Frequently asked questions

Is the water from Eko-park safe to drink?

Eko-park supplies drinking water to 21,070 users in the municipalities of Lendava, Črenšovci, Odranci, Turnišče. In 2024–2026 the state monitoring sampled 1 water system of this operator and took 40 samples, of which 4 were not compliant. The operator announces current restrictions on use.

How hard is the water from Eko-park?

Water hardness is 9.1 °dH; most customers get moderately hard water (≈9.1 °dH).

Where does Eko-park publish boil-water notices?

On its website and in local media. A boil-water notice applies until the operator lifts it.

AI chat

Ask the data, in plain language

The AI chat finds the answer in the official register and shows it with a table you can download and a link into the map. Free; it only needs an account.

For example: Which municipalities issued the most building permits last year?